You are on page 1of 10

PRAESENSA

EOL FOR CAA PA SYSTEM


PRA-EOL End-of-line device

2 Building Technologies | BT-CO/MKA1.2 | 25-08-2022


© Robert Bosch GmbH 2017. All rights reserved, also regarding any disposal, exploitation, reproduction, editing, distribution, as well as in the event of applications for industrial property rights.
PRA-EOL End-of-line device
General
 EOL device for the PRAESENSA amplifiers
 Connected to the end of a loudspeaker line

 A and B output each can have one EoL board

 EoL boards uses the pilot tone from the amplifier output

 EoL boards have a red plastic housing

 EoL board come with a spring clamp connector and flying leads
containing a thermal fuse.

3 Building Technologies | BT-CO/MKA1.2 | 25-08-2022


© Robert Bosch GmbH 2017. All rights reserved, also regarding any disposal, exploitation, reproduction, editing, distribution, as well as in the event of applications for industrial property rights.
PRA-EOL End-of-line device
General
 End of Line supervision
 1 EoL device per amplifier channel, A output

 2 EoL devices, A and B output


‒ Separate EoL fault for A and B output

 Class-A loudspeaker line supervision


 EoL device on the B output. Class-A

4 Building Technologies | BT-CO/MKA1.2 | 25-08-2022


© Robert Bosch GmbH 2017. All rights reserved, also regarding any disposal, exploitation, reproduction, editing, distribution, as well as in the event of applications for industrial property rights.
PRA-EOL End-of-line device
Amplifier supervision
 Amplifier channels supervision
 Amplifier channels are tested one by one, in sequence

 Pilot tone 25.5kHz, 3V RMS


‒ Pilot tone only present during test
‒ Duration 1 sec per channel

 Whole amplifier test takes 8 sec, if all channels are tested

 Continuous test.

8x 1 Sec = 8 sec

5 Building Technologies | BT-CO/MKA1.2 | 25-08-2022


© Robert Bosch GmbH 2017. All rights reserved, also regarding any disposal, exploitation, reproduction, editing, distribution, as well as in the event of applications for industrial property rights.
PRA-EOL End-of-line device
EoL supervision
 End of Line supervision
 EoL boards are tested in sequence EoL
EoL

EoL
 Pilot tone 25.5kHz, 3V RMS
EoL

‒ Pilot tone only present during test EoL


EoL

EoL
 Running on mains power EoL

‒ Duration 2 sec per channel (Amplifier channel and EoL test) EoL
EoL

‒ For 8 channels the test takes 16 sec EoL


EoL

‒ Channels with EoL disabled switch back to 1 sec amplifier test


EoL
‒ Continuous test. EoL

EoL
EoL

8x 2 Sec = 16 sec

6 Building Technologies | BT-CO/MKA1.2 | 25-08-2022


© Robert Bosch GmbH 2017. All rights reserved, also regarding any disposal, exploitation, reproduction, editing, distribution, as well as in the event of applications for industrial property rights.
PRA-EOL End-of-line device
EoL supervision
 End of Line supervision
 EoL boards are tested in sequence EoL
EoL

EoL
EoL
 Pilot tone 25.5kHz, 3V RMS
‒ Pilot tone only present during test EoL
EoL

EoL
 Running on Battery EoL

‒ Backup power mode active to save power EoL


EoL

‒ Tested once every 90 sec EoL


EoL

‒ Duration 1 sec per channel (Amplifier channel and EoL test)


EoL
‒ For 8 channels the test takes 8 sec EoL

EoL
EoL

 Speaker circuit requirements


‒ Max. cable length : 1000mtr
8x21Sec
8x Sec==16
8 sec
sec.
‒ Max. cable capacitance : 80nF per speaker line.

7 Building Technologies | BT-CO/MKA1.2 | 25-08-2022


© Robert Bosch GmbH 2017. All rights reserved, also regarding any disposal, exploitation, reproduction, editing, distribution, as well as in the event of applications for industrial property rights.
PRA-EOL End-of-line device
EoL supervision concept
 Detailed amplifier block diagram
 EoL detection circuit
 EoL device adds a special load to the speaker line
25.5kHz 51kHz
u i EoL device

 The detection circuit can detect the special load


caused by the EoL device

 When the special load is detected


‒ The speaker line is OK

 When the special load is missing


‒ The speaker line is broken and an EoL fault is generated.

8 Building Technologies | BT-CO/MKA1.2 | 25-08-2022


© Robert Bosch GmbH 2017. All rights reserved, also regarding any disposal, exploitation, reproduction, editing, distribution, as well as in the event of applications for industrial property rights.
PRA-EOL End-of-line device
8 Channel amplifier: Rear panel speaker connections

Loudspeaker
outputs A&B

EoL device connection for


Class-A loop wiring.

9 Building Technologies | BT-CO/MKA1.2 | 25-08-2022


© Robert Bosch GmbH 2017. All rights reserved, also regarding any disposal, exploitation, reproduction, editing, distribution, as well as in the event of applications for industrial property rights.
PRA-EOL End-of-line device
4 Channel amplifier: Rear panel speaker connections

Loudspeaker
outputs A&B
EoL device
connection

EoL device connection for


Class-A loop wiring.

10 Building Technologies | BT-CO/MKA1.2 | 25-08-2022


© Robert Bosch GmbH 2017. All rights reserved, also regarding any disposal, exploitation, reproduction, editing, distribution, as well as in the event of applications for industrial property rights.