The three-phase system is subject to phase faults as well as ground faults. For providing complete protection to a three-phase feeder, three relays connected to three CTs as shown in Figure below. As can be seen from Table 1, all the 11 numbers of shunt faults are catered for by the three relays. The relays at bus A will be coordinated with those at bus B using the procedure illustrated in previous topic. Fault current for a single line to ground fault, depends upon the system grounding as well as the tower footing resistance. Therefore, it may happen that the fault current for a single line to ground fault, may be less than the load current. In such cases, it will not be possible to cater to such faults if we use the scheme shown in figure below. Lecture 5 EPE 621 Figure 1: OC protection of a three-phase Lecture 5 EPE 621 feeder Relays which will operate Two-phase fault + Three-phase fault Fault one ground fault relays of Figure 1 relay of Figure 2 a-g Ra Ra, Rg b-g Rb Rg c-g Rc Rc, Rg а-Ь Ra, Rb Ra b-c Rb, Rc Rc c-a Re, Rc Rc , Ra a-b-g Ra,Rb Ra, Rg b-c-g Rb, Rc Rc, Rg c-a-g Ra, Rc Ra, Rc, Rg a-b-c Ra, Rb,Rc Ra, Rc a-b-c-g Ra Rb, Rc Ra, Rc
Table 1 Protection of a three-phase feeder
Lecture 5 EPE 621 Figure 2: 2-Ф Fault and one ground fault relay for OC protection of 3-Ф feeder Lecture 5 EPE 621 If we connect an OC relay in the residual current path as shown in Figure 2, it will be blind to the load current (which is balanced three-phase current) and see only the ground fault currents. The current in this path will be zero or near zero during normal balanced load conditions as well as during a three-phase fault. Thus, the setting of this relay, which is in the residual current path, can be made independent of load current and can indeed be much smaller than the load current. Further, as illustrated in Figure, it is not necessary to use all the three relays - for detection and protection against phase faults. We can get rid of any one phase fault relay without affecting the performance of the scheme. In Figure 2, the relay in the phase b has been removed. Lecture 5 EPE 621 Directional Over-current Relay Figure 3 shows a double-end-fed power system. The zones to be generated by the relays are also shown. Suppose we have only over- current relays at our disposal. Let us focus on OC relays at bus C. Note that OC relays operate on the magnitude of fault current and cannot sense the direction of the fault. Consider fault Fa, As per the desired zones, only CBs 4 and 5 should trip. However, it can be easily seen that if plain OC relays are used, CBs 3, 4, 5, and 6 will all trip as the fault will be seen by OC relays at these locations. Thus, the desired zones are not generated. The desired relay response is shown in Table 2 with respect to faults Fa and Fb. Lecture 5 EPE 621 Figure 3: Need for directional protection
Table 2: Response of OC relaysLecture
to generate 5 EPE 621 desired zone of protection Directional OC Protection of a Three-phase Feeder
Lecture 5 EPE 621
Drawbacks of Over-current Relays The reach and operating time of the over-current relay depend upon the magnitude of fault current. The fault current that would result in case of a fault at a particular location depends upon:
1. The type of fault, i.e. whether it is a ground fault or a phase
fault 2. The source impedance as shown in Figure on next slide.
Lecture 5 EPE 621
Fault current and reach is a function of fault type and source impedance Lecture 5 EPE 621 Since neither the type of fault nor the source impedance is predictable, the reach of the over-current relay keeps on changing depending upon the source conditions and the type of fault. Thus, even though the relays are set with great care, since their reach is subject to variations, they are likely to suffer from loss of selectivity. Such a loss of selectivity can be tolerated to some extent in the low- voltage distribution systems, where the only objective to be met is the continuity of supply to the consumer. However in EHV interconnected system (grid), loss of selectivity can lead to danger to the stability of the power system, in addition to large disruptions to loads. Therefore, over-current relays cannot be relied upon as a primary means of protection in EHV systems.