Induction-Motor Starting: - Connect Directly Across Full-Voltage Using A Contactor For Each Phase
Induction-Motor Starting: - Connect Directly Across Full-Voltage Using A Contactor For Each Phase
ECE 441 1
Full-Voltage Starting
ECE 441 2
Reduced-Voltage Starting
• Autotransformer starting
ECE 441 3
“S”, or “start” contactor – close to start the motor at a
reduced voltage – the autotransformers are set to 50, 60,
or 80 percent of full-voltage.
At rated speed, open the S contactors and close the “R”,
or run contactors – apply full voltage.
ECE 441 4
After coming up to speed, “Running”
ECE 441 5
Example 5.18
ECE 441 6
Example 5.18 continued
ECE 441 7
Example 5.18 Solution
Tn T (1141)
P 125
5252 5252
Trated 575.37lb ft
Check Table 5.1 for the minimum locked-
rotor torque for a 125-hp, design B, six-
pole motor
Tlr ,460 125%(Trated )
Tlr ,460 1.25(575.37) 719.2lb ft
ECE 441 8
Example 5.18 Solution continued
6.3 7.1
6.70kVA / hp
2
ECE 441 9
Example 5.18 Solution continued
ECE 441 10
Example 5.18 Solution continued
ECE 441 11
Example 5.18 Solution continued
ECE 441 12
Example 5.18 Solution continued
2 2
V2 0.65 460
T2 T1 719.2 303.9lb ft
V1 460
ECE 441 13
Current Curves
ECE 441 14
Locked-Rotor Torque Curves
ECE 441 15
The in-rush line current