BOILER-1 & 2
1. ID Fans (A,B):
• ID Trip.
• ID Failed to start.
• Motor Winding temperatures High High i.e >140Deg C with 5sec Delay
• Motor & Fan Bearing temperatures High High i.e > 95Deg C with 5sec Delay
• Scoop oil I/L temp High High i.e > 100Deg C with 5sec Delay
• Scoop oil O/L temp High High i.e > 100Deg C with 5sec Delay
• Any one Scoop Lube oil pressure <0.6 Kg/Cm2. During fan startup this interlock
will come into action after 15Secs Of fan startup.
• Fluid coupling oil tank level low switch acts.
• Furnace pressure Low Low i.e < -150mmwc 2 out of 3 selection from Furnace
pressure transmitters with 2secs delay.
• Any one ESP Hopper level high from 5fields.
• ESP I/L temp high i.e >200Deg C for a period of 30 minutes.
• ACW Pressure Low i.e <2Kg/Cm2 with 10sec delay.
• ID Fan & Motor vibration high i.e >11.2mm/sec with 5sec delay.
• Emergency pressed
• PA Trip.
• PA Failed to start
• Motor Winding temperatures High High i.e >140Deg C with 5sec Delay
• Motor & Fan Bearing temperatures High High i.e > 95Deg C with 5sec Delay
• Scoop oil I/L temp High High i.e > 100Deg C with 5sec Delay
• Scoop oil O/L temp High High i.e > 100Deg C with 5sec Delay
• Any one Scoop Lube oil pressure <0.6 Kg/Cm2. During fan startup this interlock
will come into action after 15Secs Of fan startup.
• Fluid coupling oil tank level low switch acts.
• ID Fan not running condition. During Boiler startup this condition will be satisfied
after 7minutes of any ID running condition.
• Drum Level LL i.e <16.7% 2 out of 3 selection.
• PA air presure at APH O/L High High i.e >1800mmwc, 2 out of 3 from
3transmitters.
• Furnace Pressure High High i.e >150mmWC, 2 out of 3 selection from Furnace
Pressure Transmitters with 2sec delay.
• ACW Pressure Low i.e <2Kg/Cm2 with 10sec delay.
• PA Fan & Motor vibration high i.e >11.2mm/sec with 5sec delay.
• Emergency pressed
• SA Trip.
• SA Failed to start
• Motor Winding temperatures High High i.e >140Deg C with 5sec Delay
• Motor & Fan Bearing temperatures High High i.e > 95Deg C with 5sec Delay
• Scoop oil I/L temp High High i.e > 100Deg C with 5sec Delay
• Scoop oil O/L temp High High i.e > 100Deg C with 5sec Delay
• Any one Scoop Lube oil pressure <0.6 Kg/Cm2. During fan startup this interlock
will come into action after 15Secs Of fan startup.
• Fluid coupling oil tank level low switch acts.
• PA Fan not running. During Boiler startup this condition will be satisfied after
3minutes of PA running condition.
• Drum Level LL i.e <16.7% 2 out of 3 selection.
• SA air presure at APH O/L High High i.e >1500mmwc, 2 out of 3 from
3transmitters.
• Furnace Pressure High High i.e >150mmWC, 2 out of 3 selection from Furnace
Pressure Transmitters with 2sec delay.
• ACW Pressure Low i.e <2Kg/Cm2 with 10sec delay.
• SA Fan & Motor vibration high i.e >11.2mm/sec with 5sec delay.
• Emergency pressed
• BFP Trip.
• BFP Failed to start
• Motor Winding temperatures High High i.e >140Deg C with 5sec Delay
• Motor & Pump Bearing temperatures High High i.e > 95Deg C with 5sec Delay
• Scoop oil I/L temp High High i.e > 100Deg C with 5sec Delay
• Scoop oil O/L temp High High i.e > 100Deg C with 5sec Delay
• Any one Scoop Lube oil pressure <0.6 Kg/Cm2. During fan startup this interlock
will come into action after 15Secs Of fan startup.
• Fluid coupling oil tank level low switch acts.
• Deaerator Level Low Low i.e <28%.
• Pump Suction Differential pressure high high i.e >1900mmWC.
• ACW Pressure Low i.e <2Kg/Cm2 with 10sec delay.
• Boiler Feed Pump & Motor vibration high i.e >11.2mm/sec with 5sec delay.
• Emergency pressed
For starting the Feed pump in Auto mode following conditions to be satisfied in
addition to the above interlock.
• DCF Trip
• DCF Failed to start
• Bed Temp High High i.e >990Deg C (2 oo 3 from Bed Temperatures A,B,C) or (2
oo 3 from Bed Temperatures D,E,F.)
• U Beam Temp High High i.e >980Deg C (4 oo 8 from TT-503A to TT-510A) or (4
oo 8 from TT-503B to TT-510BA)
• Both ID Fan Stop condition.
• Both PA Fan Stop condition.
• Both SA Stop condition.
• Drum Level Low Low i.e <16.7% 2 out of 3 selection.
• Seal Air to DCF Low Low Switch acts.
• Spreader Air to DCF Low Low Switch acts.
• Discharge chute KGV Close condition.
9. MDC RAV:
• Over Load trip.
• No One DCF is running.
11 | P a g e Rev 0 dated14/1/2014
6. BARRING [TURNING] GEAR MOTOR: TYPE: AUTO ENGAGE
Barring Speed: 120 rpm
Start Permissive
Jacking oil pressure => 90kg/cm2
Lube oil pressure =>1.95kg/cm2 of the lube oil header pressure
Turbine speed is <20rpm for or between 250rpm AND 300rpm --- For Unit-1
Turbine speed is <10rpm for or between 250rpm AND 300rpm --- For Unit-2
EOP ready OR Overhead lube oil tank level NORMAL
Manual Start
Through soft PB [if start permissive is available]
Through Local PB [if start permissive is available]
Manual Stop
Through Local PB if Casing temperature <=100deg C OR
Cooling down time >96 hours
Auto Start [During coasting down]
Bgm in Auto selection, Turbine speed in between 300 & 250rpm
Auto trip
Feeder fault [Overload, Switchgear fault etc]
Auto Stop [During run up]
Turbine speed =>315rpm
7. Gland Steam Blowers
Start Permissive
Drive remote selected
Manual Start
Through soft PB when drive is in Manual mode
Manual Stop
Through soft PB when drive is in Manual mode
Auto Start
Turbine speed >200 rpm OR
Standby drive is tripped
Auto trip
Feeder fault [Overload, fault start]
Closing Conditions:
1. Soft command from DCS OR
12 | P a g e Rev 0 dated14/1/2014
2. Exhaust hood temp =<55deg C OR
3. Active Power =>10% OR
4. Spray valve is in operation for 1.0 hour continuously.
15 | P a g e Rev 0 dated14/1/2014
Enable close: Close limit not acted.
Protection close: HP HTR-2 Bypass isolation open feedback acted valve selected in remote
mode.
16 | P a g e Rev 0 dated14/1/2014
26.STG Trip & Reset
The Turbine will trip due to any of following fault conditions as listed below
17 | P a g e Rev 0 dated14/1/2014
24 Generator rear shaft vibration high high =>232micron
25 Rotor axial displacement high high =±0.6mm
26 No load trip >1hour Conditions
for No Load are
Turbine speed
=>90% of rated
AND
Active Power
=<3.6MW
27 Turbine Thrust temp non active side top =>100deg C
high high
28 Turbine Thrust temp active top high high =>100deg C
29 Turbine Thrust temperature -Non =>100deg C
active side bottom high high
30 Turbine Thrust temperature - Active =>100deg C
side bottom high high
31 Turbine front bearing temp high high =>120deg C
32 Turbine rear bearing temp high high =>120deg C
33 Gearbox HS DE bearing temp high high =>130deg C
34 Gearbox HS NDE bearing temp high high =>130deg C
35 Gearbox LS NDE bearing temp high high =>130deg C
36 Gearbox LS DE bearing temp high high =>130deg C
37 Generator front bearing temp high high =>90deg C
38 Generator rear bearing temp high high =>90deg C
39 Governor emergency shutdown >Active
40 Main steam temperature gradient high >±5degC/min #
high
41 Flash Tank Level High High >95% with 2sec
delay
42 Drum level High High >80% 2 oo 3
43 Boiler trip condition
19 | P a g e Rev 0 dated14/1/2014
BOP: -
ACC 1 & 2:
Auto Start
Auto Stop
Protection Stop
• CEP Trip / F_start or CST level Low Low switch acts or CST Level <15%
Start Permissive:
• Remote mode selection.
• No Trip, RTS OK.
2. CDP 1,2:
• Remote mode selected and Flash Tank Level > 75%. Pump will start. No need to
put the pump in Auto mode.
• Remote mode selected and Flash Tank Level < 15%. Pump will stop. No need to
put the pump in Auto mode.
Enable start:
No Trip, Remote selected and RTS OK.
Protection stop:
Trip / F_start / Oil Level low switch acts / Vibration High switch acts and motor selected
in remote mode.
Enable start:
No Trip, Remote selected and RTS OK.
Auto Start:
Any one running pump stops / ACW Header pressure Low i.e <3.5Kg/Cm2 and pump
selected in Remote Auto Mode.
Protection Stop:
ACW pump Trip / F_start.
21 | P a g e Rev 0 dated14/1/2014
SIEMENS
Responsible Department Take over Department
SIEMENS LTD
Revision Doc. type
0-20410-41239-18
Folder No. :
EO IP CE TI
Prepared : Checked : Released : Language : Pages :
EO IP 0-20410.xls
0.5
0.45
0.4
Not Permissible
Exhaust Pressure Limit [ata]
0.35
0.3 TRIP
0.25
ALARM
0.2
0.1
0.05
0
0 0.2 0.4 0.6 0.8 1 1.2 1.4
P across last stage group[ata]
We reserve the rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties
without express authority is strictly forbidden. © Siemens Ltd
Format No.:IP-Q-F-3021/B
Rev./Date : - / 30.03.2010
SIEMENS Energy sector - Oil & Gas 0-20410-41269-10
Responsible Dept: Take Over Dept: Revision: Doc. Type:Folder No:
EO IP CE EO IP PE TI
Prepared: Checked: Released: Language:Page:
Aqeel 31.10.2012 SV 31.10.2012 Aqeel 31.10.2012 EN 1 of 1
Valid for: Derived from: Replaces: E-file No.
Project name: Girja Alloys Document: Min. permitted live steam temp.
Turbine Type: SST300 - V56A Turbine No: 41269
505 bara
495
490 505
50
485 bara
475 485 30 45
bara bara
465
455 ` Region C
Region B
445
435 Alarm _ _ _ _ _
425 Trip _________
415
5 Minute Delay on Low temp trip
405
Region A - Permitted during warm and hot start
395
Region B - Permitted only during Cold Startup
385
Region C - Not Permitted
375
365
0 5 10 15 20 25 30 35 40 45 50 55 60
Wheel chamber pressure bar(a)