You are on page 1of 1

TESTING PROTOCOL

2X600 MW JITPL,ANGUL,ORISSA.
BUS BAR



Signature
HVEPL VESPL BHEL JITPL JITPL(QC)

Name Prabakaran.J

TEST REPORT BUS BAR DATE:22/05/2013

Plant 2X600 JINDAL INDIA THERMAL POWER PROJECT, ANGUL,
ORISSA.
Location HT SWITCHGEAR PANEL ROOM#1BA
System BUS BAR

Insulation Resistance Test:11 KV Main Bus Bar

Details Megger Used IR Value
R phase to Ground 5000 V 12.5 G
Y phase to Ground 5000 V 16.5 G
B phase to Ground 5000 V 8.5 G
R phase to Y phase 5000 V 11.7 G
Y phase to B phase 5000 V 19.4 G
B phase to R phase 5000 v 13.0 G


Insulation Resistance Test: 220 V DC Control Bus

Source
Details
Megger Used IR Value
BUS-1
+ ve to Ground 500 V 51.2 M
- ve to Ground 500 V 52.5 M
BUS-2
+ ve to Ground 500 V 61.2 M
- ve to Ground 500 V 60.2 M


Insulation Resistance Test:230 V AC Control BUS

Details Megger Used IR Value
R phase to Ground 500V 365 M
Y phase to Ground 500 V 303 M
B phase to Ground 500 V 574 M
Neutral to Ground 500 V 145 M
R phase to Y phase 500 V 898 M
Y phase to B phase 500 V 680 M
B phase to R phase 500 V 684 M
Remarks: Test Results found satisfactory.