You are on page 1of 1

Ref: APL / FQA / Civil / dated: 15.01.

2009

To,
The Project Manager,
M/s Paharpur Cooling Towers Limited
Mundra.

Sub: List of Approved Liquid “Retarding cum Super Plasticizing” Admixtures for RCC
works of Cooling Towers Phase III and IV.
Based on the results obtained for trials conducted at site for assessing its suitability as respect to
Workability [in terms of slump] and setting times, Liquid Admixtures of following brands are
approved and can be used for RCC works of Cooling Towers Phase III and IV.
1. M/s Sika India Pvt. Limited
Sikament600 HP/2 [A] @ 0.9 % weight. of cement
2. M/s Fosroc Chemicals India Pvt. Limited
Conplast SP 430 MS @ 0.8 % weight. of cement
3. M/s BASF Conctruction India Pvt .Limited
Rheobuild 821 EJ @ 0.7 % weight. of cement
Therefore the same can be used while construction of Cooling Towers phases III and IV as per
Approved Mix Design.
You may start procuring the material.
Yours truly,

[K.P.Chakerwarti]
Deputy General Manager- Civil
Field Quality Assurance
Adani Power Limited,
5 x 660 MW TPP
Mundra.

CC to
VP / AVP / GM [Civil] [By e-mail]
SEPCO III [Hard copy]

/var/www/apps/scribd/scribd/tmp/scratch7/15371283.doc