Where
Area = Area of the room
Lux level = illuminance level as per standards
MF = Maintenance factor
UF= Utilization factor
Lumen of lamps =luminous flux of lamp(amount of light lamps is radiating)
Let’s start from bedroom-1
According to formula
Now,
Area of bedroom-1 = 3.6m x 3.3m = 11.88 m2
Lux level for bedroom = 200
Maintenance factor = 0.8 (A.C room)
Room Index = (L x B)/(L + B) x H = 2.006 ~ 2
=0.68
Utilization factor = 0.37
( consider 40W lamp with efficacy 100 lm/W)
Lumens of Lamp = 100 * 40 = 4000
Calculation of Circuit Breakers
I = 2.35 A
But MCB are selected for rated current includes 25% safety factor.
Therefore IR= 1.25 I
IR = 1.25*2.35 = 2.9 A
Therefore, the next standard MCB is 3A.
Calculation of Exhaust Fan