• Speed Controller
• Load Controller
• Pressure Controller
Controller Selection criteria
Condition Speed Load Pressure
Controller Controller Controller
(I) Start-up x x
a) Speeding up (Rolling )
600 rpm, 3000 rpm
b) Synchronization x x
c) Initial loading x x
immediately after
synchronization
(II) Loading Can be used Can cut in limit
More than house hold as backup pressure mode or
initial pr. Mode.
(III) Tripped X X
(IV) Load shedding Can be x
backup
Control Transfer Circuit
+
+
+
AH27 X21
X22
2V
Pressure
Controller
O/P
Major Field Instrumentation
• Speed Measurement
• Pressure Measurement
• Load Measurement
• Temperature Margins
• Valve Lift Position Feedback
• Collins Transmitter
• Electro Hydraulic Convertor
• Plunger Coil
Redundant DEH WH – SEC Design
Redundant
Processor
Conceptual Diagram (Control Part)
SP PR 1 PR 2 EHC-2
EHC-1
EHC-5
EHC-3
LVDT-2
LVDT-1
HPCV-1 HPCV-2
LVDT-5
EHC-6
AI AI AI LVDT-3 IPCV-1
HPCV-3 EHC-4
Triple Redundant
MW MW MW
LVDT-6
SPEED SPEED SPEED
LVDT-4 IPCV-2
PR PR PR HPCV-4
Note: EHC is electronic module (MOOG)
REDUNDENT DEH– Alternative DESIGN
Conceptual Diagram (Control Part)
Redundant
Processor
Plunger Coil
EHC-2
S PR 1 PR 2
P LVDT-2
EHC-1 IPCV-2
LVDT-1
HPCV-1
AI AI AI IPCV-1
HPCV-2
Triple Redundant
MW MW MW HPCV-3
SPEED SPEED SPEED
HPCV-4
PR PR PR Note.- Feedback OF Individual CV is not used in control. Used
only for indication purpose. EHC is electronic module.
Key Technical Comparison
Advantages VS Disadvantages
VALVE Position (Admission)
Controller
The signal from speed controller, load controller and pressure controller are
superimposed and selected for valve position controller.
LVDT measures the valve lift i.e. position of power piston in the amplifier.
PID
6V
SP EHC
Controller Amplifier
ARS12 AVC12
-7.5 to 7.5V
AKC
M
A
X
hr , actual AKC
LVDT 1 Follow up Piston
LVDT 2
Concerns
Oil Lines
1. Loss of power to Plunger Coil
2. Switching ON Plunger Coil
3. Plunger Coil Wire Break
Speed Controller
Function:
During following situation
– Start up
– Shutdown
– Synchronizing
– Raising to house lead operation.
– Lead shedding (Islanding condition)
– Limitation of speed before reaching over speed.
Speed Controller
Actual speed
Speed controller is PD loop an error in the input is must to keep valve open for running
the m/c at rated speed. To eliminate this offset pressure dependent correction signal is
given as valve operation for required speed is directly proportional to pressure system.
HMI
Speed nR
Reference Limit
2160 rmp /
Auto Synchronization
nRTD
n RTD nRTD
1800
1200
600
1 mm 2 mm 3
mm
Min req. speed 100 RPM
TSE INF on SC
n RTD nRTD
600
300
100
5k 15K 30K
TSE Margin
TSE Inf on SC
n Ref
2160 rmp
n RTD
600 rpm
1m t
n ref Vs n RTD
Speed Measurement
A 027 -X13
Hall Probe
U
AE051
U AE051 AE099
nact
A IA 11 -X13
AWI11 MV3 F1 F
A E035 Freg.
Setting
ADA 11 U
F2
U 0 to –10.8 V
U
AWI11
AC003 AB099 Nact120-120
AIA 11
A C011
AIA 11 AB115
Spare Nact
A C019
AIA 11
For
Follow up
Speed ref generation Value
Measurement of Speed
Is 30-80mA
Sensor Volt output 700to 900mV
Hall Effect
A Hall effect
probe measures
the magnetic
field by making
use of the
Lorentz
force, on the
electrical current
in a
semiconductor.
• AIA II frequency generator and pulse matching unit. I/P Pulse train o/p
sq. Wave pulse. Measurement x13 w.r.t. x22 = Max 11V.
Green light up > 12 Hz (quartz freq, std.)
Steady state droop on load throw off from full load to no load
Rate of change of speed set point R.
Up to 2820 rpm – at a rate at 2160 rpm/min
Beyond 2820 rpm – at a rate of 360 rpm / min (1/6 rate)
2160 rpm/min
Nr rate
360 rpm/min
nR measurement – AB035 : x11
2820 nR
Load Controller
Pr (lim)
T h rnc (AE131 x 12)
Load Limit H
Min
ADC/UNIT
PR MAX
T TSE Fault
H
TSE inf
dP/dt
PRF
Pr (Lim)
dp /dt hRPc
TSE inf
Load Limiter
Pr Limited
Load Controller
TSE GB
Fult OFF
Frequency
BB19 Isolated
influence
Grid Mode
Panel PRF
XII
L
O XII XII
Desk Stop
A
PB Pref PR _ Normal
D
(Optional) Y Limit PRTD hrpc
+ MIN BH075 Islanded
X25 EPR Mode
R BE083 BE163 X12
HMI
E MIN
XII PRMAX X12
F
SGC Pack Speed signal
Turbine BE115 BH043 5% droop
73080
X24
Load BE75
TSE
Gradent
dp/dt CJJ01
BE083, X25 DA10
Operator set
Load Controller
Gradient of Load reference Max
• PI controller
• ARL 12 card.
• Any change in PR
Max, PRTD changes by 5% of full load immediately
and remaining by TSE influence.
• Follow up mode must so that Prtd can brought back to zero after GB open.
• PRTD tracks actual load after synchronization.
• Fast calibration provided for follow up.
• PRTD block on TSE fault / margin.
• Prtd block on steam parameter not OK (SGC).
Load Controller
ARL 13 Card
• Integrator part
• Filter to ward out fluctuation in ARL 12 o/p.
• Hunting adjustment (filter ) pot R11/R12
• Follow up mode
Load controller off \generator Bkr off\pact < STl and P > 5%
then output is made to follow the speed controller by 150 mv.
Load controller o/p tracks speed C. with error 150 mV.
GB closed and Speed control in servise (Following low hvu)
LC tracks speed controller o/p by 150 mV.
Can not go below 150 mV of speed controller o/p.
LC output can go more than speed controller o/p.
Fast calibration is provided to mach the Prtd with actual load.
Freq influence PRf
• Limitation 40 MW.
Freq. influence ckt.
PID
6V
SP EHC
Controller Amplifier
ARS12 AVC12
Col 1
-7.5 to 7.5V
AKC
M
A
X
AKC
Col 2
hr , actual Follow up Piston
Concerns
Oil Lines
1. Switching OFF Plunger Coil
2. Switching ON Plunger Coil
3. Plunger Coil Wire Break
Collins Transmitter
Yellow + ve
+ Red
-7.5 V to + 7.5 V
24 V DC Supply Plunger
Linear w.r.t.Positive
Concerns - Black
+ 7.5 V
0 50 mm travel
25 mm = 0 V
- 7.5 V
LVDT Principle of Operation
Measurement
• Phase Angle
• Amplitude
Admission Controller
Error +ve
Balance Condition
Plunger Coil 1V
V
Error -ve
Time
Green 9 Blue -
Feedback Collins
Yellow 10 Yellow +
Hydraulic To Electro Hydraulic Control
While bringing in the Electro Hydraulic control system, the reference set point
of EHC should be reduced slowly until secondary oil pressure drops slightly.
When this happen Electro Hydraulic converter has broken over. The speeder
gear of hydraulic speed governor is then set at max. position.
Changeover from Electro Hydraulic
to
Hydraulic Control
act
n
dN /dt nact < 2850
nact > 700
GCB off
Load
5% droop
50.2 51.33
freq
Stop on Set Point Generator
TSE inf ON
OR
• Turbine Tripped.
OR
• Throttle Select.
OR
20%
-30% M
A
50%
X
M
40%
I
N
+
+
+
20%
PROBLEM
OBSERVATION
OBSERVATION
Plug at the bottom of pilot of
plunger coil was found loose
ACTION TAKEN
Plug tightened then characteristics found ok.
Also plug fixed with locktite 270 to
avoid repetitive failure
PROBLEM
ACTION
After replacement of one hall
probe, Unit synchronized
ANALYSIS
M/C should not trip on failure of one hall probe
as speed is sensed by 3 hall probes. Suspected
problem was in mean value selection logic or
malfunctioning of selection logic card
PROBLEM
Multiple cracks of 4 mm depth observed in
LPBP stop valve and control valve. Also
typical layer observed there. Problem
observed during overhaul at Khaperkheda
OBSERVATION
Attended by BHEL
At Ramagundam frequent problem observed in speed
measurement because of frequent failure of DC to DC
converter circuit on AIW 11 card mounted in DIW10B
field JB for speed measurement. As 3 separate card
are there for 3 speed channels, m/c not tripped due to
mean value selection circuit.
PROBLEM
Change over valve
Not getting reset
OBSERVATION
Change over
Valve in trip
Condition and
Control oil
Pressure low
SOLUTION
On line full flow
filter self
cleaning by RECOMMENDATION
knob rotation On line full flow
filter self
cleaning by
regular knob
rotation
PROBLEM
Electro Hydraulic
Converter Hunting
OBSERVATION
Callibrator of EHC checked with
callibrator and found oscillating
SOLUTION