You are on page 1of 1

Typical limiting values of Sub-station electrical equipments.

1. Transformer / Reactor:
SL.
NO.
EQUIPMENT / TEST DATA PERMISSIBLE LIMITS REFERENCE
A)
Transformer oil
a) BDV
-At the time of first charging 600 kV (Gap 2.5 mm) Minimum IS 1866
-During O&M 50 kV (Gap 2.5 mm) Minimum IS 1867
b) Moisture content IS 1868
-At the time of first charging 15 PPM (Max.) IS 1869
-During O&M 25 PPM (Max.) IS 1870
c) Resistivity at 90 degree C 0.1-1012 Ohm-CM (Min.) IS 1871
d) Acidity 0.2 mg KOH/gm (Max.) IS 1872
e) IFT at 27 degree C 0.018 N/M (Min.) IS 1873
f) Tan delta at 90 degree C 0.20 (Max.) IS 1874
g) Flash point 126 Deg. C (Min.) IS 1875
B)
Vibration level for reactors 200 Microns (Peak to Peak) IS 1876
60 Microns (Average) IS 1877
C) Tan delta for bushing at 20 Deg. C 0.007* IEC 137
D) Capacitance for bushing + 5% variation IEC 138
E) IR value for winding 1000 M-Ohm By 5.0/10.0 kV Ins. Tester IEC 139
F) Tan delta for windings at 20 Deg. C 0.007* IEEE/C57.12.90.1980
G)
Contact resistance of bushing
terminal connectors
10 M. Ohm / Connector NGC.UK
Recommendations
H) Turret Neutral CT ratio errors 39 IS 2705

You might also like