NEUTRAL CURRENTS WITH UNBALANCED LOADS

DOUBLE CLICK ON CHART & ENTER CURRENT PER PHASE IN YELLOW BOXES
AMPS RED AMPS YELLOW AMPS BLUE
AMPS PER PHASE 60.00 40.00 67.00
VERTICAL COMPONENT 6.50
VERTICAL SQUARED 42.25
HORIZONTAL COMPONENT -23.38
HORIZONTAL SQUARED 546.72
NEUTRAL CURRENT 24.27

CHANGE VALUES OF AMPS PER PHASE IN YELLOW BOXES


TO OBSERVE EFFECT ON NEUTRAL CURRENT.