High Efficiency

High Performance

Floor Mounted Packaged Airconditioners


&
Ducted Split Airconditioners

Floor Mounted Models :


DPA 661BS, 1052BS, 1322BS, 1983BS, 2642S
DPW 661AS, 1322AS, 1983AS
DPAY 1321S, 1982S
DPAP 661S, 1052S, 1322S, 1983S
DPAN 661S, 1052S, 1322S, 1983S

Ducted Split Models :


DSA 361D, 601D, 903B, 661DS, 1001BS,
1052BS, 1322DS, 2642S
DSW 361, 661S, 1052S, 1322S

TECHNICAL
MANUAL

First published June 2006


No part of this publication may be reproduced in any
manner whatsoever without permission in writing from the
Sr. General Manager, Packaged Airconditioning Division,
Blue Star Limited.
While due care has been taken to avoid errors or misinterpretation,
Blue Star Limited is neither liable nor responsible for consequence
of any action taken, on the basis of this publication.
Since ASHRAE standards use the FPS system, FPS nomenclature
is used in some places in this publication for convenient reference.
Published by Blue Star Limited,
9, Bazullah Road, TNagar, Chennai 600 017, India.
For restricted circulation only. Not for sale.

TECHNICAL MANUAL

Contents
Basics ....................................................................................... 2
What is airconditioning?
What is a Packaged Airconditioner?
Main Components
General layout of components
within the IDU
What is a Split Airconditioner?
What is a Ducted Split Airconditioner?
HiPer+ Packaged ACs
HiSen Packaged ACs
Scroll Compressor Technology
The Tandem Scroll

2
3
4
4
5
5
6
8
10
10

Operating Instructions:
Floor-Mounted Packaged ACs ............................................. 12
Controller Specifications

12

Operating Instructions:
Ducted Split ACs .................................................................... 16
Controller Specifications

16

Inspection & Maintenance .................................................... 19


A healthy supply
Regular inspection

19
19

Troubleshooting ..................................................................... 22
Diagnosing faults
Quick-check Troubleshooting Chart

22
22

Condenser Water Piping


Schematic ............................................................................... 25
Troubleshooting the
Water Circuit ........................................................................... 26
Technical Specifications ....................................................... 27
Schematics & Wiring Diagrams .......................................... 37
Warranty & Service ................................................................ 73

PACKAGED ACs & DUCTED SPLITS

Basics
What is airconditioning?
An airconditioning system consists of many pieces of mechanical and electrical
equipment assembled together to produce in an enclosed space acceptable
conditions of Temperature, Humidity, Air purity and Air motion.
The basic compression refrigeration cycle, the most important part of an
airconditioning system, is explained in the schematic diagram given below:

TECHNICAL MANUAL

What is a
Packaged Airconditioner?
When all the mechanical and electrical components of an airconditioning system
are assembled in a single package this is referred to as a Packaged Airconditioner.
They are generally floor-standing units.
Packaged ACs can be either air-cooled or water-cooled.

Air-cooled
Packaged Airconditioners
Air-cooled Packaged ACs use air to cool the refrigerant. The IDU contains all the
AC components except the condenser and its fan, which are separately housed
in the Outdoor Unit (ODU).
Electrical control of Aircooled Packaged AC models is at the bottom section of
the unit. The new facia controller is mounted on the upper panel section.

Water-cooled
Packaged Airconditioners
Water-cooled Packaged Airconditioners are compact floor standing units. All
components including the condenser are included in the unit. Water is pumped
into the unit to cool the refrigerant and the hot water is returned to external cooling
towers, cooled and recirculated. Only the piping connections for the water cycle
and the water cooling system are external. The electrical control panel is inbuilt
at the bottom of the unit. The new facia controller is mounted on the upper panel
section.
Indoor Unit

Outdoor Units

DPAP 5.5, 8.75, 11,


16.5 TR Models

22 TR Model

DPA, DPAN, DPAY 5.5, 8.75,


11, 16.5 TR Models

PACKAGED ACs & DUCTED SPLITS

Main Components
Air-cooled Packaged AC
A. Indoor Unit (IDU)

B. Outdoor Unit (ODU)

COMPRESSOR
COOLING COIL
EXPANSION VALVE
BLOWER FAN
BLOWER FAN MOTOR
FILTER
CONTROL PANEL

CONDENSER COIL
CONDENSER FAN WITH MOTOR

Water-cooled Packaged AC
A. Indoor Unit (IDU)
B. Water cooled condenser (EXTRA)

General layout of components within the IDU

TECHNICAL MANUAL

What is a Split Airconditioner?


A split airconditioner has two parts the Indoor Unit (IDU) and the Outdoor Unit
(ODU). The IDU is a concealed box that houses the cooling coil, centrifugal
blower fan, electrical motor, expansion device, dryer etc. assembled in a single
box. The ODU, which is the condensing unit, comprises of the compressor, aircooled condenser and a cooling fan.
The ODU and IDU are interconnected by refrigerant piping and power cables.
This keeps the noise of the compressor out of the airconditioned space.

What is a
Ducted Split Airconditioner?
A ducted split airconditioner is a split airconditioner, in which the IDU is housed
in a concealed box, usually mounted above the false ceiling. The air-flow from
the IDU is directed into a ducted air distribution network. Ducting therefore is a
key design aspect of these ACs.
The ODU is conveniently located on the skirting, sunshade, roof-top or mounted
on a special platform to be grouted into the wall.
Indoor Unit

Outdoor Units

3 TR Model

7.5 TR Model

5, 5.5, 8.75, 11 TR
Models

22 TR Model

PACKAGED ACs & DUCTED SPLITS

HiPer+ Packaged ACs


Blue Star's HiPer Plus Packaged Airconditioners offer high performance
machines even at high sensible loads and at 45o C ambients!
The HiPer Plus is specially designed to aircondition IT/ITES/BPO premises
situated in cities with harsh summers.
Blue Star's HiPer Plus Packaged Airconditioners feature:
Indoor units upsized to handle 90% sensible load delivering 550 CFM/ton,
and
Outdoor condenser upsized and system balanced to deliver full capacity at
45o C.
Hence, 100 tons of Hi Per Plus will suffice, where 125 tons of conventional
airconditioning was needed.
That makes 1 Ton load of Hi Per Plus equivalent to 1.25 nominal ton.

Features
Here are some of the features that make the Hi Per Plus Packaged Airconditioner
a high-end, superior quality product:
Efficient heat transfer:
The upsized evaporator offering enhanced surface area ensures removal of the
high sensible heat and handles a higher indoor air volume of 550 CFM per ton.
The inner grooved copper tubes with mechanically bonded slit aluminium fins
ensure efficient heat transfer.
Higher capacity evaporator fan:
Optimally selected DIDW forward curved centrifugal type fan exclusively designed
for delivering more air volume at 550 CFM/ton, with low noise levels.
Optimum expansion valve:
Optimally selected expansion valve with accurate preset super heat settings,
minimizes splash gas and eliminates the problem of improper cooling in the
evaporator.
Condenser with higher heat rejection capability:
The upsized condenser coil and twin fan condenser with higher heat rejection
capability, ensures lower condensing temperature, thereby delivering full capacity
even at temperatures as high as 45o C with extraordinary energy efficiency and
substantially lower power consumption.
Corrosion resistant blue fin condenser:
The special precoated Blue Fin Condensers are resistant to both chemical and
saline corrosion. They are tested for 500 hours of salt spray as per international
standard JIS-Z-2371.

TECHNICAL MANUAL

Energy efficient scroll compressors:


Scroll type, hermetically sealed highly energy efficient Copeland compressors.
Acoustically treated and polyester powder painted panels:
High-density EPE Insulation dampens the unit noise in the plant room.The panels
are finished with glossy polyster powder paint, for longer life.
Safety alarms and controls:
Built-in safety features in the compressor and in the refrigeration circuits ensure
high level of protection to the unit.
Advanced Microcomputer Controller:
A feature-packed microcomputer controller with Run Time Equalization, Auto
Restart after power failure, Fuzzy Logic, Self-Fault Diagnostics and much more.

PACKAGED ACs & DUCTED SPLITS

HiSen Packaged ACs


The HiSen Packaged Airconditioner is designed optimally with an upsized cooling
coil for 90% sensible heat load removal, and higher capacity indoor fan for
delivering 550 CFM per ton. The upsized-cooling coil ensures a 10% improvement
in cooling capacity and hence leads to a 10% power saving as well.

Features
Here are some of the features that make the HiSen Packaged Airconditioner a
high-end, superior quality product.
Efficient heat transfer cooling coil, with enhanced surface area:
The inner grooved copper tubes with mechanically bonded slit aluminum fins
ensure efficient heat transfer. The upsized-cooling coil offering enhanced surface
area ensures removal of the high sensible heat and handles a higher indoor air
volume of 550 CFM per ton.
Higher capacity evaporator fan:
Optimally selected DIDW forward curved centrifugal type fan exclusively designed
for delivering more air volume at 550 CFM/ton with low noise levels.
Optimum expansion valve:
Optimally selected expansion valve with accurate preset super heat settings,
minimizes splash gas and eliminates the problem of improper cooling in the
evaporator.
Corrosion resistant blue fin condenser:
The special precoated Blue Fin Condensers can take on the harsh combination
of salty air, rain and other corrosive atmospheres. They are tested for 500 hours
of salt spray as per international standard JIS-Z-2371.
Energy efficient scroll compressors:
Scroll type, hermetically sealed highly energy efficient Copeland compressors.
Acoustically treated and polyester powder painted panels:
High density rigid acoustic board insulation, with over layer protection, dampens
the unit noise in the plant room. The panels are finished with glossy polyester
powder paint, for longer life.
Ready-made air outlet flange connections:
Units are provided with readymade flanged air outlets, to enable ease of
connection to the canvas or the duct flange.
Safety alarms and controls:
Built in safety features in the compressor and in the refrigeration circuits ensure
high level of protection to the unit.

TECHNICAL MANUAL

Advanced Microcomputer Controller


The advanced microcomputer controller offers the following user-friendly features:
Run time equalization: Calculates and ensures equal run time for all
compressors.
Auto restart after power failure: No inconvenience of manual restart.
Memory back up: Keeps settings intact during power failures and
stoppages.
Built-in-time delay: Protects compressor from instant stops and starts.
Single phasing and reverse phase protection: Protects compressors from
damage.
Fuzzy logic: Cools intelligently based on the heat load, and hence increases
efficiency.
Self-fault diagnostics: Displays system trips, facilitating faster corrective
action.
Easy hook-up with fire alarm system: Potential free contacts provided for
hooking on to the fire alarm system, for stopping the units in the event of a
fire.

PACKAGED ACs & DUCTED SPLITS

Scroll Compressor Technology


The scroll technology is the most advanced compression technology with only
three moving parts and with 100 % volumetric efficiency ideally suitable for most
rugged commercial and industrial applications.
Scroll compressors have much better liquid refrigerant handling capability than
the other types of compressors due to the nature of scroll design.
Scroll compressor durability and reliability as well as its quiet operation are
inherent with the design of the scroll compressor.

The Tandem Scroll


Scroll-compressor-driven Packaged Airconditioners a few years ago paved the
way for the migration of the AC industry to a more energy efficient cooling platform,
the Tandem Scroll airconditioning system.

Tandem Compressor

A tandem scroll compressor consist of two individual compressors, mounted on


a common base, manifolded in to a single refrigerant circuit. A tandem compressor
(set) has the common suction, discharge, oil and also additional crank gas
equalizer lines between the two compressors.
For example, two scroll compressors are linked in tandem to form one tandem
scroll compressor.

10

TECHNICAL MANUAL

In a conventional multi-circuit air conditioning system (as in a 11 ton Scroll


Packaged AC), two 5.5-ton compressors drive two independent circuits, each
with its own evaporator and condenser, each circuit rated to 5.5 tons.
In a tandem scroll air conditioner, the 11-ton tandem scroll drives just one circuit,
which therefore consists of just one condenser and evaporator, both of which
are however designed for the full capacity of 11 tons.

Full Load Operation


Under full load conditions, the tandem scroll machine and the conventional scroll
machine behave almost identically.

Part Load Operation


The entire picture changes dramatically under part-load conditions.
Part-load conditions are those that prevail when an air-conditioned space is not
fully occupied or used with less occupancy, as for example a half-full theatre or
an empty showroom. In such cases, the entire capacity of the installed air
conditioning system is not required to cool the premises.
In both conventional and tandem scroll machines, one of the two compressors
switches off under part-load conditions. However, in the tandem scroll system,
the compressor that remains on utilizes the entire fully rated condenser for cooling
purposes. This seemingly minor fact is a significant air conditioning innovation,
remarkably increasing operating efficiency to the extent of 23%!
The tandem scroll advantage
Under favourable conditions, a compressor not only delivers higher tonnage,
but consumes less power thus giving a dramatic increase in EER
Under part-load conditions, using the double-capacity rated condenser is
a favourable operating condition for the compressor. Tandem Scroll
compressors should therefore deliver a higher EER under part-load conditions.

11

PACKAGED ACs & DUCTED SPLITS

Operating Instructions:
Floor-Mounted Packaged ACs
CONTROLLER SPECIFICATIONS
A) Salient Features
1. Digital control and setting of temperature values in 1o C.
2. Automatic selection of compressors with run time Equalization.
3. Non Volatile Memory backup for all set value parameters.
4. Automatic starting of unit in case of power failure.
5. Built-in time delays for Compressor and fan.
6. Built-in Single phase/phase reversal protection.

B) Specifications
1. Power supply

Single phase, Voltage: 175 to 260 V AC.


Frequency: 50 Hz + 3%

2. Operating temperature limit

0 - 65o C

3. Display

2 Digit 7-Segment LED Display,


LED indicators and touch key pad

4. Temperature control accuracy

+ 1%

5. Set temperature range

19 - 32o C

6. Temperature sensors

NTC thermister bit sensor with 5 meter long cable

7. LED Display & Keypad HANDSET Pendant mounting


8. Micro Computer Base unit

Base mounting (enclosed in fire-retardant box)

C) Description of LED Indicators & Keys on Handset


LED indicators & keys available on keypad of the PKG unit handset are as follows:
Reset LED

: This LED indicator flashes green once if any key is pressed. In


case of any fault, green flashes continuously.

FAN (Ev) LED

: If Blower Fan is ON, this LED indicator is Green and Red if it is OFF.

FAN MODE LED

: If Fan Mode is Selected, then only this LED indicator glows blue.

COOL MODE LED : If Cool Mode is Selected, then only this LED indicator glows blue.
COMPR 1,2,3 LED : If Compr 1, 2, 3 are ON, this LED indicator is Green, and Red it it is OFF.
ON/OFFLED

: This indicator is green if the unit is in ON mode and Red if it is in OFF.

UP/DN Key

: These keys are used to increment values of the selected parameter.

12

TECHNICAL MANUAL

AC MODE Key

: This key is used for selecting either Fan or Cool Mode.

ON/OFF Key

: This key is used for switching ON or OFF the unit.

RESET Key

: This key is used for resetting a Fault or for restarting the unit after
removing the existing fault.

D) Setting of Temperature
The 2-digit seven-segment display shows Actual Return Air Temperature. To
view Set Temp, press UP/DN key once. At any time of operation, if no key is
pressed for next successive 10 seconds, the display will show Actual Return Air
Temperature. Temperature can be set between 19 to 32o C by pressing the UP/
DN keys. After you press UP or DN key Display will indicate the old setting.
Press desired key to set new values. As soon as you reach the desired
Temperature stop adjusting the keys. The digits will start blinking for 5 seconds.
When the blinking stops the LED will show the Actual Return Air Temperature.
Recommended Temperature for optimum comfort and power saving is
24 +/- 1o C.

E) Fault & Alarms Display


LED indicators display various faults occurring in the unit as follows.
Nature of Fault

Display on LED

LED indication on Keypad &


correction of Fault.

SPPR Fault

SP Pr (scrolling)

RESET LED indicators will flash after


the fault is cleared, now press Reset
Key to restart the unit.

Cooling Tower
Fault

Ct

Co LED indicators will flash Red if the


fault exists. After the fault is cleared,
unit restarts automatically.

Fan Overload
Fault

BF

Ev LED indicator will flash Red if the


fault exists. After the fault is cleared,
unit restarts automatically.

Cond Fan1 MCB


trip/off Fault

CF

COMPR 1 LED indicator will flash Red


if the fault exists. After the fault is
cleared, unit restarts automatically.

Cond Fan2 MCB


trip/off Fault

CF

COMPR 2 LED indicator will flash


Red if the fault exists. After the fault
is cleared, unit restarts automatically.

Cond Fan3 MCB


trip/off Fault

CF

COMPR 3 LED indicator will flash


Red if the fault exists. After the fault
is cleared, unit restarts automatically.

13

PACKAGED ACs & DUCTED SPLITS

Compr 1 Fault
High/Lo Pressure

HP LP
(scrolling)

COMPR 1 LED indicator will flash


Red if the fault exists. RESET LED
indicator will flash after the fault is
cleared, now press Reset Key to
restart the unit.

Compr 2 Fault
High/Lo Pressure

HP LP
(scrolling)

COMPR 2 LED indicator will flash


Red if the fault exists. RESET LED
indicator will flash after the fault is
cleared, now press Reset Key to
restart the unit.

Compr 3 Fault
High/Lo Pressure

HP LP
(scrolling)

COMPR 3 LED indicator will flash


Red if the fault exists. RESET LED
indicator will flash after the fault is
cleared, now press Reset Key to
restart the unit.

Temp sensor is
open or bad.

tH

IF Temp sensor is open or bad then


only LED will display Fault. This fault
is Auto reset.

14

TECHNICAL MANUAL

F) Operating Instructions
Switch ON the unit by pressing ON/OFF key. ON LED will glow Green.

ON/OFF
Key

Fan
Mode
LED

Cool
Mode
LED

To Start Evaporator Blower (FAN Mode)


Press AC MODE Key to select the FAN Mode. FAN Mode LED will glow. The
Blower Fan will come on immediately (if fan overload relay is not tripped.)
To Start Compressor (COOL Mode)
Press AC MODE Key once again to select the COOL Mode. COOL Mode LED
will glow & Fan Mode LED will be Off. The compressor will come on with pre-set
delay of 2 minutes. In case of multi compressor system the 2nd & 3rd compr. will
come on after additional 15 sec. delay per compressor. Simultaneously the
compressor indication starts blinking Green & then glow continuously thereafter.
The Controller will select the number of compressors to be on based on Actual
Room Temp & Set Temp. as follows:
If actual Temp =/> Set Value + 3, all the Compressors will be ON.
If actual Temp =/< Set Value + 2, only two Compressors will be ON.
If actual Temp =/< Set Value + 1, only one Compressor will be ON.
If actual Temp =/< Set Value - 1, all the Compressors will be OFF.

15

PACKAGED ACs & DUCTED SPLITS

Operating Instructions:
Ducted Split ACs
CONTROLLER SPECIFICATIONS
A) Salient Features
1. Digital control and setting of Temperature values in 1 Deg. C.
2. Automatic selection of compressors with run time Equalization.
3. Non Volatile Memory backup for all set value parameter.
4. Automatic starting of unit in case of power failure.
5. Built-in time delays for Compressor and Fan.

B) Specifications
1. Powers supply

Single Phase, Voltage: 185 to 260 V AC.


Frequency: 50 Hz 3%

2. Operating temperature limit

0 - 65C

3. Display

2 Digit 7-Segament LED Display,


LED indicators and touch key pad

4. Temperature control accuracy

1%

5. Set temperature range

19 - 32C

6. Temperature sensors

NTC thermister Bit sensor


with 5 meter long cable

7. LED Display & Keypad HANDSET

Pendant mounting

8. Micro Computer Base Unit

Base mounting (enclosed in fire-retardant box)

C) Description of LED Indicators & Keys on Handset


Reset LED

: This LED indicator flashes once green if any key is pressed, or in


case of any fault, flashes green continuously.

FAN (Ev) LED

: If Blower Fan is ON, this LED indicator is Green and Red if it is OFF.

FAN MODE LED

: If Fan Mode is Selected then only this LED indicator will glow blue.

FAN SPEED LED

: If Fan Speed is Selected LO then only this LED indicator will glow
( LO / HI ) Yellow and if selected HI then LED indicator will glow Blue.

COOL MODE LED : If Cool Mode is Selected then only this LED indicator will glow blue.
COMPR 1,2,3 LED : Compr 1,2,3 is ON, this LED indicator is Green and Red if it is OFF.
ON/OFF LED

: This indicator is Green if the unit is in ON mode and Red if it is OFF.

UP/DN Key

: These keys are used for increment / decrement value of the selected
parameter.

16

TECHNICAL MANUAL

AC MODE Key

: This key is used for selecting either Fan or Cool Mode.

ON/OFF Key

: This key is used for switching ON or OFF the unit.

FAN SPEED Key

: This key is used for switching Fan speed High/Low.

RESET Key

: This key is used for resetting the Fault or for restarting the unit after removing
the existing fault.

D) Setting of Temperature
The 2-digit seven-segment display will show the Actual Return Air Temperature. To view Set Temp.
press UP/DN key once. At any time of the operation, if no key is pressed for next successive 10
seconds, the display will show Actual Return Air Temperature.
Temperature can be set between 19 to 32 Degree Centigrade by pressing UP/DN keys.
After you press UP or DN key Display will indicate the old setting. Press desired key to set new
values. As soon as you reach the desired Temperature stop adjusting the keys.
The digits will start blinking for 5 seconds. When the blinking stops the LED will show the Actual
Return Air Temperature.
Recommended Temperature for optimum comfort and power saving is 24 +/- 1 Deg. Cen.

E) Fault & Alarms Display


LED indicators displays the various faults occurring in the unit are as following.
Nature of Fault

Display on LED

LED indication on Keypad & correction of


Fault.

SPPRFault

SP Pr (scrolling)

RESET LED indicator will flash after the fault


s cleared, now press Reset Key to restart the
unit.

Cond Fan MCB


trip/off Fault

CF

Co LED indicator will flash Red if the fault


exists. This fault is Auto reset (Only for DSA
903 Model)

Compr 1 Fault
High/Lo Pressure

HP LP
(scrolling)

COMPR 1 LED indicator will


flash Red if the fault exists.RESET LED
indicator will flash after the fault is cleared,
now press Reset Key to restart the unit.
(Not for DSA903)

Compr 2 Fault
High/Lo Pressure

HP LP
(scrolling)

COMPR 2 LED indicator will flash Red


if the fault exists.RESET LED indicator will
flash after the fault is cleared, now press
Reset Key to restart the unit.
(Not for DSA903)

Temp sensor is
open or bad.

tH

IF Temp sensor is open or bad then only LED


will display Fault. This fault is Auto reset.

17

PACKAGED ACs & DUCTED SPLITS

F) Operating Instructions
Switch ON the unit by pressing ON/OFF key. ON/OFF key LED will glow Green.

On/Off Key

Fan Mode

Cool
Mode
Speed HI

Speed LO
To Start Evaporator Blower (FAN Mode):
Press AC MODE Key to select the FAN Mode, then FAN Mode LED will glow.
The Blower Fan will come on immediately.
To Start Compressor (COOL Mode):
Press AC MODE Key once again to select the COOL Mode, then COOL Mode
LED will glow
& Fan Mode LED will be Off. The compressor will come on with pre-set delay of 1 minutes. In case
of multi compressor system the 2nd & 3rd compr. will come on after additional 10 sec. delay per
compressor. Simultaneously the compressor indication will start blinking in Green for time period
stated & glow continuously thereafter. Controller will select number of compressors based on
Actual Room Temp & Set Temp. as following
If Actual Temp =/> Set Value + 3, all the Compressors will be ON. (Only for DSA 903)
If actual Temp =/< Set Value + 2, only two Compressors will be ON. (for DSA 903 / 1322)
If actual Temp =/< Set Value + 1, only one Compressor will be ON.
If actual Temp =/< Set Value - 1, all the Compressors will be OFF.

18

TECHNICAL MANUAL

Inspection & Routine Maintenance


Regular inspection of the IDU and ODU reduces failures and assures continuous
operation.

A healthy supply
CHECK IF INCOMING POWER IS AS PER THE RATED POWER SUPPLY:
VOLTS

380-420V

PHASE

THREE PHASE

CYCLES

50 Hz

TYPE

AC ONLY

Regular inspection
Regular inspection must be carried out as follows:
Item
Filter cleaning

Period
Once a week

Inspection Procedure
For Packaged AC
Filter
Water hose

Pull out from top ends and lift to remove the front
GRILLE from the UNIT. Then remove the
internal filter and wash it with water. Dry the filter
in the shade and re-install it.
For Ducted Split AC
Slide the filter from lifting upwards and wash it
with water. Dry the filter in the shade and re
install it.

19

PACKAGED ACs & DUCTED SPLITS

Item

General compressor
checks

Period

Twice a year

Inspection Procedure
For Packaged AC
Oil leaks...
Verify that there are no oil leaks.
Crank case heater...Touch the heater body to
verify that it is warm.
Vibration isolation rubber ... Inspect the
vibration isolation rubber for wear.
For Ducted Split AC
Oil leaks...
Verify that there are no oil leaks.
Vibration isolation rubber ... Inspect the
vibration isolation rubber for wear.
Check for bolts tight at the mounting legs.

Gas leak check

Twice a year

For Packaged AC

Remove the grille and front bottom cover


and conduct test for gas leaks in all
refrigerant pipe joints.
Gas leak check

Four times
a year

For Ducted Split AC


Indoor Unit

Remove the cover from the bottom and


conduct test for gas leaks inside portion of
the coil and remove filter for outer portion.
Outdoor Unit

Test for leaks in condenser coil tubes and


also compressor joints.

20

TECHNICAL MANUAL

Item

Period

Inspection Procedure
For Packaged AC

Condenser Coil
and outdoor unit

Four times
a year

Thorough cleaning of coil and the overall


unit can reduce atmospheric dust pollution
and improves performance.
For Ducted Split AC
Electrical circuits
& terminals

Four times
a year

Check all wires/cables and connector


terminals are tight with screwed ends.
If not, tighten and pull the wire for proper grip/
holding.

Condenser
coils

Once in a
month

Clean the condenser coils with portable


blower to blow out dust. This improves the
performance.

21

PACKAGED ACs & DUCTED SPLITS

Troubleshooting
Faults and complaints in Packaged AC systems can be broadly classified under
three areas. The first step in troubleshooting is to identify the area and diagnose
the fault.

Diagnosing faults
Malfunctions can be classified under any of the following:
A. The Electrical Circuit
The malfuntioning of electrical circuit is due to LOW or HIGH voltage variations,
frequent power failures, loose electrical contacts, defective electrical components,
etc. Proper periodical maintenance of the unit will reduce such malfunctioning.
Problems due to power supply quality must be sorted out with the concerned
electricity board.
B. The Refrigeration Circuit
Improper cooling usually indicates poor performance of the refrigeration circuit.
Reasons may be poor servicing, low/high gas in the system, noncondensible
gases, and lower efficiency of the compressor. Periodical service helps avoid
such problems. The troubleshooting chart that follows will help isolate the exact
fault and suggest remedies.
C. The Conditioned Air Circuit
Less air flow, poor cooling, uneven temperature, excessive airleaks are complaints
that come under this classification. Most of them can be eliminated by periodical
servicing. The troubleshooting chart that follows will help isolate the exact fault
and suggest remedies.

Quick-check Troubleshooting Chart


SYMPTOMS

CAUSE

REMEDY

1. COMPRESSOR
HIGH DISCHARGE PRESSURE

Non condensible gases


Over charged refrigerant
Choked condenser fins
Less ODU airflow

Purge the system


Remove excess
Clean the ODU coil
Correct fan direction

LOW DISCHARGE PRESSURE

Low refrigerant charge

Check for leaks, repair and


recharge

Low compression efficiency

Replace compressor.

Excessive load
Defective suction valves

Reduce fresh air & load


Replace compressor

HIGH SUCTION PRESSURE

(continued)

22

TECHNICAL MANUAL

SYMPTOMS

LOW SUCTION PRESSURE

COMPRESSOR SHORT
CYCLES ON LOW PRESSURE
COMPRESSOR TRIPS ON
HIGH PRESSURE

COMPRESSOR NOISY

CAUSE

REMEDY

Clogged suction strainer


No cooling load
Choked air filter

Clean/replace strainer
Check thermostat
Clean air filter

Thermostat erratic

Check thermostat

Air in the system


Overcharged gas
Condenser fan not working

Purge the system


Remove excess charge
Check ODU performance

Liquid knock

Check return air filter/


Check for coil chokeup

Defective valve reeds

Replace compressor

Compressor motor working


in reverse rotation

Interchange any two


phases of polarity for
changing direction

SCROLL COMPRESSOR
COMPRESSOR PRESSURE
DOES NOT BUILD UP TO
HIGH PRESSURE
COMPRESSOR PRESSURE
DOES NOT GO DOWN ON
LOW PRESSURE

Do

Do

COMPRESSOR NOISY

Do

Do

2. BLOWER
FAN MOTOR
NOT STARTING
TRIPPING ON OVER LOAD

Check power supply/fuses

Restore power supply

Check over load relay


Fuse blown

Reset relay
Check electrical circuit
and replace

Blower touching scroll


Bearing noise
Belt loose

Realign blower
Lubricate bearings
Tighten the belt

3. OVERALL UNIT
NOISY OPERATION

(continued)

23

PACKAGED ACs & DUCTED SPLITS

SYMPTOMS

UNIT OPERATES
CONTINOUSLY

CAUSE

REMEDY

Loose panels

Check & tighten screws

Shortage of refrigerant
Defective thermostat
Unit undersized

Charge gas
Replace thermostat
Recheck heatload

Less air flow


High humidity
Poor cooling

Check air filter / belt


Regulate fresh air
Check refrigeration circuit

Excess heat load


Inadequate cooling

Check & regulate heat load


Check compressor ON/
Check filter choke up

Less airflow

Check reversal of blower fan

Compressor trips soon


after start

Change incoming supply


phase polarity on any two
phases (for scroll compressor)

Defective thermostat
Contactor stuck up

Replace thermostat
Replace contactor

4. CONDITIONED AREA
DISCOMFORT IN THE
CONDITIONED AREA

TOO WARM IN
CONDITIONED SPACE

TOO COLD IN
CONDITIONED SPACE

24

TECHNICAL MANUAL

Condenser Water Piping Schematic

25

PACKAGED ACs & DUCTED SPLITS

Troubleshooting the Water Circuit


SYMPTOMS
EXCESSIVE WATER DRIFT

CAUSE
Faulty drift elimination

REMEDY
Check to be sure all Louvres,
Eliminator Sections or slats and
splash retainers are in place.
Top deck assemblies and wood fill
splash bars must be intact and
level. There must be no tendency
to channel water. Fill packs must
be intact and in place with no
sagging or gaps between packs.

Over-pumping

UNUSUAL FAN DRIVE


VIBRATION

Loose bolts & cap screws

Fan

Reduce water flow to tower to


design conditions or use larger
metering orifices.
Tighten all bolts and cap screws on
all mechanical equipment and
supports.
Be sure blades are properly
positioned in correct sockets.
Check match numbers. Make
certain all blades are as far from
centre of fan as safety devices
permit. All blades must be pitched
the same. Clean-off deposit build
up on blades.

Motor

Disconnect load and operate


motor. If motor still vibrates, check
for bent shaft or unbalanced rotor.
Replace shaft or rebalance rotor.

FAN NOISE

Loose fan hub cover

Tighten fan hub cover fasteners.

SCALE OR FOREIGN
SUBSTANCE IN WATER
SYSTEM

Insufficient blow down

Check water quality

Poor water quality

Install Water Treatment System

26

TECHNICAL MANUAL

Technical Specifications
MODELS
Floor-Mounted Packaged ACs
HiPer Plus + Packaged Airconditioner

DPAP 661S, 1052S, 1322S, 1983S

HiSen Packaged Airconditioner

DPAN 661S, 1052S, 1322S, 1983S

Tandem Packaged Airconditioner

DPAY 1321S, 1982S

Air Cooled Packaged Airconditioner

DPA 661BS, 1052BS, 1322BS,


1983BS, 2642S

Water Cooled Packaged Aircondionter

DPW 661AS, 1322AS, 1983AS

Ducted Splits
Aircooled Ductable Splits with
Recip. Compressor

DSA 361D, 601D, 903B

Air Cooled Ductable Splits with


Scroll Compressor

661DS, 1001BS, 1052BS, 1322DS


2642S

Water Cooled Ductable Splits with


Scroll Compressor and Recip

DSW361, 661S, 1052S, 1322S

27

PACKAGED ACs & DUCTED SPLITS

HiPer Plus
(Hi Sensible Air-cooled Packaged Airconditioners with
Scroll Compressors & High EER Condensers)
Model
Nominal Cooling Capacity

Units

DPAP-661S

DPAP-1052S

DPAP-1322S

DPAP-1983S

KCAL/HR

16500

26250

33000

49500

TR

5.5

8.75

11

16.5

4 Wire System-415V -3PH-50Hz


Indoor Unit
Dimensions

W x D x H (mm)

900 x 660 x 1700

1160 x 660 x 1700

1500 x 750 x 1800

Cooling Coil

Internally Grooved Copper Tubing with Slit Fins

Blower Fan

Centrifugal

1500 x 930 x 2000

Nominal Airflow

CMH

4675

7450

9350

14025

Fan Motor

Watts

560

1500

2250

3000

Compressor

Type
Quality

Scroll
1

Conrol Panel

Inbuilt

External Static

7.5

1020 x 406 x 1270

1020 x 406 x 1270

1020 x 406 x 1270

10

Outdoor Unit
(high ambient)
Dimensions

W x D x H (mm)

Condenser Coil

Inner Grooved with Slit Fins-Anti Corrosion Coating

Quantity

Condenser Fan Type

1020 x 406 x 1270

Propeller

Nominal Airflow

CMH

7500

7500

7500

7500

Fan Motor

Watts

188

188

188

188

Indoor Unit Weight

Kg

195

295

470

600

Outdoor Unit Weight

Kg

75

75

75

75

Quantity

Safety Devices for

Inbuilt Internal Thermal Protector

Compressor Protection

Internal Pressure Relief Valve


High Pressure Cutout
Low Pressure Cutout

Refrigerant Piping/Elecrical
Hot Gas Line

Hard Drawn Grade - L Copper Tubes Only

Od Inches X Gauge

Liquid Line
Condensate Drain GI / PVC
MCB Rating
Power Cable Incoming
Earthing Double Loop

28

Copper

7/8 X 16G

7/8 X 16G

7/8 X 16G

7/8 X 16G

5/8 X 19G

5/8 X 19G

5/8 X 19G

5/8 X 19G

32mm

32mm

32mm

32mm

32A

40A

40A

63A80A

4Cx6mm Sq Cu

4Cx10mm Sq Cu

4Cx10mm Sq Cu

4Cx16mm SQ CU

2 X 8 G GI Wires

2 X 8 G GI Wires

2 X 8 G GI Wires

2 X 8 G GI Wires

TECHNICAL MANUAL

HiSen
(Hi Sensible Air-cooled Packaged Airconditioners with
Scroll Compressors & Standard Condensers)
Model
Nominal Cooling Capacity

Units

DPAN-661S

DPAN-1052S

DPAN-1322S

DPAN-1983S

KCAL/HR

16500

26250

33000

49500

TR

5.5

8.75

11

16.5

1500 x 750 x 1800

1500 x 930 x 2000

4 Wire System-415V -3PH-50Hz


Indoor Unit
Dimensions

W x D x H (mm)

900 x 660 x 1700

Cooling Coil

1160 x 660 x 1700

Internally Grooved Copper Tubing with Slit Fins

Blower Fan

Centrifugal

Nominal Airflow

CMH

4675

7450

9350

14025

Fan Motor Power

Watts

560

1500

2250

3000

Compressor

Type

10

Quality

Scroll
1

Conrol Panel

2
Digital-Micro Controller Type Inbuilt

External Static

MM

7.5

W x D x H (mm)

1020 x 406 x 954

1020 x 406 x 954

1020 x 406 x 954

Outdoor Unit
(Normal ambient)
Dimensions
Condenser Coil

Inner Grooved with Slit Fins-Anti Corrosion Coating

Quantity

Condenser Fan Type

1020 x 406 x 954

Propeller

Nominal Airflow

CMH

7500

7500

7500

7500

Fan Motor Power

Watts

240

240

240

240

Quantity
Indoor Unit Weight

Kg

195

295

470

600

Outdoor Unit Weight

Kg

86

86

86

86

Safety Devices for


Compressor Protection

Inbuilt Internal Thermal Protector


Internal Pressure Relief Valve
High Pressure Cutout
Low Pressure Cutout

Refrigerant Piping/Electrical
Hot Gas Line
Od Inches X Gauge

Hard Drawn Grade - L Copper Tubes Only


7/8 X 16g
7/8 X 16g
7/8 X 16g

7/8 X 16g

Liquid Line

5/8 X 19g

5/8 X 19g

5/8 X 19g

5/8 X 19g

32mm

32mm

32mm

32mm

32A

40A

63A

63A

4Cx6mm Sq Cu

4Cx10mm Sq Cu

4Cx10mm Sq Cu

4Cx16mm Sq Cu

2 X 8 G GI Wires

2 X 8 G GI Wires

2 X 8 G GI Wires

2 X 8 G GI Wires

Condensate Drain GI/PVC


MCB Rating
Power Cable Incoming
Earthing Double Loop

Copper

29

PACKAGED ACs & DUCTED SPLITS

Air-cooled Packaged Airconditioners


(With Scroll Tandem Compressors)
Model
Nominal Cooling Capacity
Indoor Unit
Dimensions

Units

DPAY-1321S

DPAY-1982S

Kcal /Hr

33000

49500

TR

11

16.5

W X D X H (mm)

1160 X 660 X 1700

1500 X 750 X 1800

Cooling Coil
Blower Fan

Centrifugal

Nominal Airflow

CMH

7480

11220

Fan Motor

Watts

1500

2250

External Static

mm

Compressor

Type

Scroll

Scroll

Quantity

1tandem

1 Tandem + 1 Single

Safety Devices For


Compressor Protection

Inbuilt Internal Thermal Protector


Internal Pressure Relief Valve
High Pressure Cutout
Low Pressure Cutout

Control Panel
Outdoor Unit
Dimensions

Digital -micro Cotroller Type


W X D X H (mm)

Quantity
Condenser Fan Type

1020 X 406 X 954

1020 X 406 X 954

Propeller

Propeller

Nominal Airflow

CMH

7500

7500

Fan Motor

Watts

240

240

Quanity
Indoor Unit Weight

Kg

305

503

Outdoor Unit Weight

Kg

86

86

Od Inches X Gauge

1 1/8 X 16g

1 1/8 Tandem & 7/8 Solo 16 g

5/8 X 19g

5/8 X 19g Both

32mm

32mm

40A

63A

Refrigerant Piping/Elecrical
Hot Gas Line
Liquid Line
Condensate Drain GI / Pvc
MCB Rating
Power Cable Incoming
Earthing Double Loop

30

Copper

4cx10mm Sq Cu

4cx16mm Sq Cu

2 X 8 G Gi Wires

2 X 8 G Gi Wires

TECHNICAL MANUAL

Air-cooled Packaged Airconditioners


(With Scroll Compressors)
Model
Nominal Cooling
Capacity

Indoor Unit
Dimensions
Cooling Coil
Blower Fan
Nominal Airflow
Fan Motor Power
Compressor

Units

DPA-661BS

DPA-1052BS

DPA-1322BS

DPA-1983BS

New
DPA2642S

KCAL/HR

16500

26250

33000

49500

66000

TR

5.5

16.5

22

W x D x H (mm)

900 x 660 x 1700

CMH
Watts
Type
Quality

Conrol Panel
External Static
MM
Outdoor Unit
(Normal ambient)
Dimensions
W x D x H (mm)
Condenser Coil
Quantity
Condenser
Fan Type
Nominal Airflow
CMH
Fan Motor Power
Watts
Quantity
Indoor Unit Weight
Kg
Outdoor Unit Weight
Kg
Safety Devices for
Compressor
Protection

1160 x 660 x 1700


1160 x 660 x 1700
1500 x 750 x 1800
Internally Grooved Copper Tubing with Slit Fins
Centrifugal
5900
7480
11220
1100
1500
2250
Hermetically Sealed Scroll
2
2
3
Digital-Micro Controller Type (Inbuilt)
7.5
8
9

1500 x 930 x 2000

1020 x 406 x 954


1020 x 406 x 954
1020 x 406 x 954
1020 x 406 x 954
Inner Grooved with Slit Fins-Anti Corrosion Blue fin coated
1
2
2
3

1435 x 620 x 947

3740
560
1
6

7500
240
1
195
86

Refrigerant Piping/Elecrical
Hot Gas Line
Liquid Line
Condensate
Drain Gi / PVC
Mcb Rating
Power Cable
Incoming
Earthing Double
Loop

Od Inches X
Gauge

Copper

8.75
11
4 Wire System-415V -3PH-50Hz

Propeller
7500
7500
240
240
1
1
295
302
86
86
Inbuilt Internal Thermal Protector
Internal Pressure Relief Valve
High Pressure Cutout
Low Pressure Cutout

7500
240
1
438
86

14960
3000
2
10

17000
260
2
580
120

Hard Drawn Grade - L Copper Tubes Only


7/8 X 16g

7/8 X 16g

7/8 X 16g

7/8 X 16g

1 1 / 8 X 16g

5/8 X 19g
32mm

5/8 X 19g
32mm

5/8 X 19g
32mm

5/8 X 19g
32mm

7 / 8 X 19g
32mm

32A
4cx6mm Sq Cu

40A
4cx10mm Sq Cu

40A
4cx10mm Sq Cu

63A
4cx16mm Sq Cu

80A
4cx25mm Sq Cu

2 X 8 G GI Wires

2 X 8 G GI Wires

2 X 8 G GI Wires

2 X 8 G GI Wires

2 X 8 G GI Wires

31

PACKAGED ACs & DUCTED SPLITS

Water-cooled Packaged Airconditioners


(With Scroll Compressors)
Model
Nominal Cooling Capacity
Dimensions
Weight
Compressor
Type
External Static
Compressor Protection

Oil Charge (Ltrs)


Power Supply
Operating Voltage
Mounting Arrangement
Compressor Wt.
Evaporator Coil
Fin Material
Tube Material
Tube Dia Mm / Inches
Evaporator Blower
Blower Fan
Nominal Airflow
Fan Motor
Blower Size (Od Xlg)
No Of Blowers
Motor Rpm
Expansion Device
Air Filter Size
No Of Filters
Condenser Water Cooled
Type
Tube Material/ Od
Quantity
Water Connections In & Out
Refrigerant Conn. -Hs
Inlet/ Liquid
Fusible Plug Size /
Melting Temp.
Drain Plug And Vent
Water Quantity
Pressure Drop
Fouling Factor Sq. Ft. Hr.
Deg. F/Btu
Drain Piping/Elecrical
Condensate Drain
GI / PVC
MCB Rating
Power Cable Incoming
Earthing Double Loop

32

Units
KCAL /HR
TR
WxDxH (mm)
Kg
Type
Quantity
mm

Ltrs

Kgs

DPW-661AS

DPW-1322AS

16500
33000
5.5
11
900x660x1700
1160x660x1700
253
390
Scroll
Scroll
1
2
6
8
Inbuilt Internal Thermal Protector
Internal Pressure Relief Valve
High Pressure Cutout
Low Pressure Cutout
1.77
1.77
380 / 420 V, 3 Phase, 50 Hz AC
342 / 462
4 Nos Rubber Mounts With Sleeves
38.1
38.1

DPW1983AS
49500
16.5
1500x750x1800
556
Scroll
3
9

1.77

38.1

Aluminium 0.16mm Thick


Copper
9.5 / 3/8"
Centrifugal Forward
Curved Double Inlet
CMH
Watts
mm
Qtty

mm
Nos

Bsp Mm
Od Cu Inches

3740
7480
560
1500
305 X 229
305 X 305
1
1
1440
Thermostatic Expansion Valve With External Eqaliser
517x828x10
517x828x10
1
2

457x933x10
3

Cu / 3/4"Od
1

Cu / 3/4"Od
1

1/2" / 3/8"

mm / Deg C
mm Fpt
Usgpm
Psig

1/2" / 3/8"

9.5mm/91 C

20
3.5

32mm

Copper

Cu / 3/4"Od
1
32 Mm
1/2" / 3/8"

11220
2250
381x 381
1

32A
4cx6mm Sq Cu
2 X 8 G GI Wires

6.3 Mm / 1/4"
40
9
0.0005

60
10

GI/ Class B Pipes


32mm

32mm

40A
4cx10mm Sq Cu
2 X 8 G GI Wires

63A
4cx16mm Sq Cu
2 X 8 G GI Wires

TECHNICAL MANUAL

Air-cooled Ductable Split Airconditioners


(With Scroll Compressors)
Model
Indoor Unit
Nominal Cooling Capacity
Dimensions
Indoor Unit Weight
Evaporator Coil
Fin Material
Tube Material
Tube Dia Mm / Inches
Evaporator Blower
Blower Fan
Nominal Airflow
Fan Motor
Blower Size (Od Xlg)
No Of Blowers
Air Outlet Size
Expansion Device
Air Filter Size
No Of Filters
Speed Rpm
Outdoor Unit
Dimensions
Compressor
Type
Power Input Each
Compressor
Compressor Protection

Oil Charge (Ltrs)


Power Supply
Operating Voltage
Mounting Arrangement
Compressor Wt.
Condenser Coil
Quantity
Condenser Fan Type
Nominal Airflow
Fan Motor
Quanity
Weight
Refrigerant Piping/
Elecrical
Suction Line
Liquid Line
Condensate Drain
GI / PVC
Mcb Rating
Power Cable Incoming
Earthing Double Loop

Units

DSA-661DS

DSA-1001BS

DSA-1052BS

DSA-1322DS

DSA-2642S

Kcal /Hr
Tr
WxDx H (Mm)
Kg

16500
5.5
1220x675x450
68

24900
8.3
1525x675x450
96

26250
8.75
1525x675x450
96

33000
11
1850x675x450
127

66000
22
2160x1225x690
230

Aluminium 0.16mm Thick


Copper
9.5 / 3/8"
Centrifugal Forward Curved Double InletCentrifugal Forward Curved Double Inlet
Cmh
Watts
Mm
Qtty
Mm

3740
375
270x270
1
280x345

Mm
Nos
Rpm

563 X 403
2
920/870

WxDx H (mm)
Type
Quantity
Kw

1020x406x954
Scroll
1
5.25

Ltrs

Kgs

Cmh
Watts
Kg

Od InchesxGauge

Copper

5650
5900
7480
375 Each
375 Each
375 Each
270x270
270x270
270x270
2
2
2
280x920
280x920
280x1095
Thermostatic Expansion Valve With External Eqaliser
468x403
468x403
593x403
3
3
3
920/870
920/870
920/870
1380x856x557
Scroll
1
7.86

1020x406x954
Scroll
2
4.14

Inbuilt Internal Thermal Protector


Internal Pressure Relief Valve
High Pressure Cutout
Low Pressure Cutout
1.77
3.25

1.77

380 / 420 V , 3 Phase, 50 Hz Ac


342 / 462
4 Nos Rubber Mounts With Sleeves
38.1
69.4
35.4
3/8" (9.5mm) Cu Tubes And 0.16 Mm Thick Al Fins
1
2
2
Four Blade Propeller Fan
7500
10200
7500
240
586
240
1
1
1
107
188
107
Hard Drawn Grade - L Copper Tubes Only

14960
375 Each
305x229
3
342x1650
645x595
3
920/870

1020x406x954
Scroll
2
5.25

1435x620x947
Scroll
2
10.5

1.77

3.25

38.1

62.6

7500
240
1
107

17000
260
2
220

7/8 X 19g
5/8 X 19g
25mm

1 1/8 X 19g
5/8 X 19g
25mm

3/4 X 19g
1/2 X 19g
25mm

7/8 X 19g
5/8 X 19g
25mm

1 3/8 X 19g
7/8 X 19g
25mm

32A
4cx6mm Sq Cu
2 X 8 G Gi Wires

40A
4cx10mm Sq Cu
2 X 8 G Gi Wires

40A
4cx10mm Sq Cu
2 X 8 G Gi Wires

40A
4cx10mm Sq Cu
2 X 8 G Gi Wires

80A
4cx25mm Sq Cu
2 X 8 G Gi Wires

33

PACKAGED ACs & DUCTED SPLITS

Air-cooled Ductable Split Airconditioners


(With Recip Compressors)
Model
Nominal Cooling Capacity

Units

DSA -361D

DSA-601D

DSA -903B

KCAL /HR

9000

15000

Tr

7.5

WxDxH (mm)

915x660x375

1219x660x457

1525x660x457

Indoor Unit
Dimensions
Cooling Coil

Inner Grooved Copper Tubing With Slit Fins

Blower Fan

Centrifugal

Nominal Airflow

CMH

2040

3400

5100

Fan Motor

Watts

188

375

750

2-1200/1150

2-920/870

2 - 1200 /1150

Quantity
Speed - Rpm
Power To Fan Motor
External Static

230 V - 1 Ph - 50 Hz
mm

7.5

WxDxH (Mm)

1020x406x686

1020x406x954

1360x550x856

Outdoor Unit
Dimensions
Quantity
Power Supply Source

415 V -3 Ph - 50HZ

Compressor

Hermetically Sealed Recip Compressor

Quantity

Condenser Fan Type

Propeller

Nominal Airflow

CMH

4000

6800

--

Fan Motor

Watts

105

188

188

Quanity
Controller

Elec. Micro Processor Pendant Controller

Di. Pendant
Controller

Indoor Unit Weight

Kg

60

86

96 kg

Outdoor Unit Weight

Kg

80

112

220

Refrigerant Piping/
Elecrical
Suction Line

Hard Drawn Grade - L Copper Tubes Only


Od Inches X Gauge

Liquid Line
Condensate Drain
GI / PVC
MCB Rating
Power Cable Incoming
Earthing Double Loop

34

Copper

3/4 X 19g

7/8 X 19g

5/8 X 19g

3/8 X 19g

5/8 X 19g

3/8 X 19g

25mm

25mm

25mm

32A

32A

40A

4cx6mm Sq Cu

4cx6mm Sq Cu

4cx6mm Sq Cu

2X8 G GI Wires

2X8 G GI Wires

2x8 G GI Wires

TECHNICAL MANUAL

Water-cooled Ductable Split Airconditioners


(With Recip & Scroll Compressors)
Model
Nominal Cooling
Capacity

Units

DSW 361

DSW 661S

DSW 1052S

DSW 1322S

Kcal /Hr

9000

16500

26250

33000

Tr

5.5

8.75

11

W X D X H (mm)

953 X 585 X 381

1220 X 675 X 457

1525 X 675 X 457

1830 X 675 X 457

Indoor Unit
Dimensions
Blower Fan
Nominal Airflow
Fan Motor

Centrifugal
CMH /CFM

2050/1200

3740/2200

5900/3440

7480/4400

Watts

180

375

375

375

Quantity
Speed - Rpm

1200/1100

2 - 920/870

2 - 920/870

2 - 920/870

Power To Fan
Motor
External Static

230 V - 1 Ph - 50 Hz
mm

Outdoor Unit
Dimensions

W X D X H (mm)

Quantity

983x713x546

Power Supply
Source

415 V -3 Ph - 50Hz

Compressor

Recip

Quantity

Scroll

Condenser

15.5

20

Shell And Tube

Water Inlet/Out
Let Size

mm

Cooling Water
Quantity

Usgpm

31.7BSP
11

Controller

20

Electronic Micro Processor Pendant Controller

Indoor Unit Weight

Kg

60

68

96

127

Outdoor Unit Weight

Kg

130

149

144

149

Cds Water Piping/


Electrical

GI/ Ms Class B Pipes

Condenser Water In

32mm

40mm

32mm

40mm

Condenser Water Out

32mm

40mm

32mm

40mm

Condensate Drain
GI / PVC

25mm

25mm

25mm

25mm

32A

32A

40A

63A

4cx4mm Sq Cu

4cx6mm Sq Cu

4cx10mm Sq Cu

4cx10mm Sq Cu

2 X 8 G GI Wires

2 X 8 G GI Wires

2 X 8 G GI Wires

2 X 8 G GI Wires

Mcb Rating
Power Cable
Incoming
Earthing Double Loop

Copper

35

PACKAGED ACs & DUCTED SPLITS

36