Operator Interface
• Same Physical Appearance
• Single Membrane Panel
• Standard Bargraph and Graphical Display
• Same Control Operation
• New Menus when Power Transfer Control feature is used
3200 Mounting
Locking Door
Handle Exhaust Temp Option
Vibration Isolation
PT/CT Module
(same as 3100)
AVR Output
(same as 3100)
New Bus PT
UTILITY
3
PROTECTION
FUSES 3
1
TRIP
UTILITY
VOLTAGE BREAKER
SENSING
TO LOAD
CB STATUS
CLOSE GENSET
COMMAND BREAKER
SWITCHGEAR
OPEN 3
COMMAND
3
GENSET
PTC FUNCTION, power fails UTILITY
UTILITY
PROTECTION
FUSES
UTILITY
POWER FAILS
BREAKER
TIME DELAY
TO LOAD
START CMD.
GENSET
GENSET START BREAKER
TIME DELAY SWITCHGEAR
OPEN CMD
TIME DELAY
CLOSE CMD
GENSET
PTC FUNCTION, power returns UTILITY
UTILITY
PROTECTION
FUSES
UTILITY
S1 OK
BREAKER
TIME DELAY
TO LOAD
SYNC TO S1
GENSET
CLOSE CMD BREAKER
RAMP OFF SWITCHGEAR
OPEN CMD
TIME DELAY
TIME DELAY
GENSET STOP
GENSET
Control Comparison
Feature 3100 2100 3200
Isochronous Std Option Std
Governor
“2-Box” Yes Yes
Compatible
Integrated AVR Std Std Std
AVR Sensing 3 phase 3 phase 3 phase
PTC Sensing 3 phase 3 phase
PTC Sequence Open Transition Soft Transition +
Operator Panel Good Good Best
InPower Yes Yes Yes
Compatible
Feature-Option Details
H606 H611
H605
Basic Control:
– H605: Graphical Display
– H606: Bargraph ALL STANDARD
– H611: Basic Control
Paralleling Options
• H612: Isolated Bus/Manual Parallel
– Lowest cost, semi-auto parallel
– Does not automatically parallel
• H613: Isolated Bus Parallel
– Used for applications with transfer switches
• H614: Utility Paralleling/Single
– PLTx Applications ONLY, expected to be low usage
– May need to add H619 or H620
• H615: Utility Paralleling/Multiple Gensets
– Max feature version of software
– Can be used on any paralleling application
Power Transfer Options
• H616: Open Transition Transfer
– Similar in function to PLTO or OTPC
• H617: Fast Closed Transition Transfer
– Similar function to Asco CTT or PLTH
– Genset still provides active synchronizing
• H618: Soft Closed Transition Transfer
– Similar in function to PLTS and PLTE
• active synchronizing, ramping on/off between live sources
– Probably need utility protection that is NOT included
I’m from the factory and I’m here to help you….