High Performance
TECHNICAL
MANUAL
TECHNICAL MANUAL
Contents
Basics ....................................................................................... 2
What is airconditioning?
What is a Packaged Airconditioner?
Main Components
General layout of components
within the IDU
What is a Split Airconditioner?
What is a Ducted Split Airconditioner?
HiPer+ Packaged ACs
HiSen Packaged ACs
Scroll Compressor Technology
The Tandem Scroll
2
3
4
4
5
5
6
8
10
10
Operating Instructions:
Floor-Mounted Packaged ACs ............................................. 12
Controller Specifications
12
Operating Instructions:
Ducted Split ACs .................................................................... 16
Controller Specifications
16
19
19
Troubleshooting ..................................................................... 22
Diagnosing faults
Quick-check Troubleshooting Chart
22
22
Basics
What is airconditioning?
An airconditioning system consists of many pieces of mechanical and electrical
equipment assembled together to produce in an enclosed space acceptable
conditions of Temperature, Humidity, Air purity and Air motion.
The basic compression refrigeration cycle, the most important part of an
airconditioning system, is explained in the schematic diagram given below:
TECHNICAL MANUAL
What is a
Packaged Airconditioner?
When all the mechanical and electrical components of an airconditioning system
are assembled in a single package this is referred to as a Packaged Airconditioner.
They are generally floor-standing units.
Packaged ACs can be either air-cooled or water-cooled.
Air-cooled
Packaged Airconditioners
Air-cooled Packaged ACs use air to cool the refrigerant. The IDU contains all the
AC components except the condenser and its fan, which are separately housed
in the Outdoor Unit (ODU).
Electrical control of Aircooled Packaged AC models is at the bottom section of
the unit. The new facia controller is mounted on the upper panel section.
Water-cooled
Packaged Airconditioners
Water-cooled Packaged Airconditioners are compact floor standing units. All
components including the condenser are included in the unit. Water is pumped
into the unit to cool the refrigerant and the hot water is returned to external cooling
towers, cooled and recirculated. Only the piping connections for the water cycle
and the water cooling system are external. The electrical control panel is inbuilt
at the bottom of the unit. The new facia controller is mounted on the upper panel
section.
Indoor Unit
Outdoor Units
22 TR Model
Main Components
Air-cooled Packaged AC
A. Indoor Unit (IDU)
COMPRESSOR
COOLING COIL
EXPANSION VALVE
BLOWER FAN
BLOWER FAN MOTOR
FILTER
CONTROL PANEL
CONDENSER COIL
CONDENSER FAN WITH MOTOR
Water-cooled Packaged AC
A. Indoor Unit (IDU)
B. Water cooled condenser (EXTRA)
TECHNICAL MANUAL
What is a
Ducted Split Airconditioner?
A ducted split airconditioner is a split airconditioner, in which the IDU is housed
in a concealed box, usually mounted above the false ceiling. The air-flow from
the IDU is directed into a ducted air distribution network. Ducting therefore is a
key design aspect of these ACs.
The ODU is conveniently located on the skirting, sunshade, roof-top or mounted
on a special platform to be grouted into the wall.
Indoor Unit
Outdoor Units
3 TR Model
7.5 TR Model
5, 5.5, 8.75, 11 TR
Models
22 TR Model
Features
Here are some of the features that make the Hi Per Plus Packaged Airconditioner
a high-end, superior quality product:
Efficient heat transfer:
The upsized evaporator offering enhanced surface area ensures removal of the
high sensible heat and handles a higher indoor air volume of 550 CFM per ton.
The inner grooved copper tubes with mechanically bonded slit aluminium fins
ensure efficient heat transfer.
Higher capacity evaporator fan:
Optimally selected DIDW forward curved centrifugal type fan exclusively designed
for delivering more air volume at 550 CFM/ton, with low noise levels.
Optimum expansion valve:
Optimally selected expansion valve with accurate preset super heat settings,
minimizes splash gas and eliminates the problem of improper cooling in the
evaporator.
Condenser with higher heat rejection capability:
The upsized condenser coil and twin fan condenser with higher heat rejection
capability, ensures lower condensing temperature, thereby delivering full capacity
even at temperatures as high as 45o C with extraordinary energy efficiency and
substantially lower power consumption.
Corrosion resistant blue fin condenser:
The special precoated Blue Fin Condensers are resistant to both chemical and
saline corrosion. They are tested for 500 hours of salt spray as per international
standard JIS-Z-2371.
TECHNICAL MANUAL
Features
Here are some of the features that make the HiSen Packaged Airconditioner a
high-end, superior quality product.
Efficient heat transfer cooling coil, with enhanced surface area:
The inner grooved copper tubes with mechanically bonded slit aluminum fins
ensure efficient heat transfer. The upsized-cooling coil offering enhanced surface
area ensures removal of the high sensible heat and handles a higher indoor air
volume of 550 CFM per ton.
Higher capacity evaporator fan:
Optimally selected DIDW forward curved centrifugal type fan exclusively designed
for delivering more air volume at 550 CFM/ton with low noise levels.
Optimum expansion valve:
Optimally selected expansion valve with accurate preset super heat settings,
minimizes splash gas and eliminates the problem of improper cooling in the
evaporator.
Corrosion resistant blue fin condenser:
The special precoated Blue Fin Condensers can take on the harsh combination
of salty air, rain and other corrosive atmospheres. They are tested for 500 hours
of salt spray as per international standard JIS-Z-2371.
Energy efficient scroll compressors:
Scroll type, hermetically sealed highly energy efficient Copeland compressors.
Acoustically treated and polyester powder painted panels:
High density rigid acoustic board insulation, with over layer protection, dampens
the unit noise in the plant room. The panels are finished with glossy polyester
powder paint, for longer life.
Ready-made air outlet flange connections:
Units are provided with readymade flanged air outlets, to enable ease of
connection to the canvas or the duct flange.
Safety alarms and controls:
Built in safety features in the compressor and in the refrigeration circuits ensure
high level of protection to the unit.
TECHNICAL MANUAL
Tandem Compressor
10
TECHNICAL MANUAL
11
Operating Instructions:
Floor-Mounted Packaged ACs
CONTROLLER SPECIFICATIONS
A) Salient Features
1. Digital control and setting of temperature values in 1o C.
2. Automatic selection of compressors with run time Equalization.
3. Non Volatile Memory backup for all set value parameters.
4. Automatic starting of unit in case of power failure.
5. Built-in time delays for Compressor and fan.
6. Built-in Single phase/phase reversal protection.
B) Specifications
1. Power supply
0 - 65o C
3. Display
+ 1%
19 - 32o C
6. Temperature sensors
: If Blower Fan is ON, this LED indicator is Green and Red if it is OFF.
: If Fan Mode is Selected, then only this LED indicator glows blue.
COOL MODE LED : If Cool Mode is Selected, then only this LED indicator glows blue.
COMPR 1,2,3 LED : If Compr 1, 2, 3 are ON, this LED indicator is Green, and Red it it is OFF.
ON/OFFLED
UP/DN Key
12
TECHNICAL MANUAL
AC MODE Key
ON/OFF Key
RESET Key
: This key is used for resetting a Fault or for restarting the unit after
removing the existing fault.
D) Setting of Temperature
The 2-digit seven-segment display shows Actual Return Air Temperature. To
view Set Temp, press UP/DN key once. At any time of operation, if no key is
pressed for next successive 10 seconds, the display will show Actual Return Air
Temperature. Temperature can be set between 19 to 32o C by pressing the UP/
DN keys. After you press UP or DN key Display will indicate the old setting.
Press desired key to set new values. As soon as you reach the desired
Temperature stop adjusting the keys. The digits will start blinking for 5 seconds.
When the blinking stops the LED will show the Actual Return Air Temperature.
Recommended Temperature for optimum comfort and power saving is
24 +/- 1o C.
Display on LED
SPPR Fault
SP Pr (scrolling)
Cooling Tower
Fault
Ct
Fan Overload
Fault
BF
CF
CF
CF
13
Compr 1 Fault
High/Lo Pressure
HP LP
(scrolling)
Compr 2 Fault
High/Lo Pressure
HP LP
(scrolling)
Compr 3 Fault
High/Lo Pressure
HP LP
(scrolling)
Temp sensor is
open or bad.
tH
14
TECHNICAL MANUAL
F) Operating Instructions
Switch ON the unit by pressing ON/OFF key. ON LED will glow Green.
ON/OFF
Key
Fan
Mode
LED
Cool
Mode
LED
15
Operating Instructions:
Ducted Split ACs
CONTROLLER SPECIFICATIONS
A) Salient Features
1. Digital control and setting of Temperature values in 1 Deg. C.
2. Automatic selection of compressors with run time Equalization.
3. Non Volatile Memory backup for all set value parameter.
4. Automatic starting of unit in case of power failure.
5. Built-in time delays for Compressor and Fan.
B) Specifications
1. Powers supply
0 - 65C
3. Display
1%
19 - 32C
6. Temperature sensors
Pendant mounting
: If Blower Fan is ON, this LED indicator is Green and Red if it is OFF.
: If Fan Mode is Selected then only this LED indicator will glow blue.
: If Fan Speed is Selected LO then only this LED indicator will glow
( LO / HI ) Yellow and if selected HI then LED indicator will glow Blue.
COOL MODE LED : If Cool Mode is Selected then only this LED indicator will glow blue.
COMPR 1,2,3 LED : Compr 1,2,3 is ON, this LED indicator is Green and Red if it is OFF.
ON/OFF LED
UP/DN Key
: These keys are used for increment / decrement value of the selected
parameter.
16
TECHNICAL MANUAL
AC MODE Key
ON/OFF Key
RESET Key
: This key is used for resetting the Fault or for restarting the unit after removing
the existing fault.
D) Setting of Temperature
The 2-digit seven-segment display will show the Actual Return Air Temperature. To view Set Temp.
press UP/DN key once. At any time of the operation, if no key is pressed for next successive 10
seconds, the display will show Actual Return Air Temperature.
Temperature can be set between 19 to 32 Degree Centigrade by pressing UP/DN keys.
After you press UP or DN key Display will indicate the old setting. Press desired key to set new
values. As soon as you reach the desired Temperature stop adjusting the keys.
The digits will start blinking for 5 seconds. When the blinking stops the LED will show the Actual
Return Air Temperature.
Recommended Temperature for optimum comfort and power saving is 24 +/- 1 Deg. Cen.
Display on LED
SPPRFault
SP Pr (scrolling)
CF
Compr 1 Fault
High/Lo Pressure
HP LP
(scrolling)
Compr 2 Fault
High/Lo Pressure
HP LP
(scrolling)
Temp sensor is
open or bad.
tH
17
F) Operating Instructions
Switch ON the unit by pressing ON/OFF key. ON/OFF key LED will glow Green.
On/Off Key
Fan Mode
Cool
Mode
Speed HI
Speed LO
To Start Evaporator Blower (FAN Mode):
Press AC MODE Key to select the FAN Mode, then FAN Mode LED will glow.
The Blower Fan will come on immediately.
To Start Compressor (COOL Mode):
Press AC MODE Key once again to select the COOL Mode, then COOL Mode
LED will glow
& Fan Mode LED will be Off. The compressor will come on with pre-set delay of 1 minutes. In case
of multi compressor system the 2nd & 3rd compr. will come on after additional 10 sec. delay per
compressor. Simultaneously the compressor indication will start blinking in Green for time period
stated & glow continuously thereafter. Controller will select number of compressors based on
Actual Room Temp & Set Temp. as following
If Actual Temp =/> Set Value + 3, all the Compressors will be ON. (Only for DSA 903)
If actual Temp =/< Set Value + 2, only two Compressors will be ON. (for DSA 903 / 1322)
If actual Temp =/< Set Value + 1, only one Compressor will be ON.
If actual Temp =/< Set Value - 1, all the Compressors will be OFF.
18
TECHNICAL MANUAL
A healthy supply
CHECK IF INCOMING POWER IS AS PER THE RATED POWER SUPPLY:
VOLTS
380-420V
PHASE
THREE PHASE
CYCLES
50 Hz
TYPE
AC ONLY
Regular inspection
Regular inspection must be carried out as follows:
Item
Filter cleaning
Period
Once a week
Inspection Procedure
For Packaged AC
Filter
Water hose
Pull out from top ends and lift to remove the front
GRILLE from the UNIT. Then remove the
internal filter and wash it with water. Dry the filter
in the shade and re-install it.
For Ducted Split AC
Slide the filter from lifting upwards and wash it
with water. Dry the filter in the shade and re
install it.
19
Item
General compressor
checks
Period
Twice a year
Inspection Procedure
For Packaged AC
Oil leaks...
Verify that there are no oil leaks.
Crank case heater...Touch the heater body to
verify that it is warm.
Vibration isolation rubber ... Inspect the
vibration isolation rubber for wear.
For Ducted Split AC
Oil leaks...
Verify that there are no oil leaks.
Vibration isolation rubber ... Inspect the
vibration isolation rubber for wear.
Check for bolts tight at the mounting legs.
Twice a year
For Packaged AC
Four times
a year
20
TECHNICAL MANUAL
Item
Period
Inspection Procedure
For Packaged AC
Condenser Coil
and outdoor unit
Four times
a year
Four times
a year
Condenser
coils
Once in a
month
21
Troubleshooting
Faults and complaints in Packaged AC systems can be broadly classified under
three areas. The first step in troubleshooting is to identify the area and diagnose
the fault.
Diagnosing faults
Malfunctions can be classified under any of the following:
A. The Electrical Circuit
The malfuntioning of electrical circuit is due to LOW or HIGH voltage variations,
frequent power failures, loose electrical contacts, defective electrical components,
etc. Proper periodical maintenance of the unit will reduce such malfunctioning.
Problems due to power supply quality must be sorted out with the concerned
electricity board.
B. The Refrigeration Circuit
Improper cooling usually indicates poor performance of the refrigeration circuit.
Reasons may be poor servicing, low/high gas in the system, noncondensible
gases, and lower efficiency of the compressor. Periodical service helps avoid
such problems. The troubleshooting chart that follows will help isolate the exact
fault and suggest remedies.
C. The Conditioned Air Circuit
Less air flow, poor cooling, uneven temperature, excessive airleaks are complaints
that come under this classification. Most of them can be eliminated by periodical
servicing. The troubleshooting chart that follows will help isolate the exact fault
and suggest remedies.
CAUSE
REMEDY
1. COMPRESSOR
HIGH DISCHARGE PRESSURE
Replace compressor.
Excessive load
Defective suction valves
(continued)
22
TECHNICAL MANUAL
SYMPTOMS
COMPRESSOR SHORT
CYCLES ON LOW PRESSURE
COMPRESSOR TRIPS ON
HIGH PRESSURE
COMPRESSOR NOISY
CAUSE
REMEDY
Clean/replace strainer
Check thermostat
Clean air filter
Thermostat erratic
Check thermostat
Liquid knock
Replace compressor
SCROLL COMPRESSOR
COMPRESSOR PRESSURE
DOES NOT BUILD UP TO
HIGH PRESSURE
COMPRESSOR PRESSURE
DOES NOT GO DOWN ON
LOW PRESSURE
Do
Do
COMPRESSOR NOISY
Do
Do
2. BLOWER
FAN MOTOR
NOT STARTING
TRIPPING ON OVER LOAD
Reset relay
Check electrical circuit
and replace
Realign blower
Lubricate bearings
Tighten the belt
3. OVERALL UNIT
NOISY OPERATION
(continued)
23
SYMPTOMS
UNIT OPERATES
CONTINOUSLY
CAUSE
REMEDY
Loose panels
Shortage of refrigerant
Defective thermostat
Unit undersized
Charge gas
Replace thermostat
Recheck heatload
Less airflow
Defective thermostat
Contactor stuck up
Replace thermostat
Replace contactor
4. CONDITIONED AREA
DISCOMFORT IN THE
CONDITIONED AREA
TOO WARM IN
CONDITIONED SPACE
TOO COLD IN
CONDITIONED SPACE
24
TECHNICAL MANUAL
25
CAUSE
Faulty drift elimination
REMEDY
Check to be sure all Louvres,
Eliminator Sections or slats and
splash retainers are in place.
Top deck assemblies and wood fill
splash bars must be intact and
level. There must be no tendency
to channel water. Fill packs must
be intact and in place with no
sagging or gaps between packs.
Over-pumping
Fan
Motor
FAN NOISE
SCALE OR FOREIGN
SUBSTANCE IN WATER
SYSTEM
26
TECHNICAL MANUAL
Technical Specifications
MODELS
Floor-Mounted Packaged ACs
HiPer Plus + Packaged Airconditioner
Ducted Splits
Aircooled Ductable Splits with
Recip. Compressor
27
HiPer Plus
(Hi Sensible Air-cooled Packaged Airconditioners with
Scroll Compressors & High EER Condensers)
Model
Nominal Cooling Capacity
Units
DPAP-661S
DPAP-1052S
DPAP-1322S
DPAP-1983S
KCAL/HR
16500
26250
33000
49500
TR
5.5
8.75
11
16.5
W x D x H (mm)
Cooling Coil
Blower Fan
Centrifugal
Nominal Airflow
CMH
4675
7450
9350
14025
Fan Motor
Watts
560
1500
2250
3000
Compressor
Type
Quality
Scroll
1
Conrol Panel
Inbuilt
External Static
7.5
10
Outdoor Unit
(high ambient)
Dimensions
W x D x H (mm)
Condenser Coil
Quantity
Propeller
Nominal Airflow
CMH
7500
7500
7500
7500
Fan Motor
Watts
188
188
188
188
Kg
195
295
470
600
Kg
75
75
75
75
Quantity
Compressor Protection
Refrigerant Piping/Elecrical
Hot Gas Line
Od Inches X Gauge
Liquid Line
Condensate Drain GI / PVC
MCB Rating
Power Cable Incoming
Earthing Double Loop
28
Copper
7/8 X 16G
7/8 X 16G
7/8 X 16G
7/8 X 16G
5/8 X 19G
5/8 X 19G
5/8 X 19G
5/8 X 19G
32mm
32mm
32mm
32mm
32A
40A
40A
63A80A
4Cx6mm Sq Cu
4Cx10mm Sq Cu
4Cx10mm Sq Cu
4Cx16mm SQ CU
2 X 8 G GI Wires
2 X 8 G GI Wires
2 X 8 G GI Wires
2 X 8 G GI Wires
TECHNICAL MANUAL
HiSen
(Hi Sensible Air-cooled Packaged Airconditioners with
Scroll Compressors & Standard Condensers)
Model
Nominal Cooling Capacity
Units
DPAN-661S
DPAN-1052S
DPAN-1322S
DPAN-1983S
KCAL/HR
16500
26250
33000
49500
TR
5.5
8.75
11
16.5
W x D x H (mm)
Cooling Coil
Blower Fan
Centrifugal
Nominal Airflow
CMH
4675
7450
9350
14025
Watts
560
1500
2250
3000
Compressor
Type
10
Quality
Scroll
1
Conrol Panel
2
Digital-Micro Controller Type Inbuilt
External Static
MM
7.5
W x D x H (mm)
Outdoor Unit
(Normal ambient)
Dimensions
Condenser Coil
Quantity
Propeller
Nominal Airflow
CMH
7500
7500
7500
7500
Watts
240
240
240
240
Quantity
Indoor Unit Weight
Kg
195
295
470
600
Kg
86
86
86
86
Refrigerant Piping/Electrical
Hot Gas Line
Od Inches X Gauge
7/8 X 16g
Liquid Line
5/8 X 19g
5/8 X 19g
5/8 X 19g
5/8 X 19g
32mm
32mm
32mm
32mm
32A
40A
63A
63A
4Cx6mm Sq Cu
4Cx10mm Sq Cu
4Cx10mm Sq Cu
4Cx16mm Sq Cu
2 X 8 G GI Wires
2 X 8 G GI Wires
2 X 8 G GI Wires
2 X 8 G GI Wires
Copper
29
Units
DPAY-1321S
DPAY-1982S
Kcal /Hr
33000
49500
TR
11
16.5
W X D X H (mm)
Cooling Coil
Blower Fan
Centrifugal
Nominal Airflow
CMH
7480
11220
Fan Motor
Watts
1500
2250
External Static
mm
Compressor
Type
Scroll
Scroll
Quantity
1tandem
1 Tandem + 1 Single
Control Panel
Outdoor Unit
Dimensions
Quantity
Condenser Fan Type
Propeller
Propeller
Nominal Airflow
CMH
7500
7500
Fan Motor
Watts
240
240
Quanity
Indoor Unit Weight
Kg
305
503
Kg
86
86
Od Inches X Gauge
1 1/8 X 16g
5/8 X 19g
32mm
32mm
40A
63A
Refrigerant Piping/Elecrical
Hot Gas Line
Liquid Line
Condensate Drain GI / Pvc
MCB Rating
Power Cable Incoming
Earthing Double Loop
30
Copper
4cx10mm Sq Cu
4cx16mm Sq Cu
2 X 8 G Gi Wires
2 X 8 G Gi Wires
TECHNICAL MANUAL
Indoor Unit
Dimensions
Cooling Coil
Blower Fan
Nominal Airflow
Fan Motor Power
Compressor
Units
DPA-661BS
DPA-1052BS
DPA-1322BS
DPA-1983BS
New
DPA2642S
KCAL/HR
16500
26250
33000
49500
66000
TR
5.5
16.5
22
W x D x H (mm)
CMH
Watts
Type
Quality
Conrol Panel
External Static
MM
Outdoor Unit
(Normal ambient)
Dimensions
W x D x H (mm)
Condenser Coil
Quantity
Condenser
Fan Type
Nominal Airflow
CMH
Fan Motor Power
Watts
Quantity
Indoor Unit Weight
Kg
Outdoor Unit Weight
Kg
Safety Devices for
Compressor
Protection
3740
560
1
6
7500
240
1
195
86
Refrigerant Piping/Elecrical
Hot Gas Line
Liquid Line
Condensate
Drain Gi / PVC
Mcb Rating
Power Cable
Incoming
Earthing Double
Loop
Od Inches X
Gauge
Copper
8.75
11
4 Wire System-415V -3PH-50Hz
Propeller
7500
7500
240
240
1
1
295
302
86
86
Inbuilt Internal Thermal Protector
Internal Pressure Relief Valve
High Pressure Cutout
Low Pressure Cutout
7500
240
1
438
86
14960
3000
2
10
17000
260
2
580
120
7/8 X 16g
7/8 X 16g
7/8 X 16g
1 1 / 8 X 16g
5/8 X 19g
32mm
5/8 X 19g
32mm
5/8 X 19g
32mm
5/8 X 19g
32mm
7 / 8 X 19g
32mm
32A
4cx6mm Sq Cu
40A
4cx10mm Sq Cu
40A
4cx10mm Sq Cu
63A
4cx16mm Sq Cu
80A
4cx25mm Sq Cu
2 X 8 G GI Wires
2 X 8 G GI Wires
2 X 8 G GI Wires
2 X 8 G GI Wires
2 X 8 G GI Wires
31
32
Units
KCAL /HR
TR
WxDxH (mm)
Kg
Type
Quantity
mm
Ltrs
Kgs
DPW-661AS
DPW-1322AS
16500
33000
5.5
11
900x660x1700
1160x660x1700
253
390
Scroll
Scroll
1
2
6
8
Inbuilt Internal Thermal Protector
Internal Pressure Relief Valve
High Pressure Cutout
Low Pressure Cutout
1.77
1.77
380 / 420 V, 3 Phase, 50 Hz AC
342 / 462
4 Nos Rubber Mounts With Sleeves
38.1
38.1
DPW1983AS
49500
16.5
1500x750x1800
556
Scroll
3
9
1.77
38.1
mm
Nos
Bsp Mm
Od Cu Inches
3740
7480
560
1500
305 X 229
305 X 305
1
1
1440
Thermostatic Expansion Valve With External Eqaliser
517x828x10
517x828x10
1
2
457x933x10
3
Cu / 3/4"Od
1
Cu / 3/4"Od
1
1/2" / 3/8"
mm / Deg C
mm Fpt
Usgpm
Psig
1/2" / 3/8"
9.5mm/91 C
20
3.5
32mm
Copper
Cu / 3/4"Od
1
32 Mm
1/2" / 3/8"
11220
2250
381x 381
1
32A
4cx6mm Sq Cu
2 X 8 G GI Wires
6.3 Mm / 1/4"
40
9
0.0005
60
10
32mm
40A
4cx10mm Sq Cu
2 X 8 G GI Wires
63A
4cx16mm Sq Cu
2 X 8 G GI Wires
TECHNICAL MANUAL
Units
DSA-661DS
DSA-1001BS
DSA-1052BS
DSA-1322DS
DSA-2642S
Kcal /Hr
Tr
WxDx H (Mm)
Kg
16500
5.5
1220x675x450
68
24900
8.3
1525x675x450
96
26250
8.75
1525x675x450
96
33000
11
1850x675x450
127
66000
22
2160x1225x690
230
3740
375
270x270
1
280x345
Mm
Nos
Rpm
563 X 403
2
920/870
WxDx H (mm)
Type
Quantity
Kw
1020x406x954
Scroll
1
5.25
Ltrs
Kgs
Cmh
Watts
Kg
Od InchesxGauge
Copper
5650
5900
7480
375 Each
375 Each
375 Each
270x270
270x270
270x270
2
2
2
280x920
280x920
280x1095
Thermostatic Expansion Valve With External Eqaliser
468x403
468x403
593x403
3
3
3
920/870
920/870
920/870
1380x856x557
Scroll
1
7.86
1020x406x954
Scroll
2
4.14
1.77
14960
375 Each
305x229
3
342x1650
645x595
3
920/870
1020x406x954
Scroll
2
5.25
1435x620x947
Scroll
2
10.5
1.77
3.25
38.1
62.6
7500
240
1
107
17000
260
2
220
7/8 X 19g
5/8 X 19g
25mm
1 1/8 X 19g
5/8 X 19g
25mm
3/4 X 19g
1/2 X 19g
25mm
7/8 X 19g
5/8 X 19g
25mm
1 3/8 X 19g
7/8 X 19g
25mm
32A
4cx6mm Sq Cu
2 X 8 G Gi Wires
40A
4cx10mm Sq Cu
2 X 8 G Gi Wires
40A
4cx10mm Sq Cu
2 X 8 G Gi Wires
40A
4cx10mm Sq Cu
2 X 8 G Gi Wires
80A
4cx25mm Sq Cu
2 X 8 G Gi Wires
33
Units
DSA -361D
DSA-601D
DSA -903B
KCAL /HR
9000
15000
Tr
7.5
WxDxH (mm)
915x660x375
1219x660x457
1525x660x457
Indoor Unit
Dimensions
Cooling Coil
Blower Fan
Centrifugal
Nominal Airflow
CMH
2040
3400
5100
Fan Motor
Watts
188
375
750
2-1200/1150
2-920/870
2 - 1200 /1150
Quantity
Speed - Rpm
Power To Fan Motor
External Static
230 V - 1 Ph - 50 Hz
mm
7.5
WxDxH (Mm)
1020x406x686
1020x406x954
1360x550x856
Outdoor Unit
Dimensions
Quantity
Power Supply Source
415 V -3 Ph - 50HZ
Compressor
Quantity
Propeller
Nominal Airflow
CMH
4000
6800
--
Fan Motor
Watts
105
188
188
Quanity
Controller
Di. Pendant
Controller
Kg
60
86
96 kg
Kg
80
112
220
Refrigerant Piping/
Elecrical
Suction Line
Liquid Line
Condensate Drain
GI / PVC
MCB Rating
Power Cable Incoming
Earthing Double Loop
34
Copper
3/4 X 19g
7/8 X 19g
5/8 X 19g
3/8 X 19g
5/8 X 19g
3/8 X 19g
25mm
25mm
25mm
32A
32A
40A
4cx6mm Sq Cu
4cx6mm Sq Cu
4cx6mm Sq Cu
2X8 G GI Wires
2X8 G GI Wires
2x8 G GI Wires
TECHNICAL MANUAL
Units
DSW 361
DSW 661S
DSW 1052S
DSW 1322S
Kcal /Hr
9000
16500
26250
33000
Tr
5.5
8.75
11
W X D X H (mm)
Indoor Unit
Dimensions
Blower Fan
Nominal Airflow
Fan Motor
Centrifugal
CMH /CFM
2050/1200
3740/2200
5900/3440
7480/4400
Watts
180
375
375
375
Quantity
Speed - Rpm
1200/1100
2 - 920/870
2 - 920/870
2 - 920/870
Power To Fan
Motor
External Static
230 V - 1 Ph - 50 Hz
mm
Outdoor Unit
Dimensions
W X D X H (mm)
Quantity
983x713x546
Power Supply
Source
415 V -3 Ph - 50Hz
Compressor
Recip
Quantity
Scroll
Condenser
15.5
20
Water Inlet/Out
Let Size
mm
Cooling Water
Quantity
Usgpm
31.7BSP
11
Controller
20
Kg
60
68
96
127
Kg
130
149
144
149
Condenser Water In
32mm
40mm
32mm
40mm
32mm
40mm
32mm
40mm
Condensate Drain
GI / PVC
25mm
25mm
25mm
25mm
32A
32A
40A
63A
4cx4mm Sq Cu
4cx6mm Sq Cu
4cx10mm Sq Cu
4cx10mm Sq Cu
2 X 8 G GI Wires
2 X 8 G GI Wires
2 X 8 G GI Wires
2 X 8 G GI Wires
Mcb Rating
Power Cable
Incoming
Earthing Double Loop
Copper
35