Emergency Handling

In Mills-Stage II
Whenever any Mill trips
• Take oil support in running Mill

• Take out machine from CMC

• Control secondary air through


Boiler

• Reduce Burner tilt if it is more


than +12 deg,
to increase flame stability.
• Increase main air flows through
running Mill

• Reduce Load reference to control


Turbine
Throttle pressure from falling

• Monitor Drum level control &


FRS DP

• Start APH soot blowing.


Whenever any one Mill discharge
valve close indication appearing

Example:When Mills AB/CD are in service

• If any one discharge valve close limit acts


and open goes off in Elevation B, Elevation
• Take oil support in Mill AB
• Do not give start command to elevation A
• Get the problem attended ( limit switch/card
• Take elevation A
henever any one feeder tripped for a M
 Example:When Mills AB/CD are in
service and
feeder C tripped
• Take oil guns in CD elevation
• Reduce air in C Elevation to maintain mill
outlet
temperature and mill coal level.
• If feeder is not starting back,Keep the oil
support and
change over Mill
Whenever any Mill grease
sequence
is not healthy
Grease pump is in service
• Bypass grease sequence healthy protection if
rectification takes more than 15 minutes
• Immediately start manual greasing
• Get the greasing sequence rectified
Grease pump is not in service
• If pump not start back immediately
A) Simulate Grease pump running indication
B) Bypass Grease sequence healthy protection
• Immediately start manual greasing
• Get the grease pump starting problem rectified
The condition Girth Greasing
Sequence OK
• Grease pump motor is on
• Time between two successive limit
switch activation
is< 2mts
• Grease atomizing air pressure is correct
2 sec after
energizing the solenoid valve
Whenever Mill lube oil filter
DP high alarm appear

• Confirm from PMS/Event log,whether the


alarm is from LP
pump or reducer pump
• Put the respective standby pump also into
service and
changeover lube oil filter and clean the
choked one
a) Reducer flow low trip actuates if flow is
<45 LPM
and pressure is <0.75 ksc--[2FS &
1PS])--2/3 logic
b) LP flow trip actuates if end flow is <20
LPM
Whenever Mill lubrication trouble
alarm appears

• Confirm from PMS/Event log


a)In case LP pump, change over to
cleaned standby filter
b)Check for sufficient LP lube oil temp
after cooler
(around 45 deg).If less,decrease cooler
water flow
to get sufficient LP flow at each end of
the Mill
c)Maintain lube oil tank temp. around 50
deg C
d)In case of Reducer pump,change over
to cleaned
stand by filter to increase flow as well
as pressure
(Normal pressure 2.0 ksc/flow 65 lpm )
case of HP pump, change over pump and observe
ischarge pressure.(Normal 50ksc/Alarm20 ksc/
ip 17 ksc)
ufficient Lp pump before filter pressure( around 8
ank temp.(around 50 deg.)
ank level
Whenever any seal air fan trips and its
discharge valve not closed

• Running seal air fan tripped on over


loaded.
 Reduce seal air DP( around 350 mmwc)

 Reduce particular mill end airflow

 Reduce PA Header pressure

• Take oil gun in other running Mill


• Immediately close suction damper of
tripped seal air fan
from local (to avoid backflow of seal air)
• Incase Mill trips on seal air header
pressure very low
follow steps mentioned in case of mill
tripping.
Whenever any Mill current
starts hunting
• Mill current start hunting by around 10A
whenever stones
are getting filled in the mill through feeder.
It is observed
 Mill current comes down by few amperes

for half an hour.


 Current reaches around 200A

 Noise level comes down


 Mill level goes up

• Start mill purging (Keep mill noise level


constant by
regulating feeder speed in manual)
• After few hours of purging, Mill current
and noise level
improves gradually. Increase feeder speed
gradually.
• If Mill current does not come down even
after prolonged
never any running Mill PA General inl
got closed (due to failure of I/P conve

• Follow steps mentioned in case of mill


tripping.
• Reduce feeder speed/stop feeder if Mill
level going very
high
• Get the PA General gate problem
attended ,also open it
and normalize milling system and take
out oil support
Whenever any Mill main Primary
air damper flow starts hunting

• Say, when Mill AB/CD are in service ,end


'C' main air flow
starts hunting
• To avoid tripping of elevation 'D' on
ignition energy when
end 'C' air flow comes below 12 TPH, take
oil support in
mill CD
• Get the flow feedback problem attended
otherwise Change
over mill from CD to EF
henever any ID fan / PA Fan /FD fan tr
• During this condition top Mill trips
• Follow steps mentioned in case of mill
tripping.

enever any Mill Motor bearing tempera


ng high

ntact EMD to provide external air cooling for bea


Bearing temperature gets controlled,Inform MTP
d the cause
bearing temperature hunting (RTD problem) info
bypass the protection and tighten RTD.
enever any ESP Transformer /Coal M
CC -A trips

• When ESP Transformer -A is


tripped,Coal mill MCC-A
section -A becomes dead and Girth gear
greasing pumps
of Mill AB/CD/EF are tripped
• Simulate girth gear greasing pump
running indication if
supply normalization expected to take >
15 minutes
• Bypass girth gear greasing sequence
protection
• Start manual greasing with the help of
BMD
FIRE IN BALL & TUBE
MILLS
Reasons for fire:
• Entrapment of foreign material in ribbon
conveyor thus breaking the connecting rods
resulting in pulverized coal accumulation in the
screw area leading to fire.
• One end operation of mill without slight opening
of the damper on non-operating end. This may
result in coal dust accumulation on non-operating
end and consequently fire will start.
• Ball and coal dust accumulation in hot air box
(dead zone) resulting in fire.
• Non-functioning of mill level Delta “P”
(choking of tubes) resulting in uncontrolled raw
coal feeding to mill and choking the mill.
•  Accumulation of pulverized coal near the
closed PF purge damper
Avoiding Mill Fire

• Breakage of Tie rods is a possibility due to which


PF can accumulate in screw conveyor zone. Mill
should be taken into shutdown and maintenance
should take up the repair works.
• Steam inerting at the time of starting and stopping
the mill
• Mill should not be run without coal feeding to the
mill for more than 10 minutes
• Both ends of the mill should be kept in service
• Purging of mill for 10 minutes every time, before
stopping.
• If a mill is stopped without emptying coal,Keep
aux motor in service for a minimum of 4 hrs
Detection of mill fire:
• Abnormal rise in mill outlet temperature.
Interlock And Protection
Mills Stage - II
LP PUMP INTERLOCKS
The selected LP pump gets start command
when LP compartment
lub oil level is not low and Start PB is pressed.

The LP pump gets Stop command –If :


The stop P.B is pressed. OR
 The pump is in Operation for>60s AND Oil
flow is low (20<LPM) for >5s OR
LP compartment oil level is not
adequate(<250MM)
The Standby LP pump gets start command
if the selected p/p does not start within 5s OR
if the running pump is ON for>60s AND Oil
flow is low
HEATER ELEMENTS

The heater is energized if


the Lub oil temp is
low(40deg) AND any LP
pump is ON and de-
energized if lub oil temp is
High(45deg) OR If both LP
pumps are OFF
INTERLOCKS
AND PROTECTION
Start Permissives:
 Any LP pump is ON
 Lub Oil pressure in feeding line is not
low(>0.2ksc)
 Lub oil temp adequate(42deg)
HP pump starts when ON PB is pressed
OR If the other pump is On for >5s AND
discharge pressure is low(<17ksc)
The selected HP pump gets a Stop
command when:
 -The stop PB is pressed
 -Both LP pumps are OFF
 -Any HP pump discharge pr is low
and that pump is On >10s
The standby p/p is started on auto if the
selected p/p does not start within 5s
B&S PUMPS
INTERLOCKS AND
 Start permissives: PROTECTION
-Any LP pump is ON
 -Lub Oil pressure is not low
 -Lub oil temp adequate
B&S pump start PB pressed OR If the other
pump is On for >5s AND discharge pressure is
low(<12ksc) for >2s
The selected B&S pump gets a Stop command
when
 -The stop PB is pressed
 -Both LP pumps are OFF
 -Any B&S pump discharge pr is low >2s
and that pump is ON >10s
The standby p/p is started on auto if the
selected p/p does not start within 5s
REDUCER P/P INTERLOCKS
AND PROTECTION
The selected Reducer pump gets start
command when the following conditions are
present:
Red pump start PB is pressed OR If the
other pump is On for >10s
AND Red flow is low(40LPM)[2/3 Logic both
flow and Pr<0.75]
•The selected Red pump gets a Stop command
when
The stop PB is pressed
 Any Red pump flow is low >5s and that
pump is ON >10s
•The standby p/p is started on auto if the
selected p/p does not start within 5sec
GIRTH GEAR
GREASING
SYSTEM
Girth Gear Greasing System gets start
command with any of the following
commands:
Automatically when main or Aux motor is
started.
Automatically when aux motor is ON and
grease pump is
stopped for >10min
By pressing start PB
The greasing system gets stop command
either
Manually through the stop PB when both
Main& Aux Motorsare OFF OR
Automatically 30s after the main and aux
motors are OFF OR
Automatically after 5 min of running of
grease pump when Aux motor is ON
GIRTH GEAR
GREASING SYSTEM
The condition Girth Greasing Sequence OK
is generated if all the following conditions are
present:
• Grease pump motor is on
• Time between two successive limit switch
activation is< 2mts
• Grease atomizing air pressure is correct 2
sec after energising the solenoid valve.
The condition Girth Greasing Sequence NOT
OK If :
• Air pressure low for more than 2 sec
while energizing the
solenoid valve OR
• The absence of any of the above
conditions
Greasing Sequence Not
Correct
Both Grease
p/p off

End limit switch not acted


> 2 min >= Greasing seq not correct

End limit switch acted and


air pressure low within 3
sec

Note : When aux motor is on , grease pump runs for 5 min and remains off for 10
min.During this 10 min
period if it is required to take mill in service then either aux motor should be turned
grease pump should be
started so that mill lub OK permissive is available.
MILL
LUBRICATION
‘Mill lubrication OK’ is generated if:
Any LP pump on
AND
Oil flow in LP circuit OK
AND
Any HP pump on And pr not low
AND
Greasing sequence correct
AND
Any reducer pump on
AND
Reducer lube oil temp not high
AND
Reducer lube oil flow not low
AND
> Any B&S pump on And pr not low
Mill Lubrication
Correct

Red Lub OK

Mill Lub Correct


Brg Lub OK
&
Greasing Seq OK

B&S Pump On & disch pr. Not low


>=1
Mill Lubrication Not
Correct

Red Lub
not OK
Brg Lub not OK >= Mill Lub Not
Correct
asing Seq not OK for 15 min
Mill Red OK

Any pump on>10 sec

Red oil temp<90 deg C Red lub OK


&
Red Flow
>40 LPM

Red Lub Not


OK
Red oil temp>90 deg C
> 10 sec

Red flow s/w 1<40 lpm 10 sec delay

Red flow s/w 2<40 lpm


2/3 >= Red Lub
Red disch pr < 0.75 KSC
not OK
Both p/p off >10 sec
Mill Brg Lub OK

Hp disch > 17Ksc

Any HP
p/p on Mill Lub OK
Oil flow >20 lpm &
Any LP
p/p on

Mill Brg Lub not


OK

Both LP off> 1sec

Both HP off> 1sec

Oil flow < 20 lpm for 3 >= Mill Lub not


sec
HP disch pr <17
OK
ksc for 2 sec
GIRTH GEAR
SEAL AIR FAN

GG seal air fan A starts up


 manually by pressing start PB
 automatically when mill start sequence
first step is completed.

GG seal air fan B starts up


 manually by pressing PB
 automatically when fan A fails to start or
tripped.

GG seal air fan stops


 manually by pressing PB
 automatically 30sec after both main and
aux motors are off.
TRUNNION SEAL
The selected sealAIR
air fanFANS
gets start command
if:
 Start PB pressed.
 Mill start order AND mill starting sequence
first step completed AND any side all mill
outlet gates are open.
 The selected seal air fan is shut down if:
 Mill main motor is off for > 30 sec
OR
 Seal air fan on for > 60 sec AND
 Seal air pressure not OK For>10sec
OR
 Stop PB pressed
The stand by seal air fan is started on auto if:
 Any seal air fan on for > 60 sec AND Seal
air pressure low for>5 sec OR
 The selected seal air fan is not started
within 5 sec
OR
 The running fan trips
GRAVIMETRIC FEEDER
PERMISSIVES
 

A MILL MAIN MOTOR ON

B NO MFT IS CHANNEL 1,2


&3
C FEEDER IN REMOTE

D MILL RELEASE
AVAILABLE

E FEEDER O/L GATE OPEN


F MILL – OUTLET TEMP
O.K.
G ALL MILL O/L GATE
OPEN
H FEEDER – I/L GATE OPEN
I BUNKER – O/L GATE
OPEN
Feeder protections
Sl Descriptions Value Remarks
no

1 Feeder – On And Feeder >20s


O/L Gate Closed.

2 MFT 2/3 Logic

3 All Mill O/L Gate Closed

4 Main motor Off

5 Feeder – ON And NO >1.7min


COAL ON BELT

6 Loss Of 24V DC

7 MFT HARD
WIRED
8 Ignition Energy Not
available
RAW COAL
FEEDER
RC feeder is started when
 Respective feeder start PB is pressed
OR
 Through mill start sequence if
1.Mill release available AND
2.Mill outlet temp on side NDE OK AND
3.Mill outlet gates on side NDE open AND
4.Bunker O/L gate open and feeder inlet
gate open AND
5.Mill start order side NDE AND
6.Step-4 in mill start up sequence
completed
RC feeder is stopped if
 Respective feeder stop PB is pressed
 Feeder stop command from mill stop sequence
 MFT
 Feeder on for >20 sec and feeder outlet gate not
opened
 Feeder on and no coal flow for> 100 sec
 Mill main motor off
 Mill O/L gates closed(side-NDE)
 Loss of 24 V DC in mill section
MILL MAIN MOTOR
PERMISSIVES
NO MFT AT CHANNEL 1,2
A
&3

B MILL LUBRICATION
CORRECT
MILL ELEV. IGNITION
ENERGY AVAILABLE (AT
C ANY
ELEV.CORRESPONDING
TO THAT MILL)

ELECTROMAGNETIC
D BRAKE RELEASED

MILL AUX. MOTOR OFF.


E

F PURGE AIR DAMPER NDE


& DE CLOSED

G MILL TO SEAL AIR DP OK


AND ANY TRUNION SA
FAN ON > 10 SEC.
COAL MILL
PROTECTIONS
Sl Description Value rem
N arks
o
1 A.Mill Lub Not Ok(LP FLOW NOT <20
OK DELAY OF 3SEC) LPM

B. All lube oil (LP pump) TRIP with


01 sec Delay
C. HP Pressure Low- Delay Of 2 Sec <17
KSC.

D. RED Lub Oil Flow Delay Of 10 Sec < 40


LPM

E. RED Lube Oil temp HIGH Delay > 90


of 10 seconds Deg

F. Greasing Sequence Not Ok More


Than 15
Minutes
F. RED Lube oil Temp V.HIGH >90 Tem
Deg p
swit
ch
Sl Description Value remark
No s

2 Mill De/NDE Brg. Temp > 55deg 10sec


60 Deg alarm Delay

3 Motor De/NDE Brg. Temp 95deg 10sec


> 100 Deg alarm Delay

4 Trunnion Seal Air Fan Off


For >30 Seconds

5 Centrifuge Safety Device


Acted
6 Seal Air to Mill DP Not <300 mm Press
O.K> 01 Minute <250 wcl switch
mmwcl and
tx(2/3)
7 Ignition Energy Not
Available
8 Emergency Trip
9 MFT Trip 2/3 Logic Hardwi
red
Sl Description Value
remark
No s
10 PA Header Pressure Low/Both <450m Press
PA Off <350mmwcl mwcl switch
ALAR (2/3)
M
11 Four elevations in service and
any PA/ FD fan TRIP top two
elevations will TRIP

12 Both Feeders OFF >10


Minutes(First feeder starts
after main motor START and
both feeder OFF for> 10
minutes)
13 Electromagnetic Brake
Engaged
14 Auxiliary motor On

15 24 V Dc Supply Failure Hardwi


red
COAL ELEVATION / TUBE
MILL
STARTING OF TUBE MILL SIDE-NDE WHEN DE IS
NOT IN SERVICE
 Mill release available
 PA permit available
 Coal burners main shut off gates open
 Purge air shut off gates open
When elevation start PB is pressed it is brought into service
in the following 5 steps
Step-1
 PA general shut off gate closed
 PA bypass control dampers closed (side NDE & DE)
 PA to mill control dampers closed (side NDE& DE)
 Purge air dampers closed (side NDE &DE)
 Feeder outlet gate closed(NDE&DE)
 Mill outlet gates closed (side NDE &DE)
 Start order ( side NDE & DE)
Step-2
 Purge air dampers of side NDE & side DE gets open
command
 If purge air dampers are opened and mill outlet gates
are closed, a 60 sec purge timer is started ,after that:
 PC pipes purging mill and classifiers are inerted with
steam for 240 sec and closing of steam inerting valves
after 240 sec.
 Starting of girth gear seal air fan
 Opening of NDE side mill outlet gates
 Starting of any one trunnion seal air fan
Step 3
 Establishing girth gear greasing system when the
mill main motor is on.
 Mill main motor starting if all the conditions for
mill main motor are present and mill auxiliary
motor is stopped before starting of main motor.
Step 4
 PA general shut off opening cold PA shut off gate
is opened
 Opening of feeder outlet gate of side NDE
 Hot and cold air dampers of NDE side are
released to AUTO
 Bypass and air to mill control dampers of side
NDE are released to AUTO
Step-5
 If the mill outlet temp is correct ,the feeder on the
selected side is started
 As the feeder is on a command feeder set point at
filling value is given to auto controls for rapidly
filling the mill 30 sec later if the coal level in the
mill is representative and mill DP value is more
than adequate ,the feeder is released to auto
operation
STARTING OF MILL-SIDE –NDE
WHEN MILL SIDE DE IS IN
SERVICE
This can be done if the mill outlet gates of side
NDE are closed
AND
Mill side NDE is selected on manual in three
steps as stated below
Step-1&3:
Bypassed
Step-2:
 PC pipe purging of side NDE
 Opening of mill outlet gates of side NDE
Step-4:
 Opening of side NDE feeder outlet gates
 Hot and cold airdampersof NDE side are
released to AUTO
 By pass and air to millcontroldampers of
sideNDEare releasedtoAUTO
Step-5:
 If the mill outlet temp is correct the feeder
on side NDE is started as mentioned earlier
 Starting of mill side DE when mill side NDE
is in service
COAL MILL ELEVATION /
TUBE MILL SHUT DOWN
SHUT DOWN OF MILL SIDE NDE WHEN
SIDE DE IS IN SERVICE
If elevation of stop PB is depressed the
following will occur:

Side NDE feeder gets stop command and


the feeder speed control is set to manual
mode

Feeder outlet gate on side NDE closes

Mill outlet gates on side NDE closes

PA to mill & bypass air control dampers on


side NDE opens

PC pipes purge air dampers on NDE side


opens

10 min after PC pipes purging,purge air


dampers are closed
SHUT DOWN OF MILL SIDE NDE
WHEN SIDE DE IS NOT IN SERVICE
If elevation stop PB is depressed the
following will take place:
Instantaneously:
Feeder on side NDE will stop and feeder speed control is
set manual mode
Raw coal gate on side NDE closes
After 10 min:
PA to mill bypass control & Pa to mill control damper closes
PC outlet gates on side NDE closes
PA general inlet shut off gate closes
Mill main motor is stopped
Aux motor is started
PC pipes purging on side NDE starts i.e. Purge air damper on
side NDE open
After 20 min:
Purge air dampers on side NDE closed
TUBE MILL MAIN
MOTOR
MILL MOTOR GETS START COMMAND IF
PC pipes purge shut off dampers closed
AND
Mill start order(side NDE / DE)
AND
Mill release available comprising of
 electromagnetic brake is in open position
 mill lubrication is OK
 no MFT
 mill ignition energy available
AND
Girth gear seal air fan motor is on
AND
Mill starting sequence step-2 completed
AND
Any trunnion seal air fan on and mill/seal DP OK
THE MAIN MOTOR GETS TRIP
COMMAND IF ONE OR MORE OF
THE FOLLOWING CONDITIONS
EXISTS:
 MFT
 Centrifugal safety device acted
 Mill lubrication not correct
 Mill bearing temp very high
 Mill motor bearing temp very high
 PA pressure very low
 Mill/seal air DP not OK>60 sec
 Mill ignition energy not available
 Electromagnetic brake engaged
 Both trunnion seal air fans off>10 sec
 Aux. Motor on>10 sec
 Mill emergency trip PB activated
 Loss of elev. 24 V DC power
Elevation –A Start
sequence
RELEASE
REQUIRED

Purge air shut off damper


open
Mill lubrication
correct
PA fan permit

Elev-A release
NO MFT for start
Ch-1
NO MFT
&
Ch-2
NO MFT
&
Ch-3

Electromagnetic brake
released
Mill AB ignition energy
available
All end-A manual coal o/l
gate open
PA FAN PERMIT
PA hdr pr low

Any PA fan ON

Any FD fan
ON &
2 or more elevn in
service
& PA
permit
OR
Both PA ON

Both FD ON
&
Both BFP
ON
TUBE MILL IGNITION
PERMISSIVES
Elevation-A
• ¾ Nozzle valves proven in AB.
OR
• Elev B airflow >22 T/Hr AND BLI >30%
Elevation-B
• ¾ Nozzle valves proven in AB.
OR
• Elev A or C airflow > 22 T/Hr AND BLI >30%

• ¾ Nozzle valves proven in CD AND Elev.C Airflow > 22


T/Hr

Elevation-C
• ¾ Nozzle valves proven in CD.
OR
• Elev B or D airflow > 22 T/Hr AND BLI >30%
OR
• ¾ Nozzle valves proven in AB AND Elev.B Airflow > 22
T/Hr
TUBE MILL IGNITION
PERMISSIVES

Elevation-D
¾ Nozzle valves proven in CD
OR
Elev E or C airflow > 22 T/Hr AND BLI >30%
OR
¾ Nozzle valves proven in EF AND Elev.E Airflow > 22 T/Hr
Elevation-E
¾ Nozzle valves proven in EF.
OR
Elev D or F airflow > 22 T/Hr AND BLI >30%
OR

¾ Nozzle valves proven in CD AND Elev.D Airflow > 22 T/Hr


Elevation-F
¾ Nozzle valves proven in EF
OR
Elev E airflow > 22 T/Hr AND BLI >30%
Elev A Ignition permit
not available

¾ HONV not
open Elev ign
BLI<30% & permit NA
Air flow endB<11T/hr >=
End B any o/l gate >=
closed
ELEV B IGN PERMIT
AVAILABLE

Elev C air flow>22 T/h

Elev CD ¾ HONV open &


BLI > 30% Elev B ign
permit
Elev C air flow>22 T/h & >= available
>
Elev A air flow>22 T/h

Elev AB ¾ HONV open


ELEVATION B IGN
PERMIT NOT
AVAILABLE
BLI <30%

End –A any o/l gate closed

>= >=
End-A air flow <11TPH
& Ign
not
End-C any o/l gate availa
closed ble
>= &
End-C air flow <11TPH Elev AB ¾ HONV not open

Elev CD ¾ HONV open

Elev C air flow>22 T/h &


Elevn-A Start (Elevn-B
not in service)
Step-1 Commands
a)PA gen inlet gate close
b)Purge air damper end-A close
c)Mill o/l gate end-A close
d)Purge air damper end-B close
e)Mill o/l gate end-B close
f) Feeder outlet gate end-A &B close.

Above all drive’s


close limit

Main air damper Close STEP-1


Complete
limit &
Bypass air damper
Close limit
Step-2 :Commands
Purge Air damper end-A open

Purge air
damper end-A Close purge air
limit switch Delay damper
open 1min
Pre light up purge
complete

Steam Delay Steam


inerting
inerting
start 4min complete
command

STEP-2
COMPLETE

Pre light up purge


complete
Step-2 Complete
&
Steam inerting
complete
STEP-3 Commands

a)Blow down sequence start


b)GG seal air fan start

STEP-3
COMPLETE

Any reducer p/p


ON
Step-3 complete
Any GG SAF ON &
STEP-4 Commands

a)Mill outlet gates End-A open


b)All end-A outlet gates
limit switch open SEAL AIR FAN
& START
Step Order
c)main motor ON /Aux motor
OFF( Note: Main motor will start only if Seal air
fan is ON and SA DP is OK>250mmwcl)
d)PA gen gate open( Note: PA gen inlet gate
will open only when motor is ON and cold PA shut
off gate is OPEN)
e)Start Grease pump

STEP-4 Complete
PA gen inlet gate limit
switch open
Aux motor OFF STEP-4
COMPLETE
Main motor ON
&
SEAL Air FAN ON
End-A all outlet gate open
limit switch
STEP-5 COMMANDS

a) Feeder-A outlet
gate open
b) Start feeder –A
(Feeder will start
only when >

Feeder-A outlet gate open


limit switch FEEDER-A
Mill outlet temp & ON
>50deg

STEP-5
COMPLETE

Feeder-A outlet gate open


limit switch
STEP-5
Feeder-A ON & Complete
ELEVATION-A START
(When B in service)
Step-1 is bypassed
Step-2
a)Purge air damper open(Purging
will continue for 1min)
b)Steam inerting will not take
place.
ELEVATION A Stop sequence
(When B not in service)
PB/VPC stop
command
End-A outlet gates
closed
Main motor
OFF

Elevn-A
shutdown
EM Brake command
engaged OR

MFT 2/3

OR
Mill AB ign energy not available

Mill lub not OK


STEP-51

COMMANDS
Feeder off command

After 10 min Aux motor ON


PA Gen Gate closed

Main motor
OFF
All mill outlet gates
end-A close
After 14 min Purge air
damper open
Feeder-A OFF
Feeder-A outlet
gate closed
Mill outlet gates
end-A closed
Purge air damper end-
A opened STEP-51 complete

Elev-A ign energy not OR &


available
Main air damper closed

Bypass air damper


closed
Main motor OFF
• STEP-52
• Purge air damper remains open
for 10 min
• Completed:
Elev-A ign energy not
available
Step-52
10min elapsed after OR completed
STEP-52 initiation

STEP-53
Commands:
• Puge air damper close
Completed :
Purge air damper end-A close
limit
STEP-54
SHUTDOWN SEQ completed
Elevation-A Stop sequence (When
B is in service)
• STEP-51
• Commands:Feeder-A OFF
End-A mill outlet gates close
Purge air damper open end-A(Only when all
outlet gate are closed)
Completed:

All above
conditions
STEP-51
complete
STEP-52 End-B outlet &
gates open
Purging for
10 min Main
Complete &bypass air
dampers
After 10 min close end-A

STEP-53 Commands : End A purge air damper


close
Completed : Purge air damper End-A
close limit

STEP-54 : Shutdown complete


Elevation tripping on
loss of FD/PA/BFP
Any PA OFF

Any FD
OFF OR
Any BFP
OFF
Trip
& elevation
F
3 or more elevation in
service
Trip
Delay
elevation E
2s

Trip
Delay elevation
4s D

Trip
Delay
elevation C
6s
Thanks