Q? I keep getting an F02 Auxiliary fault, and cannot get rid of it.
A! There needs to be a true state connection on terminal 24 on the control interface card. If
there is no control interface card, a jumper needs to be in place in J4 for the A frame or in J7
for the B-G frame drives. See the user manual for jumper locations. If these conditions are
met and the display does not change either the Control Interface Board is faulty or the Main
Control Board needs replacement. The same question applies to the Plus II drive also.