University of Salahaddin-Hewler College of Engineering Department of Civil Eng
University of Salahaddin-Hewler College of Engineering Department of Civil Eng
College of Engineering
Department of Civil Eng.
(2006-2007)
1
*
*
(32)
They(Angels) said:"Glory be to You,we have no
knowledge except what you have taught us.Verily it is
you,the All-Knower,the All-Wise."
(Al-Baqarah 32)
Dilshad,Trifa&Kamaran
27/5/2007
Table Of Contents:
-CHAPTER ONE....SLAB
-CHAPTER TWO...........BEAMS
-CHAPTER THREECOLUMNS
-REFERENCES
CHAPTER ONE
Design of Slab using
Direct Design Method(DDM)
Occupacy:-Supermarket
Primary dimensions:
-Slab Thickness:160 mm
-Beam Dimension:(300*560)mm
-Column Dimension:(400*400)mm
Limitations:
1-Min. 3 panels in each direction. O.K.
2-l/l=5.8/4.4=1.32<2 Two-way span O.K.
3-Difference in spans=4.8-4.4=0.4 <4.8/3 O.K.
4-Offsets of columns=0 <10% O.K.
5-Calculating 1 & 2 :be for T-section=bw+2(h-t)=<bw+8t
=300+2(560-160)=<300+8*160
=1100=<1560
Be=1100 mm
Be for L-section=bw+(h-t)=<bw+4t
=300+(560-160)=<300+4*160
=700=<940
Be=700 mm
-Beams 1&2:
3
bh
I =k
b
12
b
b
1 + ( e 1)( t )[4 6( t ) + ( t ) 2 + ( e 1)( t )3 ]
h
bw
h
h
h
bw
k=
b
1 + ( e 1)( t )
bw
h
For T-section:
K=1.72
For L-section:
K=2.6434
=Ib/Is=4.61
-Beams 3&4:
=15.455
-Beams 5&6
=3.8144
-Beams 6&7:
=11.7244
for all panels:
0.2<((1*l2^2)/(2*l1^2))<5.0
O.K.
For roof:
Wd.l=0.02*16+0.16*24+0.02*12+0.06*18+0.07*24
=7.16 KN/m^2
Wd.l=0.03*23+0.05*23+0.16*24+0.02*16=6.0 KN/M^2
8
Panel
m
1
8.9
2
6.92
3
6.19
4
4.21
0.65M
0.16M
0.65M
0.70M
10
C=(1-0.63x/y)*((x^3 * y)/3)
11
X,mm
Y,mm
160
700
(x^3
(10.63x/y) y)/3
10^9
mm^4
0.856
0.956
A1
C,10^9
2.7173
2
1
300
160
400
400
0.5275
0.252
3.6
0.546
A2
1.8384
2
300
560
0.3375
5.04
Width=4.8m
M.st. =2.4m
Col.st.=2.4 m
Width=5.8m
Col.st.=2.9m
M.st. =2.9m
-ve
T-M 48.55
Slab
38.67
Beam 6.82
M.st
3.06
T-M
38.94
Slab 31.36
Beam 5.53
M.st. 2.05
Exterior span
+ve
-ve
173
212.4
117.8 144.61
20.8
25.52
34.43 42.27
138.74 170.4
81
99.5
14.3
17.6
43.43 53.34
Calculation of :
= 1 (1 1 2mR )
m
fy
M=fy/(0.85f'c)=15.46
R=Mu/(*b*d^2)
14
Interior span
-ve
+ve -ve
197.22 106.2 197.22
134.28 72.31 134.28
23.7
12.76 23.7
39.25 21.13 39.25
158.2 85.2 158.2
92.4
49.75 92.4
16.3
8.78 16.3
49.5
26.67 49.5
Long direction:
-Col.st. & M.st:
=0.0647(1-(1-0.00316Mu))
Short direction:
-Col.st.
=0.0647(1-(1-0.00318Mu))
-M.st.
=0.0647(1-(1-0.0027Mu))
15
Exterior span
-ve
+ve
Col.st.As,mm^2 619
681
No. of bar
6
7
Spacing
Smax. Smax.
M.st.As,mm^2 619
1114.56
No. of bar
6
10
Spacing
Smax. 240
Interior span
-ve
-ve
+ve
836
774
619
8
7
6
300
Smax. Smax.
1393.2 1300.3 681
13
12
7
184
200
Smax.
-ve
774
7
Smax.
1300.3
12
200
-Short direction:
Exterior span
-ve
+ve
Col.st.As,mm^2 678.6 678.6
No. of bar
6
6
Spacing
Smax. Smax.
M.st.As,mm^2 678.6 1323.27
No. of bar
6
12
Spacing
Smax. 240
16
Interior span
-ve
-ve
+ve
678.6
678.6
678.6
6
6
6
Smax. Smax. Smax.
1628.64 1526.85 814.32
15
14
8
193
207
362.5
-ve
678.6
6
Smax.
1526.85
14
207
Long direction
-Col.st.:
-ve(top bar) 12@30 cm C/Ca
+ve(bottom) 12@30 cm C/C.b
-M.st.:
-ve, 12@15 cm C/C.c
+ve, 12@15 cm C/Cd
Short direction
-Col.st.:
-ve , 12@30 cm C/Ce
+ve , 12@30 cm C/C...f
-M.st.:
-ve , 12 @15 cm C/Cg
+ve , 12@15 cm C/Ch
For corner use 10@20 cm C/C
17
18
19
L.L=2 KN/m^2
Wu=11.39 KN/m^2
Moment:
-long direction=198.75200 KN.m
-short direction=159.45160 KN.m
-Long direction:
Total
M.st.
Beam
Slab
Exterior span
Ex -ve
+ve
-ve
32
114
140
2.016
22.69
27.86
25.49
77.64
95.32
4.5
13.7
16.82
Interior span
-ve
+ve
-ve
130
70
130
25.87
13.93
25.87
88.51
47.66
88.51
15.62
8.41
15.62
Col.st. width=2.4 m
M.st. width =2.4 m
d=129 mm ,
m=15.46
M
R=
bd
u
m=
fy
f c
Col.st:
-ve As=619.2 mm^2 Use 812 @ 30cm C/C
+ve As=619.2 mm^2 Use 812 @ 30cm C/C
M.st.:
-ve As=897.84 mm^2 Use 812 @ 30cm C/C
+ve As=743 mm^2
Use 812 @ 30cm C/C
20
-Short direction
Total
M.st.
Beam
Slab
Exterior span
Ex -ve
+ve
-ve
25.6
91.2
112
28.55
35
53.26
65.4
9.4
11.54
-Col.st. width=2.9 m
-M.st. Width =2.9 m
d=117 mm , m=15.46
Col.st.:
-ve M , Use 812 @ 30 cm C/C
+ve M , Use 812 @ 30 cm C/C
M.st.:
-ve M , Use 1212 @ 24 cm C/C
+ve M , Use 912 @ 32 cm C/C
21
-ve
104
Interior span
+ve
-ve
56
104
CHAPTER TWO
Design Of Beams
22
-Floor Beams
-Long direction:
Grid 1:- Using Moment Distribution Method Of Analysis
bh 3
Ib =
2
12
=8.8 * 10^-3
23
K=4
EI
L
Kb=129.78
Kc=60.73
DF(1-2)=129.78/(129.78+2*60.73)=0.52
DF(1-1`,1-1``)=0.24
DF(2-3)=0.34
DF(2-2` ,2-2``)=0.16
FEM =
1
Wu l 2
12
24
FEM=94.19 KN.m
Joint 1
DF
COF
FEM
DM
COM
Joint 2
DM
1-2
2-1
2-2
2-3
3-2
3-3
0.24
0.51
0.34
0.16
0.34
0.34
0.16 0.34
0.5
0.5
0.5
0.5
0.5
-94.19
94.19
94.19
94.19
22.79 48.04 0
0
8.19-
4-3
4-4
4-5
5-4
5-5
0.34
0.16
0.34
0.51
0.24
0.5
0.5
0.5
94.19-
94.19
94.19-
94.19
48.04 22.79
24.023.84-
8.19-
4.095
0.991 2.089
8.19
4.095-
3.84
8.19
4.095-
4.095
2.089 0.995
1.045
DM
0.36-
3-4
Joint 5
24.02
COM
COM
Joint 4
1-1
DM
COM
Joint 3
1.0450.360.167
0.36
0.18-
0.168 0.36
0.18
89.915
102.74
25
102.74 4.01
89.915
0.18
48.34 110.705
23.78
26
-It is clear that the results of coefficient method are close to (greater or
equal)moment dist. Method,so it is possible to use coeff. Method(ACI
8.3.3) to determine moments and shear in design of beams.
-Long Direction
Beam BL1:
+ve moment =80.74 KN.m
-ve moment =113 KN.m
Shear =112 KN
27
m=15.46
R=Mu/(0.9*b*d^2)
= 0.065(1 1
min =
2 15.46 0.01402 M u
)
272
1.4
f c
= 0.0015
fy
4f y
v u = 1.15
w uln
= 112.06 KN
2
1-If Vu>Vc
a Vu <
1
d
f `c b w d , S or 600mm
3
2
1
2
d
f `c b w d < Vu <
f `c b w d , S or 300mm
3
3
4
28
2-If (Vc/2)<Vu<Vc
Av =
1 bwS
d
, S max =
3 fy
2
Vc =
f `c b w d ; = 0.75
6
Vc=87.7 KN
For beam BL1 : min. shear required
S=257 mm
Use 10mm@25cm C/C
Beam BL2:
-Ve moment=102.76 KN.m
+Ve moment=70.64 KN.m
29
Floor Beams:
113
102.76
178.97
162.7
65.71
71.1
106.57
115.3
80.74
70.64
127.83
127.8
47
55.86
76.12
90.6
112.1
97.44
177.42
154.3
85.87
74.67
139.3
132.1
30
516
516
620
520
416
416
516
516
416
416
420
420
416
416
416
416
10@25cm
10@25cm
10@25cm
10@25cm
10@25cm
10@25cm
10@25cm
10@25cm
Roof Beams:
-Ve
M
KN.m
79.39
73
115.6
105
46.46
51
60
65
+Ve
M
KN.m
57
56.7
83
82.56
33.2
33.2
43
43
Shear
Shear
-Ve
+Ve
Force,KN Reinf. Reinf. Reinf.
78.7
68.44
114.6
99.6
60.72
57.6
78.43
74.41
31
416
416
516
416
416
416
416
416
416
416
416
416
416
416
416
416
10@25cm
10@25cm
10@25cm
10@25cm
10@25cm
10@25cm
10@25cm
10@25cm
CHAPTER THREE
Design of Columns
32
Roof:
e min . = 15 + 0.03h = 0.027m
Axial load=Reactions + Wt. of column
COL.
C1
C2
P,KN
500.31
861.72
ex,m
0.1313
0.1237
ey,m
0.1411
C3
C4
839.42
1525
0.0357
0.0319
0.1332
C3`
C4`
894.42
1566.24
0
0
0.125
emin .
emin .
emin .
Case
Biaxial
Uniaxial
Biaxial
Uniaxial
Uniaxial
Axial
Ground floor:
COL.
C1
P,KN
131.57
Mx,KN.m ex,m
50
0.46
My,KN.m ey,m
60
0.38
Case
Biaxial
C2
218.94
6.39
0.274
60
emin .
Uniaxial
C3
224.8
72.2
0.07
15.5
0.32
Biaxial
C4
368.5
10.6
0.061
22.5
emin .
Uniaxial
C3`
255
72.2
---
---
0.283
Uniaxial
C4`
369.5
10.6
---
---
0.029
Axial
33
Ast=1600 mm^2
400 ( 2 * 20)
= 0.8
400
f c = 28Mpa = 4Ksi
f y = 420Mpa = 60Ksi
From reciprocal method:
1
1
1
1
=
+
Pn Pnx Pny P0
Pnx = Pux = 264.37Kip = 1176.44KN
Pny = Puy = 270.8Kip = 1205KN
P0 = Pu = 515.8Kip = 2295.5KN
Pn = 803.7KN > 500.31KN
Use 816
O.K .
Ast=1600 mm^2
Ties: -16*bar=256 mm
-48*tie=480 mm
-least column dimension=400 mm
Ast=0.0016m^2=1600 mm^2
O.K.
e/h=0.31
Pu=193.64 kip
Pu
193.64
=
= 0 .3
.min. Controls
35
References
-Arthur H.Nilson,David Darwin,Charls W.Dolan,
(Design of concrete structures,13th eddition)
-Jack C.Mc Cormac,James K.Nelson
(Design of reinforced concrete,6th eddition)
-Building Code requirements for structural concrete and
commentry(ACI 318M-05)
-Arthur H.Nilson,George Winter
(Design of concrete structures,10th eddition)
-Lectures of Reinforced Concrete Design by Dr.Omer Qarani
THE END.