Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec A.8.17.4.2
• E. valves
N. Test valve cont.

A N
S S
H A
L I
. A
N G
E
Fire Fighting Tech. For You  Refer to NFPA 20-2013ed-sec A.6.3.1
• E. valves
O. Pressure Relief Valves

A N
S
Remarks :

A S
Shall be installed with diesel drive
pump when 121% of shutoff (churn)

I H
pressure plus static pressure exceed.
component rating pressure.

A L Shall be installed between the pump

G . and discharge check valve.

E N
Fire Fighting Tech. For You  Refer to NFPA 20-2013ed-sec4.18.1.2
 Refer to NFPA 20-2013ed-sec4.18.3
• E. valves
P. Pressure Reducing Valve (PRV)

A N
Remarks :

S S
A
I. In portions of systems where all
P1
H
P2 components are not listed for
pressure greater than 175 psi (12.1

L I bar) and the potential exists for


normal water pressure in excess of

A
175 psi (12.1 bar), a listed pressure-
P2 < P1

G . reducing valve shall be installed.

N
II. Used with fire hose cabinet to avoid

E
exceeding the maximum permissible
pressure.

Fire Fighting Tech. For You  Refer to NFPA 13-2013ed-sec 8.16.1.2


• F. Water flow alarm devices
Flow switch
N
Water motor &Gong

A
S S
H A
L I
. A
N G
E
Fire Fighting Tech. For You