Advanced Coal Fired Power Plants


2x800 MW class reference plant
Single Line Diagram and Principles
2x800MW - Reference Plant
Single Line Diagram
E0 1 REFERENCE PLANT - 2 x8 0 0 MW with turbine drive n pum p Powe r Tu rb o -Syste m s
     Electrica l BO P

SINGLE LINE DIAGRAM

This do cu me nt is the exclusive prope rty of ALSTO M a nd sh a ll not be used, copie d or commun ica te d to third pa rtie s without the ir prior a uthoriza tio n
O PTIO N
LO CAL
N ETWO RK HV NETWO RK
HV NETWO RK

MAINTENANCE

Ce docume nt proprié té d' ALSTO M ne doit pa s ê tre utilisé , copié o u co mmuniqué à de s tie rs sa ns son a utorisa tion
TRANSFO RMER
5 MVA
GENERATO R
TRANSFO RMER GEN ERATO R
3 x ...MVA TRANSFO RMER
EHV/ 2 6kV

0 9 LGA 10 kV STATIO N SWITCHBO ARD (B0 5 )


UNIT AUX. G
UNIT AUX. UNIT AUX.
G
CO S = 0 .8 5 0 9 LGB 1 0kV STATIO N SWITCHBO ARD (B0 5 ) TRAN SFO RMERS ~
~ 6 0 Hz 2 6 kV TRAN SFO RMER 2 6 kV TRANSFO RMER
2 6 kV

1 0 .5kV 10 .5 kV 1 0 .5kV 1 0 .5 kV

01 LGC0 1 0 1 LG C0 2 BFWP1 BFWP2


BFWP1 BFWP2 4 2 0V
0 1 LGA 1 0 kV TURBINE HALL & BO ILER SWBD (B1 0 ) 0 2 LGA 1 0 kV TURBINE HALL & BO ILER SWBD (B1 0)
0 1 LGB 1 0 kV TURBIN E HALL & BO ILER SWBD (B1 0 ) 4 0 0 V 0 9 LKH (B0 5 ) 0 2 LGB 1 0 kV TURBINE HALL & BO ILER SWBD (B1 0 )

CO AL HANDLING

420V 420V 4 2 0V 7 2 0V
7 2 0V 4 2 0V 420V 420V
4 0 0 V 0 1 LKC (B1 3 ) 6 9 0 V 0 1LKH (B1 3 )
6 9 0 V 0 9 LKD (G 05 ) 4 0 0V 0 9 LKB (G0 5 ) 4 0 0 V 0 9LKE (---)
4 0 0 V 0 1 LKE (B1 3 ) 0 1 LKB 4 0 0 V (B1 1 )
ESP SWBD ESP SWBD
0 1 LLB EMERGENCY SWBD 8 00 kVA FGD SWBD
UNIT 2
STATIO N SERVICES WATER TREATMENT
ASH HAN DLIN G BO ILER SWBD
400V SWITCHBO ARD SWITCHBO ARD (O PTIO N) IDENTICAL TO UNIT 1

720V 4 20 V G
~
0 2 LLP
NO RMAL EMERGENCY
LIGHTING LIGHTING 4 0 0V 3 Ph + PEN 01 LLD
BO ILER MO V
PEN
0 1 LKI 69 0 V (B10 ) 0 1 LKA 4 0 0 V TURBINE SWBD (B1 0) 0 1 LLA 4 0 0V EMERGENCY SWBD 4 0 0 V 0 1 LLP (B1 0 ) 0 9 LLA 4 0 0 V GEN. EMERGEN CY SWBD 0 9 LKA (B0 5 ) 40 0 V
TURBINE SWBD EMERGENCY SWBD GEN AUX SWBD

M
~ M
~ UPS
90kW< P< 350kW P< 90kW

NO RMAL EMERGENCY ~ ~ EMERG ENCY NO RMAL


LIGHTING LIGHTING = = LIGHTING LIGHTING
~ ~
= =
400V 3Ph + PEN 01LLC = UPS = UPS ~ ~
~ ~ = = UPS UPS
TURBINE MO TO RIZED = =
~ ~
VALVES
~ ~
= =

01LBA 110V DC 01LNA 230 V UPS 01LNC 2 30V UPS 01LNB 230V UPS 01LND 230V UPS 09LBA 110V DC 230V UPS 09LN A 230V UPS 09LNB
TURBINE BO ILER TURBINE BO ILER

~ ~ ~ ~ ~ ~
= = = = SAFETY = =
SWITCHBO ARDS
STARTING

24V DC 01LCC 24V DC 01LCD SWITCHBO ARDS LIGHTING 24V DC 09LCA 24V DC 09LCB
CUBICLE

CO NTRO L 24V DC O 1LCA 24V DC 01LCB


CO NTRO L CO NTRO L
DC

& DC PO WER & DC PO WER RO O M


AUXILIARIES AUXILIARIES

M UNIT 1 AUXILIARIES GENERAL AUXILIARIES


~
DC EMERGENCY
MO TO RS
2x800MW - Reference Plant
Main equipment per unit

 Generator transformer: 3 single phase transformers


– high MVA rating of the generator transformer (about
950MVA),
– limited number of potential sub-suppliers able to
manufacture so large 3-phase transformers,
– difficulty of transportation and handling of large 3-phase
transformers
– tap changer type : off-circuit
2x800MW - Reference Plant
Main equipment per unit
 Unit auxiliary transformers : 2 identical 3-windings
transformers
– same rating
– one winding dedicated to one boiler FWP (or possibly
another large motor), to ensure a good starting
– on-load tap changer
– possibility to provide a spare unit auxiliary transformer
2x800MW - Reference Plant
Main equipment per unit

 Generator circuit-breaker : the benefits are many


– starting from the HV network through GT and UAT’s:
• no need of HV bay for the starting transformer
• no MV change over necessary after synchronization
– better protection selectivity: in case of generator faults, only
the GCB is tripped. No need to transfer the auxiliaries.
– better protection of the main transformer: in case of
transformer fault, it is isolated faster.
– easier operation during commissioning and maintenance
periods, thanks to the possibility to separate the generator
and the transformers
– 2 experimented potential manufacturers: Areva and ABB
2x800MW - Reference Plant
Main equipment per unit

 Phase isolated busbars


– naturally air cooled (In~23000A, suitable for natural cooling)

 MV distribution:
– two 10 kV switchboards per unit, in the turbine electrical
buildings
– connection from UAT by cables
2x800MW - Reference Plant
Main equipment per unit

 LV distribution:
– « radial » type
– one switchboard for turbine hall auxiliaries, in the turbine electrical
building
– one switchboard for boiler auxiliaries, in the boiler electrical building
– decentralized switchboards for other plants

 Emergency LV diesel generator : one per unit, designed for


the essential auxiliaries of one unit + common

 UPS and DC systems


– production: in the unit electrical building
– distribution as necessary (boiler), and production of 24VDC locally
2x800MW - Reference Plant
Main equipment for station auxiliaries

 One maintenance transformer of limited size (5MVA


typically), as option
– used during unavailability of unit power transmission
equipment

 MV distribution
– Two 10 kV switchboards, in the central electrical building
– supplied from Unit 1 or 2
2x800MW - Reference Plant
Main equipment for station auxiliaries

 LV distribution
– 1 switchboard, in the central control building
– decentralized switchboards for FGD, WTP, coal, ...

 UPS and DC systems


– production: in the central control building,
– distribution: decentralized necessary
2x800MW - Reference Plant
Operation

 Normal operation:
– each pair of UAT supplies the unit auxiliaries
– the common auxiliaries are supplied by either unit
 Starting:
– from the HV network through the main transformer and the
unit auxiliary transformers, with the generator CB open
– no starting transformer
2x800MW - Reference Plant
Operation

 Normal shutdown:
– opening of the generator CB
– supply of the auxiliaries from the HV network
 Emergency shutdown:
– the emergency diesel set supplies the essential unit
auxiliaries
– the essential common auxiliaries are supplied from unit 1 or
unit 2
2x800MW - Reference Plant
Standards and Voltage Levels

 Generally, IEC standards are applied for design and tests


 One MV level: 10 kV for motors > 300kW
– lower voltage is not possible due to the high rated power of the boiler
FWP (~13MW)
 690V for motors > 90kW & <= 350kW
 400V for motors <= 90kW, MOV’s
 110V DC for control voltage, solenoid valves, DC motors
 230V AC UPS single phase for DCS ALSPA P320
 24V DC for DCS interfaces, transmitters
2x800MW - Reference Plant
MV Switchboards

 MV switchboards
– withdrawable type, metal-clad, IP 30
– air insulated cubicles
– outgoing feeders: circuit-breakers or fuse-contactors, SF6
or vacuum
– digital protection relays
– digital measuring units, connected to DCS ALSPA P320
through Modbus link
 MV/LV transformers
– dry type, indoor, naturally air cooled
– close to the LV switchboards
2x800MW - Reference Plant
LV Switchboards

 LV switchboards
– withdrawable type, IP 31
– PMCC type: no separate PCC and MCC. Advantages: smaller electrical
rooms and less switchboards
– incomers and busties: air circuit-breakers
– motor feeders: fuse-contactors
– sub-distribution feeders: fuse-switches
– auxiliary control voltage: 110V DC, thus control voltage always
available whatever the disturbances on LV network. Very good
feedback from many projects, standardized interfaces with DCS P320.
 Distribution panels (MOV’s, lighting, UPS, DC, …)
– fixed type
2x800MW - Reference Plant
Miscellaneous

 Motorized valves with integrated contactors, supplied from


fixed type distribution panels. Advantages :
– Smaller size of switchboards and electrical rooms
– Less I&C cabling

 Emergency lighting:
– Supplied from the emergency diesel generator
– Ensures about 20% of normal lighting and participates to normal
lighting

 Safety lighting:
– Supplied from the 110 V DC system
– Dedicated to the control room
2x800MW - Reference Plant
UPS and 24V DC systems

 For each unit and the station auxiliaries, two redundant UPS,
including:
– 2 dedicated batteries, 1 hour autonomy per switchboard, lead acid type,
– 2 battery chargers, naturally air cooled,
– 2 inverters, naturally air cooled,
– 1 bypass transformer,
– a set of static switches,
– 2 independant distribution boards
 24V DC systems :
– supplied from UPS
– no dedicated batteries,
– 2 sets of redundant modular 230V AC/24V DC converters
– 2 independant distribution boards
Production principle
P320 system auxiliary power supplies
REFERENCE PLANT- PET 350MW/700MW/800MW
UPS and 24V DC systems
2x800MW - Reference Plant


   
Ele ctrical BO P
Pow e r Tu rbo -Syste m s

Ce d o cume nt p roprié té d' ALSTO M ne d oit pa s ê tre utilisé , copié ou comm un iq ué à de s tie rs sa ns son a utorisa tion
This do cum e nt is th e e xclusive prope rty of ALSTO M a nd sha ll no t be use d, copie d or com munica te d to third p a rtie s witho ut the ir p rior a utho riza tion
2x800MW - Reference Plant
110V DC system

 For each unit and the station auxiliaries, one 110V


DC system, including:
– 1 dedicated battery, 1 hour autonomy, lead acid type,
– 2 battery chargers, naturally air cooled,
– 1 subdistribution board
2x800MW - Reference Plant
110V DC system

M a n d sh a ll n o t be u se d , co p ie d o r co m m u n ica te d to th ird p a rtie s with o u t th e ir p rio r a u th o riza tio n


REFERENCE PLANT PET 3 50 MW - 7 00 MW - 80 0 MW      Po w e r
Electrica l & Control Systems

1 10 V DC distribution prin ciple

M n e d o it p a s ê tre u tilisé , co p ié o u co m m u n iq u é à de s tie rs sa n s so n a u to risa tio n


UNIT 1 GENERAL AUXILIARIES UNIT 2

NO RMAL LV DISTRIBUTIO N EMERGENCY LV DISTRIBUTIO N NO RMAL LV DISTRIBUTIO N EMERGENCY LV DISTRIBUTIO N NO RMAL LV DISTRIBUTIO N EMERGENCY LV DISTRIBUTIO N
4 00V AC 01LKA 4 00 V AC 0 1LLA 4 00 V AC 0 9LKA 40 0V AC 09LLA 4 00V AC 02 LKA 4 00 V AC 02 LLA
M M M

110 V DC 110 V DC 1 10V DC


1h 1h 1h

40 0V 40 0V 4 00V 400 V 400 V 4 00V


~ ~ ~ ~ ~ ~

1 10 V DC 1 10 V DC 110V DC 1 10 V DC 1 10 V DC 110V DC

1 1 0V DC 01LBA 11 0 V DC 09 LBA 1 10V DC 02LBA

Ce d o cu m e n t p ro p rié té d ALSTO
Th is d o cu m e n t is th e e xclu sive pro p e rty oALSTO
f
'
SWITCHBO ARD CO NTRO L SWITCHBO ARD CO NTRO L SWITCHBO ARD CO N TRO L
DC MO TO R AN D DC PO WER AND DC PO WER DC MO TO R AN D DC PO WER
STARTER SAFETY STARTER
AUXILIARIES " UNIT 1 AUXILIARIES " UN ITS 1 & 2 AUXILIARIES " UNIT 2
LIGHTING
CHANNEL 2 CHANNEL 1 CHANNEL 2
SUPPLY " SUPPLY " SUPPLY "

DC EMERGENCY DC EMERGENCY
M M
= MO TO R = MO TO R
www.alstom.com

You might also like