Professional Documents
Culture Documents
The panels should be rectangular, and the ratio of the longer span to the
shorter span within a panel should not be greater than 2.0.
1
It should be permissible to Offset columns to a maximum of 10 percent of the
The successive span lengths in each direction should not differ by more than one-
third of the longer span. The end spans may be shorter but not longer than the
interior spans.
The design live load should not exceed three times the design dead load.
2
Total design moment for a span
In the direct design method, the total design moment for a span should be
determined for a strip bounded laterally by the centre line of the panel on each
side of the centre line of the supports. The absolute sum of the positive and
average negative bending moments in each direction should be taken as:
ln= clear span extending from face to face of columns, capitals, brackets or walls, but
When transverse span of the panels on either side of the centre-line of supports
When the adjacent span and parallel span edge are being considered, the
distance from the edge to the line of the panel should be substituted for l2 in the
above equation.
4
Negative and positive design moment
The negative design moments are located at the face of rectangular supports, circular supports being
treated as square supports having the same area. In an interior span, the design moment M O should be
The distribution of moment between supports and midspan in exterior and interior spans is shown in the
Fig below:
where,
= ratio of flexural stiffness of the columns to the flexural stiffness of the slab at a joint taken in
the direction moments are being determined
Kc = sum of the flexural stiffness of the columns meeting at the joint, and
Ks = flexural stiffness of the slab, expressed as moment per unit rotation
5
Fig. 2. Distribution of moments between column and middle strips
6
It is permissible to modify these design moments by up to 10 percent so long as
the total design moment M0 for the panel in the direction considered is not less
The negative moment section is designed to resist the larger of the two interior
negative design moments determined for the spans framing into a common
7
Distribution of bending moments across the panel width
Bending moment at critical cross-section is distributed to the column strips and middle
strips as shown in Fig. below:
8
When openings in flat slabs are located at a distance less than ten times the
thickness of the slab from a concentrated reaction or when the openings are located
within the column strips, the critical section is modified so that part of the
periphery of the critical section which is enclosed by radial projections of the
opening to the centroid of the reaction area is considered ineffective, and opening
should not encroach upon column head.
Fig.
i. Interior column
iii.Corner column
Example 1.
A flat slab is supported on 600 mm dia. circular columns spaced
apart in both directions. The column head has a diameter of 120 cm.
the live load on the flat slab is . Determine the moment in the slab
along its 8 m span.
Solution
Span of slab Since the span is large, it is desirable to provide drop.
The minimum size of drop is
Provide drops of size
That is, for service stress in Fe 415 grad tension steel)
or
Let us adopt overall thickness D = 25 cm and d = 22 cm.
Dead load of slab
Finish load (say)
Live load
Total
Equivalent side of the column head having the same area
Exterior Panel
Interior Panel
BM at first interior support