Professional Documents
Culture Documents
Condensation
BUILDING SERVICES & ENVIRONMENTAL
SCIENCE
Condensation
Objectives and Content
Objectives Content
● Humidity
● Condensation in buildings
● Structural temperature gradient
● Dew point temperature gradient
● Interstitial condensation risk
● Minimising condensation risk
Humidity
Moisture in the air, or humidity, influences the heat balance and comfort of the
human body, the durability of building materials and also causes condensation in
buildings
Air always contains some water vapour (wv) ie has humidity. The amount of water
that can be present in air is related to the ambient temperature. Warmer air can
contain more moisture than cooler air. When the upper limit of wv is reached, the air
is saturated.
The actual amount of wv in the air relative to the maximum saturation level is the
relative humidity (RH). The temperature at which air is fully saturated (ie at 100%
RH) is the dew point temperature. If the temperature falls below the dew point
temperature, the air cannot contain all the wv present and some wv will condense
into a liquid (ie condensation will occur).
Water vapour is a gas, suspended in air. It exerts a pressure which increases with
wv content and/or temperature. The pressure exerted by the molecules of wv
contained in the air is the vapour pressure. Pressure and temperature differentials
will cause warm, humid air to diffuse to colder areas, colder surfaces and permeate
colder structures, leading to cooling of the air and possible condensation.
Humidity: Definitions
The amount of moisture in a given sample of air can be specified using a number of
different variables:
1) Vapour pressure - The pressure exerted by the molecules of water vapour
contained within the air. Units: Pascals (Pa)
2) Saturated vapour pressure - Vapour pressure which would be given by
saturated air at a specific temperature. (Units Pa)
3) Dew point temperature - The temperature at which a sample of air with a given
moisture content becomes saturated. (Units: oC)
4) Moisture content - The actual quantity of water vapour in a given sample of air.
(Units: g/kg of dry air)
5) Relative humidity - Quantity of water contained within a given sample of air
expressed as a percentage of the maximum quantity of water which could be
contained within that air at that temperature. (Units: %RH at temp. in oC)
CIBSE recommend that for most applications, the relative humidity should be
between 40% and 70% for human comfort.
Humidity: Sources of
Table 1.12 in the ASHRAE Journal (January, 2002) shows the amount of
moisture produced from a variety of sources.
In addition, building materials will absorb moisture from the environment. This
moisture will then be released back into the atmosphere when the internal
conditions allow it.
Humidity: Sources of (Cont.)
Humidity: Psychrometric Chart
The variables used to specify the amount of water vapour (wv) in the air are
interrelated. The relationships can be shown graphically in a Psychrometric Chart.
One version of this type of chart is shown below:
Saturation curve
Shows the combination of temperature and moisture
content at which the air is saturated, i.e. RH of 100%.
The temperature at which saturation occurs is the Dew
Point Temperature. The curve is also known as the
Dew Point curve.
Examples:
1. What is the vapour pressure of air which
is at 20oC and has a relative humidity (RH)
of 60% ?
1400 Pa
1800 Pa
Example
If we have air at 20OC and 50% RH (point A) all the
moisture can be held in the air. If more
water vapour is introduced into this air and
the temperature of the air remains
constant, the RH of the air will increase. If
the RH is increased to 100% (saturation
point) point B, then any additional water vapour
that is introduced into this air will be
deposited as condensation. If on the
other hand, the amount of water vapour in B
the air remains constant but the
temperature of the air falls, the RH of the
air will rise because the cooler air can
support less moisture. If the air is cooled
to around 10OC, the RH will rise to 100%
(saturation point) point C and any further
cooling will cause the water vapour C A
within the air to condense.
Condensation in Buildings
1) Surface - occurs on surfaces of the building envelope which are at or below the
dew point of the air immediately adjacent to them
2) Interstitial - occurs within or between the layers of the building envelope when
the temperature of some part of the structure within the building envelope equals
or drops below the dew point temperature.
Therefore:
a) Materials which have the highest thermal resistances will have the
steepest temperature gradients.
b) Materials with the lowest thermal resistances will have the shallowest
temperature gradients.
High R Low R
The boundary temperatures between the individual layers of the building fabric
can be determined from the thermal resistances which make up the U-value of
that element.
The boundary temperature at any point within a building element can be predicted
using the following equation:
where
= temperature difference across a particular layer (oC)
= total temperature difference across the structure (oC)
= resistance of that layer (m2K/W)
= total resistance of the structure (m2K/W)
1. Find the inside surface temperature of an external wall which has a U-value of
1.8 W/m2K, when the internal temperature is 21OC and the external temperature
is -1OC. Rwall = 0.123m2K/W, Rsi = 0.123m2K/W, Rso = 0.055m2K/W
Solution:
Total temperature drop across the wall
Using:
The vapour resistance (RV) describes the ease with which a material will permit
the diffusion of water vapour.
where
= vapour resistance of the material (GNs/kg)
= vapour resistivity of the material (GNs/kg m)
= thickness of the material (m)
The total vapour resistance (RVT) of a multi-layered element is the sum of the
vapour resistances of all of the separate components.
Vapour Resistivity
The vapour resistivity of a number of materials can be seen below.
where
= vapour pressure drop across a layer
= vapour resistance of that layer
= total vapour pressure drop across the structure
= total vapour resistance of the structure
If the structural and dew point temperature gradients are drawn on the same
scaled diagram and compared, the points at which the structural temperature falls
below the dew point temperature will indicate a risk of interstitial condensation
occurring.
Interstitial Condensation Risk Analysis – (Prob. 5.3)
Use a scaled cross section diagram of the wall to plot the structural temperature
gradients and the dew point gradients, like this:
Example 5.3 – (Handout, Page 114)
Data:
Wall Thickness
LPlasterboard = 10 mm = 10/1000 = 0.01 m
LExp. Poly. Board (EPS) = 25 mm = 25/1000 = 0.025 m
Xconcrete (dense) = 150 mm = 150/1000 = 0.15 m
Thermal Resistance
RSi = 0.123 m2 K/W
RPlaster Board = 0.06 m2 K/W
REPS = 0.75 m2 K/W
RConcrete (Dense) = 0.105 m2 K/W
RSO = 0.055 m2 K/W
Vapour Resistivity
RVSi = negligible (very small, - MN s/g m)
RV1 (Plaster) = 50 MN s/g m
RV2 (EPS) = 100 MN s/g m
RV3 (Concrete) = 30 MN s/g m
RVSO = negligible (very small, - MN s/g m)
Temperatures
TInside (T1) = 200C ……………….. 59% RH ………. (1400 Pa)
Interstitial Condensation Risk Analysis – (Solution)
Step 1: Use the thermal resistances to calculate the temperature drop across
each layer and the temperature at each boundary.
Item
Thermal resistance Temperature drop Boundary temperature
Rn Layer R (m2K/W) Δθ(ºC) (ºC)
Inside air - - 20
Rsi Internal surface 0.123 ([0.123/1.093) *20) = 2.3 -
Boundary - - 17.7
R1 Plasterboard 0.06 1.1 -
Boundary - - 16.6
R2 EPS 0.75 13.7 -
Boundary - - 2.9
R3 Dense concrete 0.105 1.9 -
Boundary - - 1.0
Rso External surface 0.055 1.0 -
Outside air - - 0.0
RT = 1.093 θT = 20
Interstitial Condensation Risk Analysis
(Solution Continue)
Step 2: Use vapour resistances to calculate the vapour pressure drops across
each of the layers then, using the psychrometric chart, find the dew point
temperature at each boundary.
Step 4: Plot the dew point temperatures on the scaled, section diagram and
produce a dew point gradient.
In walls constructed from permeable materials, water vapour can pass through the
structure, and evaporate from the outside surface.
Vapour barriers should be fitted to the warm side of the structure to minimise
vapour penetration.
Minimising Condensation Risk: Design
There are a number of ways in which good design can prevent the occurrence of
condensation within buildings. The factors that should be considered during the
design process are:
(2) Ventilation Increasing the ventilation rate will help to remove the moist air within the
building. Ventilation will be most effective if it is near the source of
moisture generation. Care should be taken to avoid excessive ventilation as
this will have an energy penalty.
(3) Heating Heating a building will raise the internal surface temperatures, keeping
them above the dew point temperature of the air inside the building. Care must
be taken to prevent excessive heating as this will not only incur an energy penalty,
but may also raise temperatures above comfort conditions. If heating is
intermittent, more continuous heating will raise internal surface temperatures and
structural temperatures, thus reducing the condensation risk.
Insulation Insulating the building envelope will help to raise the internal surface
(4) temperatures of the building.
References
BSI (2005) BS 5250: Code of Practice for Control of Condensation in Dwellings. London: British Standards
Institution.
BURBERRY, P. (1997) Environmental Services 8th Edition. Mitchell’s Building Construction Series
CIBSE (1999) Volume A Design Data, 5th Edition. London: Chartered Institution of Building Services Engineers
CIBSE (2004) Guide to Energy Efficiency, London: Chartered Institution of Building Services Engineers
CIBSE (2006) Energy Assessment and Reporting Methodology, London: Chartered Institution of Building
Services Engineers
CIBSE (2007) , Environmental Design Guide A, London: Chartered Institution of Building Services Engineers
CIBSE (2007 a) Sustainability Guide, London: Chartered Institution of Building Services Engineers
DEFRA (2005) The Government’s Standard Assessment Procedure for Energy Rating of
Dwellings 2005 Edition, Watford: BRE
JOHNSTON, D. (2009) GHA monitoring programme – Phase 1. Report Number 1 – Draft Co-heating Testing
Proposal Leeds: Leeds Metropolitan University
RIBA (2007) Low Carbon Standards and Assessment Methods London: Royal Institute of British Architects
UK Green Building Council (2007) Report on Carbon Reductions in Non-Domestic Buildings London: DCLG
WINGFIELD, J. BELL, M. MILES-SHENTON, D. LOWE, B. and SOUTH, T. (2007) Interim Report Number 7 –
Co-heating tests and Investigation of party Wall Thermal Bypass. Partners in Innovation Project: CI 39/3/663.
Leeds: Leeds Metropolitan University.