Professional Documents
Culture Documents
Voltage Drop Calculation
Voltage Drop Calculation
MARIMON, PERIAS,
CALCULATION RAMA
INTRODUCTION TO VOLTAGE
DROP
occurs when load current flows through a
conductor or transformer having a finite
impedance.
results in lower-than-normal values of
system voltage at a given point in the
power system.
(decrease in electrical potential)
INTRODUCTION TO VOLTAGE
DROP
Lower-than-normal voltage may cause:
Motor Failures
Dropout of Motor Starters
The torque is proportional to the square of the
supply voltage.
Therefore, if the voltage drops the starting torque
will also decrease, making it more difficult to start
up motors.
INTRODUCTION TO VOLTAGE
DROP
Lower-than-normal voltage may cause:
Motor Failures
Dropout of Motor Starters
The torque is proportional to the square of the
supply voltage.
Therefore, if the voltage drops the starting torque
will also decrease, making it more difficult to start
up motors.
Dimming of Lamps
FACTORS THAT CAUSE
VOLTAGE DROP
System Impedances
Line (Conductor) Impedances
Transformer Impedances
System Loads
Length of Conductors and Distance of Loads
Motor Starting
SUBTOPICS TO BE DISCUSSED:
Voltage Tolerance
Voltage Drop Defined
Cable Impedances
Transformer Impedances
Application in Electrical System Design
VOLTAGE TOLERANCE
VOLTAGE TOLERANCE
The actual voltage in any power system will deviate from nominal due to voltage
drops in the system.
By ANSI Standard C84, the actual service voltage must lie within:
For low-voltage systems (< 1000V), ±5% of nominal
For medium-voltage systems (up to 35kV), -2.5% and +5% of nominal
Quick Bits: This is why we see 100-125V or 220-240V in some power supplies. This
is to accommodate the variations of voltage due to voltage drop.
EXAMPLE 1
Calculate
the allowable service voltage range for a 120/240 V, single phase, three-
wire service.
Solution:
For Lower Range For Higher Range
EXAMPLE 2
Calculate
the allowable service voltage range for a 480Y/277 V, three phase, four-
wire service.
Solution:
For Lower Range For Higher Range
VOLTAGE DROP
DEFINED
EQUIVALENT CIRCUIT FOR
VOLTAGE DROP
CALCULATIONS
Equation (16-1)
DERIVING VOLTAGE DROP
EQUATION
(16-1)
Therefore, the voltage dropped () due to line impedance () is:
(16.2)
Equation (16-4)
CABLE IMPEDANCES
IMPEDANCE TABLE
The cable impedances are determined
based on the tables given by:
the manufacturer,
the National Electric Code (per 1000 ft) or
the Philippine Electric Code (per 305 m)
For Parallel Conductors: Simply divide and by the number of conductors per phase.
THREE-PHASE VOLTAGE DROP
line-to-neutral voltage drop, from equation 16-3:
For
Solution:
From the table: the resistance is 0.029 ohm/1000 ft and the reactance is 0.048 ohm/1000 ft
Therefore:
For L-N Voltage Drop:
Solution:
From the table: the resistance is 0.029 ohm/1000 ft and the reactance is 0.048 ohm/1000 ft
Therefore:
For L-N Voltage Drop:
Solution:
From the table: the resistance is 2.0 ohm/1000 ft and the reactance is 0.068 ohm/1000 ft
Therefore:
For L-N Voltage Drop:
Percentage:
TRANSFORMER
VOLTAGE DROP
TRANSFORMER EQUIVALENT
CIRCUIT & EQUATION
𝑉𝐷 = VD
𝑉𝐷=
|𝑰 𝐿𝑆|×[ 𝑅𝑇𝑅 ×cos ( 𝜃 ) − 𝑋 𝑇𝑅 ×sin (𝜃 ) ] % ×100 %
𝐕
| LS|
Equation (16-10) Equation (16-11)
TRANSFORMER IMPEDANCES
]
]
If transformer percent impedance (%) and X/R ratio is given:
Solution:
=312.3A
EXAMPLE 7A:
Determine the voltage drop
50 kVA, 480-120/240 V, 1-Phase TX, 1.3 %R, 1.7%X
Operating at Full Load, Unity Power Factor
Solution:
=208.3A
EXAMPLE 7B:
Determine the voltage drop
50 kVA, 480-120/240 V, 1-Phase TX, 1.3 %R, 1.7%X
Operating at Full Load, 0.8 lagging power factor
Solution:
=208.3A
EXAMPLE 7C:
Determine the voltage drop
50 kVA, 480-120/240 V, 1-Phase TX, 1.3 %R, 1.7%X
Operating at Full Load, 0.8 leading power factor
Solution:
=208.3A