You are on page 1of 18

SineWave

Installation recommandations
Ref N° 51027000YB ind AA

Update: June 8th 2010


Written by Claudine PIN
Checked by Pascal CHAPUIS

All content in this presentation is protected – © 2008 American Power Conversion Corporation
Site audit
A site audit is important in that it helps avoid technical and commercial problems in
subsequent phases.

The major points dealt with:


● Identification of needs (remember, not all problems are related to harmonics).
● Definition of goals with the customer.
● Measurement of harmonics in the installation (if possible).
● Preparation of a single-line diagram (sources, protection, loads, cable lengths, etc.).
● Selection of SineWave installation points.
● Floor space and volume available for installation.
● Installation of protection circuit breakers, taking into account discrimination with
upstream circuit breakers.
● Installation of sensors in the switchboards, taking into account the need to de-
energize.
● Evacuation of heat losses
● Zones sensitive to noise and vibrations

APC by Schneider Electric – Sinewave Installations Recommendations – Date: June 8th 2010
Installation constraints

 Provide at least 300 mm for evacuation of hot air

 No adjacent heat sources

s in e w a v e

 Temperature of incoming air must be < 40°C


25°C advised because service life decrease as
temperature
increase
 No heat sources under the unit
Heat (windings, transformers, power resistors, etc.)
source
 Provide a clearance of at least 300 mm for air input
 Provide sufficient space for maintenance

APC by Schneider Electric – Sinewave Installations Recommendations – Date: June 8th 2010
Installation constraints

 Do not install two SineWave units one above the other on a


s in e w a v e

wall (the top unit will draw hot air produced by the bottom
unit)

s in e w a v e

APC by Schneider Electric – Sinewave Installations Recommendations – Date: June 8th 2010
Installation constraints in a cabinet
 Do not use a cabinet rated IPx1x or IPx2x (plain roof)
 Allow for the free flow of hot air (vented roof)

 Install a deflector between the two units (standard option)

 Provide sufficient air input for cooling (> 2000 m 3 / hr)


 Provide sufficient space for maintenance

APC by Schneider Electric – Sinewave Installations Recommendations – Date: June 8th 2010
Environmental constraints

s in e w a v e

 Do not install SineWave in a closed space


(unventilated technical duct, false ceilings, etc.)

s in e w a v e

APC by Schneider Electric – Sinewave Installations Recommendations – Date: June 8th 2010
Environmental constraints (cont.)

 Do not install SineWave in areas with conducting or


aggressive dust (e.g. containing hydrocarbons) such as parking
lots, road tunnels, etc.)

s in e w a v e
 Do not install SineWave in rooms with high levels of dust
(SineWave degree of protection is IP205, protected against
particles > 5 mm)

 Periodically clean the ventilation grates (depending on the


level of dust)

APC by Schneider Electric – Sinewave Installations Recommendations – Date: June 8th 2010
Sensor selection
CB1
! System performance is guaranteed on the condition that the
sensors are approved and supplied with the SineWave used
CB2

 SineWave is normally supplied with open CT (or APC split


P1
toroids) 600/1 rating.
P2 T E R M IN A L B L O C K
s in e w a v e

 Open CT (or APC split toroids) rated 2000/1 are also


available as an option.

 The other recommended ratings are available in closed CT (or


APC closed toroids)

 The sensor rating depends on the RMS value and the peak
value of the load currents requiring processing ! Always use the
rating indicated in the selection table or
the next highest rating (see Appendix in the CDST)

APC by Schneider Electric – Sinewave Installations Recommendations – Date: June 8th 2010
Short-circuit protection

CB1
 Selection of protection devices depends on local standards
(breaking capacity, system earthling arrangement, neutral
CB2
protection and interruption, etc.)

 ! Computer loads, I_neutral <= 3 x I_phase (IH3)

s in e w a v e

A discrimination study is required


(CB2 must open before CB1)

 If discrimination is not ensured, select a lower SineWave


rating (parallel connection) or install a faster protection system
(ultra fast fuses)

! 90 A and 120 A SineWave units must be protected by two


circuit-breakers (one per 45 A or 60 A power module)

APC by Schneider Electric – Sinewave Installations Recommendations – Date: June 8th 2010
Installation of the sensors 1/2

CB1

 The sensors must always be installed downstream of the


CB2 SineWave connection point

P1
 The sensors must be correctly installed (see the manual)

 The wires of each sensor must be twisted and marked


P2 T E R M IN A L B L O C K
s in e w a v e

 Do not connect the secondary windings to the exposed


conductive parts ( S2 connected to 0V and the neutral)

 Sensor wires must not run close to power conductors

 Sensors can be supplied and installed before the SineWave


units (short-circuitable terminal block is indispensable)

 The CT twist wire have to be well twisted , especially if there


is one conncetion terminal between CT twist wire.
If the connection is not good,the condition will affect CT
sampling precision
APC by Schneider Electric – Sinewave Installations Recommendations – Date: June 8th 2010
Installation of the sensors 2/2
PointA

Ic
In the case it’s impossible to install
P1 P2
Source sensors in normal installation point, it’s
Is P2
If
possible to use combination of
P1 sensors in other place in the installation:
SineWave
USE the SAME SENSOR.
(see CDST)
Is+If=Ic CCTY, PARY,
TIFY

PointA Point A

P2 P2

S1 S2 S1 S2
P1 P1

CCTY,PA
RY, TIFY
source Sinewave
APC by Schneider Electric – Sinewave Installations Recommendations – Date: June 8th 2010
Sinewave + passive-filter combination

Ls
Source Loads

Lf

H5 AHF Cf

s in e w a v e

 Install the current sensors downstream of the passive filter tuned to H5

Do not condition H5

Remark:
IF AHF is design for another harmonic (for instance:H7) do not condition this
other harmonic (for instance:H7)

APC by Schneider Electric – Sinewave Installations Recommendations – Date: June 8th 2010
Capacitors for power-factor correction

Ls
3Ph
S o u rc e Loads

3Ph

C C

s in e w a v e

Power-factor correction capacitors must always be connected upstream of


the SineWave connection point.
If it’s not possible to move capacitors upstream the Sinewave or if the
capacitors are included into the load, the type 6 setup must be selected

APC by Schneider Electric – Sinewave Installations Recommendations – Date: June 8th 2010
Specific loads (lighting load)

S o u rc e
Ls
C o m p e n s a te d
lig h t in g
 Do not condition lighting with a
compensated ballast : (very capacitive
load, risk of resonance with Ls)

s in e w a v e

Ls
S o u rce
D im m e r w /o
s m o o t h in g in d u c t o r  Do not condition variable-speed
drives without a smoothing inductor
(unstable load). Addition of an inductor
reduces harmonic pollution by half
s in e w a v e

APC by Schneider Electric – Sinewave Installations Recommendations – Date: June 8th 2010
Setup

 Except in special cases, the band width should be reduced to a strict minimum.
For most applications, it can be limited to H13 and even H9

Type 2 must never be used (risk of serious malfunctions),


Type 2 only for tests in the factory

 Except in special cases, filtering should not be used (+32, +64, +96)

In the case of several SW are installed in the same place (same building),
a start up delay must be added with setup menu in order to delay start up
SW by SW
 step about 10s.
This is to avoid auto instability between SW when Network Power is coming back.

APC by Schneider Electric – Sinewave Installations Recommendations – Date: June 8th 2010
Neutral connection
S o u rc e
Ls
3Ph + N
Loads  Connect the neutral to SineWave and set
3Ph + N
SineWave to "neutral distributed" if this
is the case, whatever the type of load
conditioned (computers, variable-speed
drives, etc.)
s in e w a v e

Remark: Current reading done on the 3 sensors installed

Ls
3Ph
 Set to "neutral not distributed" if the neutral is
S o u rc e

3Ph
Loads
not distributed.
! An inductor must be installed in the unit
(option) to recreate an artificial neutral.
! Following setup is mandatory:
To remove all H3 and multiple odd harmonic (to
s in e w a v e

remove H3, H9, H15 & 21)

Remark: Current reading done only on the 2 sensors installed phase 1&2,
current phase 3 created by the software.
APC by Schneider Electric – Sinewave Installations Recommendations – Date: June 8th 2010
"Cascading" installation of conditioners
● Avoid cascading configuration ● Conditioners are recommended to be
The risk is some regulation interference between installed at the same electrical
Conditioners Up to conditioner issue : shutdown installation level.
or damage
Source Load 1

SW Downstream

s in e w a v e
SW1

Load 2

Source Load 1

s in e w a v e
SW1 s in e w a v e
SW2

Load 2

Source Load 1

s in e w a v e
SW2

Load 2
s ine w a ve
sin e w a v e
SW1&2

SW Near the Source

APC by Schneider Electric – Sinewave Installations Recommendations – Date: June 8th 2010
SW Installation with 2 CT
The 2 CT are placed:
● One upstream measuring source current
● One downstream measuring conditioner current

● The current IF and IH: ● The current IF and IH:


● IF is not sinusoidal wave ● The inject point is moved to the front of all A + B + C
● IH is a very big harmonic current for filler A+B+C
● low risk to cause resonance
● some risk to cause resonance in path C

APC by Schneider Electric – Sinewave Installations Recommendations – Date: June 8th 2010

You might also like