HVAC Designs, Inc. // Collection Vol. 1

HVAC SYMBOLS
CEILING REGISTER
1 WAY THROW
FMC 603.15

RECTANGULAR
DUCTWORK
FMC SECTION 603

THERMOSTAT @ 60"
ABOVE FLOOR
FEC 13-613

CEILING
REGISTER
2 WAY THROW
FMC 603.15

FLEXIBLE
DUCTWORK
FMC SECTION 603

WALL MOUNTED
HUMIDISTAT @ 60"
ABOVE FLOOR

AIR DISTRIBUTION
BOXES FMC
SECTION 603

CEILING REGISTER
4 WAY THROW
FMC 603.15

RETURN AIR
PLENUM TRUNK
FMC SECTION 602

EQUIPMENT
ACCESS PANEL
FMC SECTION 306

CEILING REGISTER
CORNER THROW
FMC 603.15

SUPPLY AIR
PLENUM TRUNK
FMC SECTION 602

EXHAUST FAN
EF-1 or as NOTED
FMC SECTION 403

WALL REGISTER
2 WAY THROW
FMC 603.15

AIR VOLUME
CONTROL DAMPER
FMC 603.15

ZD

ZONE CONTROL
AIR DAMPER
FMC 303 -- 312

FLOOR REGISTER
2 WAY THROW
FMC 603.15

DUCT MOUNTED
FIRE DAMPER
FMC SECTION 607

BP

BYPASS AIR
DAMPER
FMC 303 -- 312

FLOOR GRILLE
FILTER RETURN
AIR FMC 603.15

DRYER VENT
ROOF / WALL
CAP FMC 504

RANGE VENT
ROOF / WALL CAP
FMC 505 - 506

CEILING GRILLE
FILTER RETURN
AIR FMC 603.15

CEILING GRILLE
DUCTED T/A
FMC 603.15

CONDENSATE
DRAIN TO GRASS
FMC SECTION 307

WALL GRILLE
DIRECT T/ A
FMC 603.15

CONDENSATE
TO DRYWELL
FMC SECTION 307

AFF = ABOVE FINISH FLOOR


AHU = AIR HANDLING UNIT
BP = BYPASS DAMPER
BD = BAROMETRIC DAMPER

ZONE

ROOM NAME

OCCUPANTS

DURATION

SUPPLY AIR CFM

RETURN AIR CFM

EXHAUST AIR CFM

FRESH AIR CFM

1
1
1
1
1
1
X
ZONE

Class
Science
Corridor 1
Locker G
Restroom G
Restroom B
X
ROOM NAME

17
17
0
0
0
0
X
OCCUPANTS

> 3 HRS
> 3 HRS
N/A
N/A
N/A
N/A
X
DURATION

797
686
97
51
88
81
X
SUPPLY AIR CFM

795
685
0
0
0
0
X
RETURN AIR CFM

0
0
0
300
300
300
X
EXHAUST AIR CFM

255
255
0
0
0
0
X
FRESH AIR CFM

2
2
2
2
2
2
2
X
ZONE

Mech
Locker B
Restroom
Lobby
Office
Reading
Corridor 2
X
ROOM NAME

0
0
0
0
2
17
0
X
OCCUPANTS

> 3 HRS
N/A
N/A
N/A
> 3 HRS
> 3 HRS
N/A
X
DURATION

51
36
29
535
527
485
137
X
SUPPLY AIR CFM

0
0
0
520
500
460
0
X
RETURN AIR CFM

0
325
50
0
0
0
0
X
EXHAUST AIR CFM

0
0
0
0
40
255
0
X
FRESH AIR CFM

3
3
3
3
3
X
ZONE

Media
Electric
Office 102
Office 101
Corridor 3
X
ROOM NAME

17
0
1
1
0
X
OCCUPANTS

> 3 HRS
N/A
> 3 HRS
> 3 HRS
N/A
X
DURATION

900
67
336
412
85
X
SUPPLY AIR CFM

860
67 T/A
620
0
0
X
RETURN AIR CFM

0
0
0
0
0
X
EXHAUST AIR CFM

255
0
20
20
0
X
FRESH AIR CFM

4
4
4
4
4
4
4
4
4
X
ZONE

Computers
Break
Office 120
Office 121
Office 123
Office 125
Pricipal
Office 122
Corridor 4
X
ROOM NAME

17
0
1
1
1
1
1
1
0
X
OCCUPANTS

> 3 HRS
N/A
> 3 HRS
> 3 HRS
> 3 HRS
> 3 HRS
> 3 HRS
> 3 HRS
N/A
X
DURATION

955
86
93
157
157
174
103
70
5
X
SUPPLY AIR CFM

889
86 T/A
93 T/A
157
157
174
103
70 T/A
0
X
RETURN AIR CFM

0
0
0
0
0
0
0
0
0
X
EXHAUST AIR CFM

255
0
20
20
20
20
20
20
0
X
FRESH AIR CFM

SERVER

N/A

600

405

200

95

> 3 HRS

7800

6325

1475

1475

CLASSIFICATION

OCCUPANTS

DURATION

MAX. REQ. AIR

ADJUSTED AIR

TOTAL AIR

CFM / PERSON OR SQ FOOT

PEAK
PEAK

Classrooms
Office

85
10

1.00
1.00

15
20

15
20

1275
200

15
20

BUILDING TOTALS

95

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE

22x22,9", 266 CFM

THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

22x22, 14", -500

22x22, 14", -520

TYPICAL AIR
DEVICE

Walk In Closet

VERTICAL AIR
HANDLER ON
STAND
FMC SECTIONS
303 --- 312

8x4 = DEVICE NECK SIZE


4" = BRANCH DUCT SIZE
32 = AIRFLOW CFM
ADJUSTMENTS

Bedroom

TYPICAL ROOM

PKG = PACKAGE UNIT


R/A = RETURN AIR
RTU = ROOFTOP UNIT
S/A = SUPPLY AIR

SF = SUPPLY FAN
T/A = TRANSFER AIR
VTE = VENT TO EXTERIOR
ZD = ZONE DAMPER

1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS.
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER.

1475

22x22,9", 266 CFM

EF-3

TYPICAL
BRANCH
DUCT

CONDENSING UNIT
ON SLAB
FMC SECTIONS
303 -- 312

ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.

BUILDING VENTILATION CALCULATION


TIME

22x22,9",263 CFM

PACKAGE UNIT
ROOF MOUNTED
FMC SECTIONS
303 -- 312

THIS HVAC DDRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.

THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

Lobby

PACKAGE UNIT
SLAB MOUNTED
FMC SECTIONS
303 -- 312

HVAC NOTES

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3

Office

DUCTLESS
AIR
HANDLER
FMC
SECTIONS
303 -- 312

1" UNDERCUT
DOOR
30 CFM T/A

EF = EXHAUST FAN
FPM = FEET PER MINUTE
MUA = MAKE UP AIR
O/A = OUTSIDE AIR

CFM = CUBIC FEET / MINUTE


CU = CONDENSING UNIT
DH = DE-HUMIDIFIER
E/A = EXHAUST AIR

BUILDING AIR BALANCE SCHEDULE

BUILDING TOTALS

CONTROL /
REFRIGERANT
PIPING FMC 1101

WALL GRILLE
FILTER RETURN
AIR FMC 603.15

22x22,9",263 CFM

DUCT MOUNTED
SMOKE DETECTOR
FMC SECTION 606

CEILING REGISTER
3 WAY THROW
FMC 603.15

HORIZONTAL AIR
HANDLER
MOUNT
FROM
STRUCTURE
FMC SECTIONS
303 --- 312

VTE

Restroom G
Locker G

Restroom B

16x16,9",-300 CFM
10x10

Mech

Locker B
12x12,7",-125 CFM

16x16,9",-300 CFM

Reading

Media

Electric

22x22,9",300 CFM

Office 101

Office 102

22x22,5",67 CFM

22x22,8",168 CFM

10x14

10x14

12x16
22x22,8",161 CFM

10x12

16x16, 9",-300 CFM

8x4,4",36 CFM

8x4,4",51 CFM

HVAC SCHEDULES + DETAILS

16x16,9",-200 CFM

22x22,5",88 CFM
22x22,5",81 CFM

22x22,9",300 CFM

22x22,8",161 CFM

EF-1

6x12

Restroom

24x12

14x12

14x12

TRANE EQUIPMENT

22x22,9",206 CFM
22x22,9",300 CFM

AIR HANDLER MARK:


UNIT MODEL NUMBER:

22x22,8",168 CFM

22x22,16",-860 CFM

Corridor
24x12 2

14x16

24x18

22x22, 14", -460

AHU-2

10x12

MECH ROOM
ABOVE CEILING

Corridor 1
22x22,6",97 CFM

22x22,7",140 CFM

24x18

Office 122

Pricipal Office

24x12

22x22,7",-103 CFM

22x22,9",238 CFM

22x22,6",93 CFM
24x12

22x22, 6",70 CFM

22x22,9",199 CFM

22x22,8",171 CFM
14x12

22x22,8",171 CFM

14x12
TRANSFER AIR
FROM BREAK
- CORRIDOR
HIGH WALL

22x22,9",171 CFM

8x12

14x12

24x12

Class

22x22,9",238 CFM

Science

22x22,9",238 CFM

AHU-5

CU-2

UNIT MODEL NUMBER:


UNIT VOLTAGE:

2TTR4060A
208/230/ 1 / 60

UNIT MCA / BREAKER:


UNIT DIMEN H/W/D:

34 / 50
46.4X35.1X38.7

ON SLAB

ON SLAB

ON SLAB

22x22,8", -157 CFM

SENS. COOLING BTUH:

44,500

LAT. COOLING BTUH:


TOTAL HEATING BTUH:

16,500
34,120

CU-3

2.5

GRADE

CU-5

EQUIPMENT SLAB

CCW18000

CONDENSING UNIT DETAIL

200/230/ 1 / 60
12.5 / 20
35X12X28

UNIT WEIGHT:
TOTAL COOLING BTUH:

156
18,400

SENS. COOLING BTUH:


LAT. COOLING BTUH:

11,200
7,200

TOTAL HEATING BTUH:

17,000

SEER:

0.73
14

FASTENER
FMC 301.13

29

UNIT MCA / BREAKER:


UNIT DIMEN LWH:

* FRESH
AIR
DUCT
FMC 401

REFRIGERANT PIPING +
CONTROL WIRING FMC
1101

1/2 THREADED ROD


SUSPEND FROM
TOP CHORD
AIR HANDLER
FMC 303

13

THERMOSTAT MODEL:

RETURN DUCT
FMC 601

T8411R1002

SUPPLY AIR DUCT FMC 601


AUX. DRAIN PAN + FLOAT
SWITCH FMC 301.2.3

Office 123

Office 125

EF-3
GREENHECK

690

QT-200

CSP-264

EXHAUST

EXHAUST

INLINE EXHAUST

50

200

1225

0.25

.25

.5

120/1/60

120 / 1 / 60

FAN VOLTAGE:

22x22,8", 174 CFM

EF-2
NUTONE

FAN CFM:
TOTAL PRESSURE:

22x22,7", 157 CFM

EF-1
NUTONE

FAN TYPE:

MODEL NUMBER:

22x22,8", -157 CFM


22x22,7", 157 CFM

ON SLAB

279
61,000

FLOOR

42X12X8

CONDENSER MARK:
UNIT VOLTAGE:

WALL

200/230/ 1 / 60

UNIT MODEL NUMBER:

CONDENSING UNIT
FMC 303

HEATSTRIP KW:

50 / 60

120/1/60

FAN AMPERAGE:

0.5

1.0

7.8

FAN DIMEN LWH:

9X11X8

14X10X9

24X14X14

3.25X10 TO 7

19X8

12X11

15X11

23X13

10
1,2

14

59

1,3

1,2

DUCT OUTLET SIZE:


DUCT INLET SIZE:

1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS

CU-5

.35

UNIT WEIGHT:

CU-1,2,3,4

FAN WEIGHT:
NOTES:

CU-1

600 / .40

* CEILING

Office 121
NOTE: AHU-5, CU-5 ARE
OPTIONAL ONLY IF
THIS ROOM IS USED
FOR COMPUTER SERVERS
FOR OFFICE - USE 7" S/A
DUCT AND 22x22 GRILLE

SUPPLY FAN CFM / SP :

REFRIGERANT PIPING + CONTROL WIRING


FMC 1101 - MAY ALSO ROUTE BELOW SLAB

CONDENSATE DRAIN FMC 307

EXHAUST FAN SCHEDULE

WALL MOUNT

Computers

DUCTLESS

UNIT DIMEN LWH:

CONDENSER MARK:
NOMINAL A/C TONS :

MANUFACTURER:

22x22,8",171 CFM

RETURN PLENUM SIZE :

UNIT VOLTAGE:

208 / 240
7.2 / 9.6

FAN MARK:

22x22,9",199 CFM

DUCTLESS

OUTDOOR AIR CFM:

HEATER BREAKER:

Corridor 4
DUCTLESS
AIR HANDLER
600 CFM S/A
600 CFM R/A
NO OCCUPANCY

1.5

SUPPLY PLENUM SIZE :

SUPPLY FAN H/P :

368
1 / 60

PIPE COVER - MAY MOUNT INTERIOR

ACWH1800

NOTES: ALTERNATE BRAND EQUIPMENT WITH


EQUAL PERFORMANCE ARE ACCEPTABLE.
SUBMIT PERFORMANCE DATA FOR APPROVAL.

Server

VTE

1800 / .40
1

THERMOSTAT MODEL:

22x22,9", -174 CFM

EF-2

SUPPLY FAN CFM / SP :


SUPPLY FAN H/P :

SENSIBLE HEAT %
SEER:

22x22,6",103 CFM

12x16
10x12

NOMINAL A/C TONS :

24X12
24X18

UNIT WEIGHT:
TOTAL COOLING BTUH:

22x22,9",238 CFM

TYPICAL (x4) 9" FRESH AIR DUCT


VTE,FILTER,SET TO 368 CFM

16x12

24x18

Office 120

22x22,5",86 CFM
22x22,18",-686

22x22,5",85 CFM

MECH ROOM
ABOVE CEILING

Break

UNIT MODEL NUMBER:

OUTDOOR AIR CFM:


UNIT PHASE / HERTZ:

AHU-4
22x22,16",-889 CFM

TWE065E

SUPPLY PLENUM SIZE :


RETURN PLENUM SIZE :

AHU-5

AIR HANDLER MARK:

63X26X21
218

UNIT VOLTAGE:
HEATER KW:

MECH ROOM
ABOVE CEILING

Corridor 3

MECH ROOM
ABOVE CEILING

22x22, 18", -794

22x22,14",-620 CFM

AHU-3

AHU-1

24x12

24x12

24x18

8x4,4",29 CFM

ENVIRO AIR EQUIPMENT

AHU-1,2,3,4

UNIT DIMEN H/W/D:


UNIT WEIGHT:

24x12

TYPICAL (x6) 16x16


TRANSFER AIR
GRILLE - WALL /
DOOR MOUNT
300 MAX CFM

22x22,9",199 CFM

22x22,9",206 CFM

VTE

8x4,4",51 CFM

22x22,9",199 CFM

10x12

22x22,8",161 CFM

3 = WALL SWITH CONTROL

* ACCESS PANEL FMC 306.3

* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN


DRAWING FOR EXACT CONFIGURATION.

ENCLOSED MECHANICAL
ROOM IN ATTIC, R-19
INSULATION + SEALED
GWB, PROVIDE ACCESS

HORIZONTAL AIR HANDLER DETAIL

CU-4
ON SLAB

North

PROJECT NAME: American Youth Academy 6949 w


PROJECT ADDRESS: 5903 E 130th Avenue
PROJECT STATE, ZIP: Temple Terrace Florida
CONDITIONED SQ. FT.: 6949
CLASSIFICATION : Commercial Add + Remodel

Designed By:
Neil Fimbel
HVAC Designs
813-885-2258
FL BERS #884

DRAWING DATE
8/26/2008
PERMIT SET
SCALE

1/8"=1'-0"

HVAC
DRAWING
1 OF 1

* FRESH
AIR DUCT
FMC 401

HVAC NOTES

SUPPLY
AIR DUCT
FMC 601

* CEILING

THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
HVAC SYMBOL, HVAC CONTRACTOR MUST REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.

AIR HANDLER
FMC 303
22x22,10",300 CFM

Unit J1

22x22,10",300 CFM

AIR HANDLER
STAND

22x22,10",284 CFM
22x22,10",284 CFM

22x22,10",284 CFM
B
B

RELIEF AIR VENT


16x16 480 CFM 10"
+ BACKDRAFT DAMPER

Unit J2

* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN


DRAWING FOR EXACT CONFIGURATION.

VERTICAL AIR
HANDLER DETAIL

(2) 24x18 R/A - 960 CFM


2 STG

22x22,10",300 CFM

(2) 9" O/A


DUCT @
240 CFM

Toilet 10
EF-1

CONDENSATE
DRAIN
FMC 307

22x22,10",300 CFM

ON STAND

8x4,5",63 CFM

1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS.
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING
IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES)
SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.

FLOOR

16"

AHU-10A

16"

ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT INTERIOR DOOR = ONLY 30 CFM OF RELIEF AIR.

REFRIGERANT
PIPING
+ CONTROL
WIRING
FMC 1101

22x22,10",284 CFM

VTE

AHU-10B

10' MINIMUM
FROM PARKING

12" O/A DUCT

RAIL
PIPE COVER

ON STAND

REFRIGERANT PIPING + CONTROL WIRING


FMC 1101

18x18 +480 CFM O/A


30x20 R/A -1200 CFM

Toilet 9

10" O/A DUCT

AHU-9

8x4,4",47 CFM

18x18 + 400 CFM O/A

CONDENSING UNIT
FMC 303

ON STAND

22x22,10",311 CFM

22x22,10",311 CFM

FASTENER
FMC 301.13

RELIEF AIR VENT


16x16 400 CFM 10"
+ BACKDRAFT DAMPER

16"
B

EQUIPMENT
PLATFORM

RAISED
PLATFORM

WALL

CU-10A

HVAC SYMBOLS

FLOOR

CU-10B
22x22,10",311 CFM

RECTANGULAR
DUCTWORK
FMC SECTION 603

CEILING REGISTER
2 WAY THROW
FMC 603.15

FLEXIBLE
DUCTWORK
FMC SECTION 603

CEILING REGISTER
3 WAY THROW
FMC 603.15

AIR DISTRIBUTION
BOXES FMC
SECTION 603

CEILING REGISTER
4 WAY THROW
FMC 603.15

RETURN AIR
PLENUM TRUNK
FMC SECTION 602

EQUIPMENT
ACCESS PANEL
FMC SECTION 306

CEILING REGISTER
CORNER THROW
FMC 603.15

SUPPLY AIR
PLENUM TRUNK
FMC SECTION 602

EXHAUST FAN
EF-1 or as NOTED
FMC SECTION 403

WALL REGISTER
2 WAY THROW
FMC 603.15

AIR VOLUME
CONTROL DAMPER
FMC 603.15

ZD

ZONE CONTROL
AIR DAMPER
FMC 303 -- 312

FLOOR REGISTER
2 WAY THROW
FMC 603.15

DUCT MOUNTED
FIRE DAMPER
FMC SECTION 607

BP

BYPASS AIR
DAMPER
FMC 303 -- 312

FLOOR GRILLE
FILTER RETURN
AIR FMC 603.15

CEILING GRILLE
FILTER RETURN
AIR FMC 603.15

THERMOSTAT @ 60"
ABOVE FLOOR
FEC 13-613

WALL MOUNTED
HUMIDISTAT @ 60"
ABOVE FLOOR

CEILING GRILLE
DUCTED T/A
FMC 603.15

CONDENSATE
DRAIN TO GRASS
FMC SECTION 307

WALL GRILLE
DIRECT T/ A
FMC 603.15

CONDENSATE
TO DRYWELL
FMC SECTION 307

CFM = CUBIC FEET / MINUTE


CU = CONDENSING UNIT
DH = DE-HUMIDIFIER
E/A = EXHAUST AIR

DUCTLESS AIR
HANDLER
FMC SECTIONS
303 -- 312

PACKAGE UNIT
SLAB MOUNTED
FMC SECTIONS
303 -- 312

PACKAGE UNIT
ROOF MOUNTED
FMC SECTIONS
303 -- 312

1" UNDERCUT DOOR


30 CFM T/A

RANGE VENT
ROOF / WALL CAP
FMC 505 - 506
CONTROL /
REFRIGERANT
PIPING FMC 1101

HORIZONTAL AIR
HANDLER MOUNT
FROM STRUCTURE
FMC SECTIONS
303 --- 312

DUCT MOUNTED
SMOKE DETECTOR
FMC SECTION 606

DRYER VENT
ROOF / WALL
CAP FMC 504

WALL GRILLE
FILTER RETURN
AIR FMC 603.15

AFF = ABOVE FINISH FLOOR


AHU = AIR HANDLING UNIT
BP = BYPASS DAMPER
BD = BAROMETRIC DAMPER

TYPICAL
BRANCH
DUCT

CONDENSING UNIT
ON SLAB
FMC SECTIONS
303 -- 312

8x4
4"
32

TYPICAL AIR
DEVICE

Walk In Closet

VERTICAL AIR
HANDLER ON STAND
FMC SECTIONS
303 --- 312

= BRANCH DUCT SIZE


= AIRFLOW CFM
ADJUSTMENTS

Bedroom

TYPICAL ROOM
SF = SUPPLY FAN
T/A = TRANSFER AIR
VTE = VENT TO EXTERIOR
ZD = ZONE DAMPER

PKG = PACKAGE UNIT


R/A = RETURN AIR
RTU = ROOFTOP UNIT
S/A = SUPPLY AIR

EF = EXHAUST FAN
FPM = FEET PER MINUTE
MUA = MAKE UP AIR
O/A = OUTSIDE AIR

= DEVICE NECK SIZE

22x22,10",311 CFM

22x22,10",311 CFM

Unit I

CU-9

CEILING REGISTER
1 WAY THROW
FMC 603.15

CONDENSING UNIT DETAIL

CU-6
UNCONDITIONED
LOBBY

Unit H

CU-7

10' MINIMUM
FROM PARKING

18x18 + 420 CFM O/A

CU-8
10" O/A DUCT

18x18 +360 CFM O/A


22x22,10",326 CFM

18x18 + 360 CFM O/A


10" O/A DUCT

22x22,10",326 CFM

Unit G

Unit D

Unit E

Unit F

Unit B

Unit C

18x18 +480 CFM O/A

10" O/A DUCT

22x22,10",300 CFM

22x22,10",312 CFM

22x22,10",300 CFM

Unit A1

22x22,10",312 CFM
12" O/A DUCT

22x22,10",310 CFM
22x22,10",310 CFM
C

22x22,10",312 CFM

18"

22x22,10",326 CFM

HVAC DUCT SYSTEMS ARE TYPICAL FOR UNITS B,C,D,E,F

22x22,10",326 CFM

22x22,10",300 CFM

30x20 R/A -1600 CFM

16"

22x22,10",300 CFM

22x22,10",310 CFM

22x22,10",310 CFM

22x22,10",312 CFM

Unit A2

16"
16"

30x20 R/A -1240 CFM

30x20 R/A - 1240 CFM

22x22,10",287 CFM

(2) 24x18 R/A -960 CFM

AHU-2
ON STAND

2 STG

AHU-1B

22x22,10",287 CFM

ON STAND

16"
B

22x22,10",310 CFM

AHU-6
22x22,10",326 CFM

22x22,10",326 CFM

AHU-8

AHU-7

ON STAND

ON STAND

ON STAND

AHU-4

AHU-5

AHU-3

ON STAND

ON STAND

(2) 9" O/A @ 240 CFM

ON STAND

AHU-1A

22x22,10",312 CFM

ON STAND

Toilet 3
8x4,4",42 CFM

EF-1

EF-1

VTE

VTE

Toilet 8

8x4,4",48 CFM

Toilet 6

Toilet 7

RELIEF AIR VENT


16x16 420 CFM 10"
+ BACKDRAFT DAMPER

Toilet 4

VTE

8x4,4",42 CFM

Toilet 5

Toilet 1

Toilet 2

CU-4

CU-5

CU-3

CU-2

22x22,10",287 CFM

EF-1

EF-1
VTE

RELIEF AIR VENT


16x16 360 CFM 10"
+ BACKDRAFT DAMPER

22x22,10",287 CFM

8x4,4",53 CFM

CU-1A CU-1B

RELIEF AIR VENT


16x16 360 CFM 10"
+ BACKDRAFT DAMPER

RAISED PLATFORM

RELIEF AIR VENT


16x16 480 CFM 10"
+ BACKDRAFT DAMPER

BUILDING AIR BALANCE SCHEDULE


ZONE

ROOM NAME

OCCUPANTS

DURATION

SUPPLY AIR CFM

RETURN AIR CFM

EXHAUST / RELIEF AIR CFM

FRESH AIR CFM

1
X
ZONE

UNIT A1
X
ROOM NAME

6
X
OCCUPANTS

> 3 HRS
X
DURATION

1200
X
SUPPLY AIR CFM

960
X
RETURN AIR CFM

240
X
EXHAUST AIR CFM

240
X
FRESH AIR CFM

2
2
X
ZONE

UNIT B
TOILET
X
ROOM NAME

9
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

1558
42
X
SUPPLY AIR CFM

1240
0
X
RETURN AIR CFM

360
80 SWITCHED
X
EXHAUST AIR CFM

360
0
X
FRESH AIR CFM

3
3
X
ZONE

UNIT C
TOILET
X
ROOM NAME

9
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

1558
42
X
SUPPLY AIR CFM

1240
0
X
RETURN AIR CFM

360
80 SWITCHED
X
EXHAUST AIR CFM

360
0
X
FRESH AIR CFM

4
4
X
ZONE

UNIT D
TOILET
X
ROOM NAME

9
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

1558
42
X
SUPPLY AIR CFM

1240
0
X
RETURN AIR CFM

360
80 SWITCHED
X
EXHAUST AIR CFM

360
0
X
FRESH AIR CFM

UNIT DIMEN H/W/D:

5
5
X
ZONE

UNIT E
TOILET
X
ROOM NAME

9
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

1558
42
X
SUPPLY AIR CFM

1240
0
X
RETURN AIR CFM

360
80 SWITCHED
X
EXHAUST AIR CFM

360
0
X
FRESH AIR CFM

6
6
X
ZONE

UNIT F
TOILET
X
ROOM NAME

9
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

1558
42
X
SUPPLY AIR CFM

1240
0
X
RETURN AIR CFM

360
80 SWITCHED
X
EXHAUST AIR CFM

360
0
X
FRESH AIR CFM

FAN MARK:

7
7
X
ZONE

UNIT G
TOILET
X
ROOM NAME

9
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

1552
48
X
SUPPLY AIR CFM

1240
0
X
RETURN AIR CFM

360
80 SWITCHED
X
EXHAUST AIR CFM

360
0
X
FRESH AIR CFM

FAN TYPE:

EXHAUST

FAN CFM:

80

HEATER BREAKER:

TOTAL PRESSURE:

.25

8
8
X
ZONE

UNIT H
TOILET
X
ROOM NAME

12
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

1958
42
X
SUPPLY AIR CFM

1600
0
X
RETURN AIR CFM

400
80 SWITCHED
X
EXHAUST AIR CFM

400
0
X
FRESH AIR CFM

FAN VOLTAGE:

120/1/60

9
9
X
ZONE

UNIT I
TOILET
X
ROOM NAME

10
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

1553
47
X
SUPPLY AIR CFM

1200
0
X
RETURN AIR CFM

400
80 SWITCHED
X
EXHAUST AIR CFM

400
0
X
FRESH AIR CFM

DUCT OUTLET SIZE:

10
10
X
ZONE

UNIT J1
TOILET
X
ROOM NAME

5
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

1137
63
X
SUPPLY AIR CFM

960
0
X
RETURN AIR CFM

240
80 SWITCHED
X
EXHAUST AIR CFM

240
0
X
FRESH AIR CFM

LAT. COOLING BTUH:

8,800

13,200

18,000

13,200

11
11
X
ZONE

UNIT A2
TOILET
X
ROOM NAME

6
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

1147
53
X
SUPPLY AIR CFM

960
0
X
RETURN AIR CFM

240
80 SWITCHED
X
EXHAUST AIR CFM

240
0
X
FRESH AIR CFM

TOTAL HEATING BTUH:

25,590

34,120

34,120

34,120

0.74

0.72

0.69

0.72

13

13

13.5

13

12

UNIT J2

> 3 HRS

1200

960

240

240

THERMOSTAT MODEL:

T8411R1002

T8411R1002

T8411R1002

T8411R1002

97

> 3 HRS

18000

14080

3920

3920

BUILDING TOTALS

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

BUILDING VENTILATION CALCULATION

AMERICAN STANDARD SPLIT SYSTEM EQUIPMENT SCHEDULE


AHU-1A,1B,10A,10B

AHU-2,3,4,5,6,7

AHU-8

AHU-9

TIME

CLASSIFICATION

OCCS / SF

DURATION

MAX. REQ. AIR

ADJUSTED AIR

TOTAL AIR

CFM / SF

2TEC3F36A

2TEC3F48A

2TEC3F60A

2TEC3F48A

PEAK

Mechant (usable sq ft)

97 / 13066

1.00

0.3

0.3

3919.8

0.3

46.5X24X23.5

59.5X26X23.5

59.5X26X23.5

59.5X26X23.5

125

151

155

151

SUPPLY PLENUM SIZE :

12.02X19.22

12.02X21.22

12.02X21.22

12.02X21.22

RETURN PLENUM SIZE :

18.07X19.5

18.07X21.5

18.07X21.5

18.07X21.5

SUPPLY FAN CFM / SP :

1200 / .40

1600 / .40

2000 / .40

1600 / .40

AIR HANDLER MARK:


UNIT MODEL NUMBER:
UNIT WEIGHT:

EXHAUST FAN SCHEDULE


EF-1

MANUFACTURER:

NUTONE

MODEL NUMBER:

QT-80

FAN AMPERAGE:
FAN DIMEN LWH:
DUCT INLET SIZE:
FAN WEIGHT:
NOTES:
1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS

.7
9X9X6
4
10X10

SUPPLY FAN H/P :

1/3

1/2

1/2

OUTDOOR AIR CFM:

240

360

420

400

UNIT PHASE / HERTZ:

1 / 60

1 / 60

1 / 60

1 / 60

UNIT VOLTAGE:

208 / 240

208 / 240

208 / 240

208 / 240

HEATER KW:

5.76 / 7.68

7.2 / 9.6

7.2 / 9.6

7.2 / 9.6

40 / 45

50 / 60

50 / 60

50 / 60

CONDENSER MARK:

CU-1A,1B,10A,10B

CU-2,3,4,5,6,7

CU-8

CU-9

NOMINAL A/C TONS :

UNIT MODEL NUMBER:


UNIT VOLTAGE:
UNIT MCA / BREAKER:
UNIT DIMEN H/W/D:

2TTR3036A

2TTR3048A

2TTR3060A

2TTR3048A

208/230/ 1 / 60

208/230/ 1 / 60

208/230/ 1 / 60

208/230/ 1 / 60

18 / 30

25 / 40

32 / 50

25 / 40

38X30.1X33

46.4X35.1X38.7

46.4X35.1X38.7

46.4X35.1X38.7

12

UNIT WEIGHT:

194

273

269

273

1,2

TOTAL COOLING BTUH:

34,200

47,000

58,000

47,000

SENS. COOLING BTUH:

25,400

33,800

40,000

33,800

SENSIBLE HEAT %
SEER:

NOTES: ALTERNATE BRAND EQUIPMENT WITH EQUAL PERFORMANCE ARE ACCEPTABLE.


SUBMIT PERFORMANCE DATA FOR APPROVAL.
CYCLE EQUIPMENT OFF DURING UNOCCUPIED HOURS.

BUILDING TOTALS

3920 PROVIDED

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

North

PROJECT NAME: Rose Lake Plaza Phase 2


PROJECT ADDRESS: 14400 N Florida Ave
PROJECT STATE, ZIP: Tampa Florida
CONDITIONED SQ. FT.: 13352
CLASSIFICATION : New Commercial

Designed By:
Neil Fimbel
HVAC Designs
813-885-2258
FL BERS R#884
FL BERS C#8508

DRAWING DATE
9/19/2008
PERMIT SET
SCALE 1/8"=1'-0"

HVAC
DRAWING
1 OF 1

HVAC SYMBOLS
CEILING REGISTER
1 WAY THROW
FMC 603.15

RECTANGULAR
DUCTWORK
FMC SECTION 603

THERMOSTAT @ 60"
ABOVE FLOOR
FEC 13-613

CEILING REGISTER
2 WAY THROW
FMC 603.15

FLEXIBLE
DUCTWORK
FMC SECTION 603

WALL MOUNTED
HUMIDISTAT @ 60"
ABOVE FLOOR

CEILING REGISTER
3 WAY THROW
FMC 603.15

AIR DISTRIBUTION
BOXES FMC
SECTION 603

CEILING REGISTER
4 WAY THROW
FMC 603.15

RETURN AIR
PLENUM TRUNK
FMC SECTION 602

EQUIPMENT
ACCESS PANEL
FMC SECTION 306

CEILING REGISTER
CORNER THROW
FMC 603.15

SUPPLY AIR
PLENUM TRUNK
FMC SECTION 602

EXHAUST FAN
EF-1 or as NOTED
FMC SECTION 403

WALL REGISTER
2 WAY THROW
FMC 603.15

AIR VOLUME
CONTROL DAMPER
FMC 603.15

ZD

ZONE CONTROL
AIR DAMPER
FMC 303 -- 312

FLOOR REGISTER
2 WAY THROW
FMC 603.15

DUCT MOUNTED
FIRE DAMPER
FMC SECTION 607

BP

BYPASS AIR
DAMPER
FMC 303 -- 312

FLOOR GRILLE
FILTER RETURN
AIR FMC 603.15
CEILING GRILLE
FILTER RETURN
AIR FMC 603.15

8x4,4",13 CFM
M Toilet

M Bed

M Bath
10x6,5",77 CFM
10x6,5",77 CFM

8x4,4",43 CFM

Dining / Living
12x8,116 CFM
A

18x18, 12",-606 CFM

WYE

12x6,6",106 CFM

10x6,6",89 CFM

ABOVE CEILING
IN SEALED MECH
ROOM R-19 ISUL

14"

Foyer

Bed 4

AHU-1

10"

14"

14"

12x8,8",116 CFM

Powder
18x18 R/A
@ CHASE
-500 CFM
12"

12" BYPASS

BP

ZD ZD

4" DRYER VTE

8x4,4",31 CFM

12x12,7",-89 CFM

ACCESS TO
ATTIC

12x6,6",113 CFM

DUCTS DOWN

Lav

14"

CU-1

ON SLAB

8x4,4",24 CFM

Laundry
8x4,4",35 CFM

8x4,4",5 CFM

Bath 2
12x12,7",-99 CFM

CONDENSATE
DRAIN TO GRASS
FMC SECTION 307

WALL GRILLE
DIRECT T/ A
FMC 603.15

CONDENSATE
TO DRYWELL
FMC SECTION 307

TYPICAL
BRANCH
DUCT

CONDENSING UNIT
ON SLAB
FMC SECTIONS
303 -- 312

TYPICAL AIR
DEVICE

8x4
4"
32

Walk In Closet

VERTICAL AIR
HANDLER ON STAND
FMC SECTIONS
303 --- 312

EF = EXHAUST FAN
FPM = FEET PER MINUTE
MUA = MAKE UP AIR
O/A = OUTSIDE AIR

= DEVICE NECK SIZE


= BRANCH DUCT SIZE
= AIRFLOW CFM
ADJUSTMENTS

Bedroom

TYPICAL ROOM

PKG = PACKAGE UNIT


R/A = RETURN AIR
RTU = ROOFTOP UNIT
S/A = SUPPLY AIR

SF = SUPPLY FAN
T/A = TRANSFER AIR
VTE = VENT TO EXTERIOR
ZD = ZONE DAMPER

1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS.
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING
IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES)
SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.

HVAC SCHEDULES + DETAILS


TRANE HEAT PUMP

FIRST
FLOOR

AIR HANDLER MARK:


UNIT MODEL NUMBER:
UNIT DIMEN H/W/D:
UNIT WEIGHT:
SUPPLY PLENUM SIZE :
RETURN PLENUM SIZE :
SUPPLY FAN CFM / SP :
SUPPLY FAN H/P :
OUTDOOR AIR CFM:
UNIT PHASE / HERTZ:
UNIT VOLTAGE:
HEATER KW:
HEATER BREAKER:
CONDENSER MARK:
NOMINAL A/C TONS :
UNIT MODEL NUMBER:
UNIT VOLTAGE:
UNIT MCA / BREAKER:
UNIT DIMEN H/W/D:
UNIT WEIGHT:
TOTAL COOLING BTUH:
SENS. COOLING BTUH:
LAT. COOLING BTUH:
TOTAL HEATING BTUH:
SENSIBLE HEAT %
SEER / HSPF :

10x6,6",91 CFM

SECOND
FLOOR

CEILING GRILLE
DUCTED T/A
FMC 603.15

12x12,7",-91 CFM

10x6,6",99 CFM

PACKAGE UNIT
ROOF MOUNTED
FMC SECTIONS
303 -- 312

ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.

12x8,116 CFM

Stair / Otb

PACKAGE UNIT
SLAB MOUNTED
FMC SECTIONS
303 -- 312

THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.

M Wic

10"

CONTROL /
REFRIGERANT
PIPING FMC 1101

CFM = CUBIC FEET / MINUTE


CU = CONDENSING UNIT
DH = DE-HUMIDIFIER
E/A = EXHAUST AIR

DUCTLESS AIR
HANDLER
FMC SECTIONS
303 -- 312

HVAC NOTES

12x8,334 CFM
8x4,4",5 CFM

RANGE VENT
ROOF / WALL CAP
FMC 505 - 506

7" RANGE VTE

12x12,9",-215 CFM
12x6,6",106 CFM

1" UNDERCUT DOOR


30 CFM T/A

WALL GRILLE
FILTER RETURN
AIR FMC 603.15

AFF = ABOVE FINISH FLOOR


AHU = AIR HANDLING UNIT
BP = BYPASS DAMPER
BD = BAROMETRIC DAMPER

Family / Nook / Kitchen

DUCT MOUNTED
SMOKE DETECTOR
FMC SECTION 606

DRYER VENT
ROOF / WALL
CAP FMC 504

HORIZONTAL AIR
HANDLER MOUNT
FROM STRUCTURE
FMC SECTIONS
303 --- 312

Bed2 3
Bed

AHU-1
2TEC3F48A
59.5X26X23.5
151
12.02X21.22
18.07X21.5
1600 / .40
1/2
0
1 / 60
208 / 240
7.2 / 9.6
50 / 60

CU-1
4
2TWR3048A
208/230/ 1 / 60
25 / 40
46.4X35.1X38.7
279
46,000
33,200
12,800
43,500
0.72
13 / 8.4

THERMOSTAT MODEL:

PROGRAM

NOTES: ALTERNATE BRAND EQUIPMENT WITH


EQUAL PERFORMANCE ARE ACCEPTABLE.
ZONING SHOWN PER MANUAL J

PIPE COVER - MAY MOUNT INTERIOR

FLOOR

FASTENER
FMC 301.13

1/2 THREADED ROD


SUSPEND FROM
TOP CHORD
AIR HANDLER
FMC 303

RETURN DUCT
FMC 601

CONDENSING UNIT
FMC 303

WALL

* CEILING

SUPPLY AIR DUCT FMC 601

AUX. DRAIN PAN + FLOAT


SWITCH FMC 301.2.3
CONDENSATE DRAIN FMC 307

GRADE
EQUIPMENT SLAB

* ACCESS PANEL FMC 306.3

CONDENSING UNIT DETAIL


TRI - BOX

REDUCER - BOX
W

* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN


DRAWING FOR EXACT CONFIGURATION.

HORIZONTAL AIR HANDLER DETAIL

W2

BOX DIMENSIONS - INCHES


MARK W
W2
H
L

EF-1
NUTONE
690
EXHAUST
50
0.25
120/1/60
0.5
9X11X8
3
12X11
10
1,2

REFRIGERANT PIPING
+ CONTROL WIRING
FMC 1101

REFRIGERANT PIPING + CONTROL WIRING


FMC 1101 - MAY ALSO ROUTE BELOW SLAB

EXHAUST FAN SCHEDULE


FAN MARK:
MANUFACTURER:
MODEL NUMBER:
FAN TYPE:
FAN CFM:
TOTAL PRESSURE:
FAN VOLTAGE:
FAN AMPERAGE:
FAN DIMEN LWH:
DUCT OUTLET SIZE:
DUCT INLET SIZE:
FAN WEIGHT:
NOTES:

* FRESH
AIR
DUCT
FMC 401

13

13

18

N/A

17

17

18

N/A

C
D

21

21

18

N/A

13

13

18

17

17

18

21

21

18

*
*
*

= CAP SIZE EQUALS OUTLET DUCT + 1"

1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS

North
PROJECT NAME: HDS Model Residence 1964 s
PROJECT ADDRESS:
PROJECT STATE, ZIP:
CONDITIONED SQ. FT.: 1991
CLASSIFICATION : New Residence

Designed By:
Neil Fimbel
HVAC Designs
813-885-2258
FL BERS R#884

DRAWING DATE
9/12/2008
Permit Set
SCALE 1/4"=1'-0"

HVAC
DRAWING
1 OF 1

HVAC SYMBOLS

Cooler

CEILING REGISTER
1 WAY THROW
FMC 603.15

RECTANGULAR
DUCTWORK
FMC SECTION 603

THERMOSTAT @ 60"
ABOVE FLOOR
FEC 13-613

CEILING REGISTER
2 WAY THROW
FMC 603.15

FLEXIBLE
DUCTWORK
FMC SECTION 603

WALL MOUNTED
HUMIDISTAT @ 60"
ABOVE FLOOR

CEILING REGISTER
3 WAY THROW
FMC 603.15

AIR DISTRIBUTION
BOXES FMC
SECTION 603

CEILING REGISTER
4 WAY THROW
FMC 603.15

RETURN AIR
PLENUM TRUNK
FMC SECTION 602

EQUIPMENT
ACCESS PANEL
FMC SECTION 306

CEILING REGISTER
CORNER THROW
FMC 603.15

SUPPLY AIR
PLENUM TRUNK
FMC SECTION 602

EXHAUST FAN
EF-1 or as NOTED
FMC SECTION 403

WALL REGISTER
2 WAY THROW
FMC 603.15

AIR VOLUME
CONTROL DAMPER
FMC 603.15

ZD

ZONE CONTROL
AIR DAMPER
FMC 303 -- 312

FLOOR REGISTER
2 WAY THROW
FMC 603.15

DUCT MOUNTED
FIRE DAMPER
FMC SECTION 607

BP

BYPASS AIR
DAMPER
FMC 303 -- 312

FLOOR GRILLE
FILTER RETURN
AIR FMC 603.15

CEILING GRILLE
FILTER RETURN
AIR FMC 603.15

(2) 22x22, 16", -920 CFM EA

CEILING GRILLE
DUCTED T/A
FMC 603.15

CONDENSATE
DRAIN TO GRASS
FMC SECTION 307

WALL GRILLE
DIRECT T/ A
FMC 603.15

CONDENSATE
TO DRYWELL
FMC SECTION 307

DUCTLESS AIR
HANDLER
FMC SECTIONS
303 -- 312

PACKAGE UNIT
SLAB MOUNTED
FMC SECTIONS
303 -- 312

PACKAGE UNIT
ROOF MOUNTED
FMC SECTIONS
303 -- 312

1" UNDERCUT DOOR


30 CFM T/A

TYPICAL
BRANCH
DUCT

CONDENSING UNIT
ON SLAB
FMC SECTIONS
303 -- 312

8x4
4"
32

TYPICAL AIR
DEVICE

Walk In Closet

VERTICAL AIR
HANDLER ON STAND
FMC SECTIONS
303 --- 312

EF = EXHAUST FAN
FPM = FEET PER MINUTE
MUA = MAKE UP AIR
O/A = OUTSIDE AIR

CFM = CUBIC FEET / MINUTE


CU = CONDENSING UNIT
DH = DE-HUMIDIFIER
E/A = EXHAUST AIR

Kitchen

RANGE VENT
ROOF / WALL CAP
FMC 505 - 506
CONTROL /
REFRIGERANT
PIPING FMC 1101

AFF = ABOVE FINISH FLOOR


AHU = AIR HANDLING UNIT
BP = BYPASS DAMPER
BD = BAROMETRIC DAMPER

DUCT MOUNTED
SMOKE DETECTOR
FMC SECTION 606

DRYER VENT
ROOF / WALL
CAP FMC 504

WALL GRILLE
FILTER RETURN
AIR FMC 603.15

HORIZONTAL AIR
HANDLER MOUNT
FROM STRUCTURE
FMC SECTIONS
303 --- 312

= DEVICE NECK SIZE


= BRANCH DUCT SIZE
= AIRFLOW CFM
ADJUSTMENTS

Bedroom

TYPICAL ROOM

PKG = PACKAGE UNIT


R/A = RETURN AIR
RTU = ROOFTOP UNIT
S/A = SUPPLY AIR

SF = SUPPLY FAN
T/A = TRANSFER AIR
VTE = VENT TO EXTERIOR
ZD = ZONE DAMPER

HVAC NOTES

22x22,10",320 CFM

22x22,10",320 CFM

THIS HVAC DDRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.
ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.

12x12

1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS.
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER.

12x12
24x12

RTU-1
ON ROOF

22x22,10",320 CFM
22x22,10",320 CFM

KITCHEN HOOD
BY OTHERS 380
CFM MUA BY
A/C EQUIPMENT

BUILDING AIR BALANCE SCHEDULE


ZONE

ROOM NAME

OCCUPANTS

DURATION

SUPPLY AIR CFM

RETURN AIR CFM

EXHAUST AIR CFM

FRESH AIR CFM

1
1
X
ZONE

COOLER ROOM
KITCHEN
X
ROOM NAME

0
5
X
OCCUPANTS

N/A
> 3 HRS
X
DURATION

78
1922
X
SUPPLY AIR CFM

0
1840
X
RETURN AIR CFM

0
380 CFM @ HOOD
X
EXHAUST AIR CFM

0
160
X
FRESH AIR CFM

2
2
X

RESTROOM
ORDER / CASHIER
X

0
9
X

N/A
VARIES
X

18
1582
X

0
1380
X

50 INTERMITTENT
0
X

0
220
X

BUILDING TOTALS

14

VARIES

3600

3220

380

CONDENSATE DRAIN
TO GUTTER / GRASS
TYPICAL OF 2

HVAC SCHEDULES + DETAILS

22x22,10",320 CFM
22x22,10",320 CFM

ROOFTOP EQUIPMENT SCHEDULE

RTU-2

380

EXISTING
ON ROOF

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

PACKAGE UNIT MARK:

RTU-1

RTU-2

UNIT MANUFACTURER:

TRANE

EXISTING

UNIT MODEL NUMBER:


NOMINAL A/C TONS :

4
DOWNFLOW

37X45X70

37X45X70

682

669

SUPPLY PLENUM SIZE :

17X15

17X15

RETURN PLENUM SIZE :

23X14

23X14

SUPPLY FAN CFM / SP :

2000 / .4

1600 / .4

160

220

UNIT WEIGHT:

BUILDING VENTILATION CALCULATION


PEAK
PEAK
PEAK

CLASSIFICATION
Dining / Order
HOOD MUA
Kitchen / Prep

BUILDING TOTALS

OCCUPANTS
9
0
5

14

DURATION
1.00
1.00
1.00

MAX. REQ. AIR


20
125
15

ADJUSTED AIR
20
125
15

20x12
TOTAL AIR

CFM / PERSON OR SQ FOOT

180
125
75

20
0
15

380

Restroom

SUPPLY FAN H/P :

EF-1

OUTDOOR AIR CFM:


UNIT PHASE / HERTZ:

VTE
8x4,4",18 CFM

UNIT VOLTAGE:

22x22, 16"
-1380 CFM

UNIT MCA:
UNIT MAX BREAKER:
HEATER KW:

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE

22x22, 10",316 CFM

HEATER MCA:

THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

3/60

3/60

208/230

208/230

28.8

22.6

40

35

9/12

9/12

37.5/42.4

37.5/42.4

HEATER BREAKER:

45/45

40/45

TOTAL COOLING BTUH:

62,400

49,800

SENS. COOLING BTUH:

47,300

39,400

LAT. COOLING BTUH:

15,100

10,400

TOTAL HEATING BTUH:

40,944

40,944

0.76

0.79

COOLING EFFICIENCY:

13

13

THERMOSTAT MODEL:

T8411R1002

T8411R1002

SENS. HEAT %

22x22, 10",316 CFM

THC043A3

DOWNFLOW

UNIT CONFIGURATION:
UNIT DIMEN H/W/D:

TIME

THC063A3

DUCT
CONNECTION

CURB
CONNECTION

ROOFTOP
EQUIPMENT
3/8 BOLT
@ 18" O.C.

MASTIC
SEAL

CURB

ROOF

DUCT

JOIST

EQUIPMENT
CONNECTION

1/2"
SCREWS
@ 8" O.C.

ROOFTOP
EQUIPMENT

CURB

3/8"
SCREWS
1/4" PLATE
OR ANGLE
@ 18"" O.C.

2" U CHANNEL X
1/4" THK
SPAN 3 JOISTS

ROOFTOP
EQUIPMENT
FMC 303

R/A
DUCT
FMC
601

S/A
DUCT
FMC
601

CURB

MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD
MECHANICALLY FASTEN AND SEAL DUCTS PER FMC SECTIONS 603 AND 604
MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOAD

NOTES: ALTERNATE BRAND EQUIPMENT WITH

18x12

EQUAL PERFORMANCE ARE ACCEPTABLE.


SUBMIT PERFORMANCE DATA FOR APPROVAL.

ROOFTOP PACKAGE UNIT DETAIL

EXHAUST FAN SCHEDULE


EF-1

FAN MARK:

22x22, 10",316 CFM

MANUFACTURER:

NUTONE

MODEL NUMBER:
FAN TYPE:

690
EXHAUST

FAN CFM:
TOTAL PRESSURE:
FAN VOLTAGE:

22x22, 10",316 CFM

0.5

FAN DIMEN LWH:

9X11X8

DUCT INLET SIZE:


FAN WEIGHT:
NOTES:

22x22, 10",316 CFM

North

120/1/60

FAN AMPERAGE:
DUCT OUTLET SIZE:

Order - Cashier

50
0.25

3
12X11
10
1,2

1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS

PROJECT NAME:
PROJECT ADDRESS:
PROJECT STATE, ZIP:
CONDITIONED SQ. FT.:
CLASSIFICATION :

Marcos Pizza Renov Boynton Beach 1320 e


Boynton Beach Florida, 33461
1320
Restaurant Renovation

Designed By:
Neil Fimbel
HVAC Designs
813-885-2258
FL BERS #884

DRAWING DATE
8/14/2008
Permit Set
SCALE 1/4"=1'-0"

HVAC
DRAWING
1 OF 1

BUILDING AIR BALANCE SCHEDULE

HVAC SYMBOLS

ZONE

ROOM NAME

OCCUPANTS

DURATION

SUPPLY AIR CFM

RETURN AIR CFM

EXHAUST AIR CFM

FRESH AIR CFM

1
1
1
1
1
1
1
1
1
1
1
1
X
ZONE

Office
Exam
Exam
Reception
Restroom
Restroom
Exam
Consult
Exam
Exam
Lab
Work Stations
X
ROOM NAME

1
1
1
1
0
0
1
1
1
1
0
0
X
OCCUPANTS

> 3 HRS
VARIES
VARIES
> 3 HRS
N/A
N/A
VARIES
> 3 HRS
VARIES
VARIES
VARIES
VARIES
X
DURATION

256
147
261
304
38
31
94
37
64
64
39
665
X
SUPPLY AIR CFM

256
147
261
304
0
0
94
37 T/A
64
64
39 T/A
680
X
RETURN AIR CFM

0
0
0
0
90
90
0
0
0
0
0
0
X
EXHAUST AIR CFM

20
15
15
20
0
0
10
20
15
15
0
0
X
FRESH AIR CFM

CEILING REGISTER
1 WAY THROW
FMC 603.15

RECTANGULAR
DUCTWORK
FMC SECTION 603

CEILING REGISTER
2 WAY THROW
FMC 603.15

FLEXIBLE
DUCTWORK
FMC SECTION 603

CEILING REGISTER
3 WAY THROW
FMC 603.15

AIR DISTRIBUTION
BOXES FMC
SECTION 603

CEILING REGISTER
4 WAY THROW
FMC 603.15

RETURN AIR
PLENUM TRUNK
FMC SECTION 602

EQUIPMENT
ACCESS PANEL
FMC SECTION 306

2
2
2
2
2
X
ZONE

Break
Waiting
Reception
P Restroom
E Restroom
X
ROOM NAME

2
20
2
0
0
X
OCCUPANTS

VARIES
VARIES
> 3 HRS
N/A
N/A
X
DURATION

243
1389
335
10
23
X
SUPPLY AIR CFM

243
1292
335
0
0
X
RETURN AIR CFM

0
0
0
90
90
X
EXHAUST AIR CFM

15
75
40
0
0
X
FRESH AIR CFM

CEILING REGISTER
CORNER THROW
FMC 603.15

SUPPLY AIR
PLENUM TRUNK
FMC SECTION 602

EXHAUST FAN
EF-1 or as NOTED
FMC SECTION 403

WALL REGISTER
2 WAY THROW
FMC 603.15

AIR VOLUME
CONTROL DAMPER
FMC 603.15

ZD

ZONE CONTROL
AIR DAMPER
FMC 303 -- 312

3
3
3
3
3
3
3
3
3
X
ZONE

Office
Exam
Exam
Reception
Corridor
Exam
Exam
Restroom
Restroom
X
ROOM NAME

1
1
1
1
0
1
1
0
0
X
OCCUPANTS

> 3 HRS
VARIES
VARIES
> 3 HRS
N/A
VARIES
VARIES
N/A
N/A
X
DURATION

118
124
100
108
83
120
99
24
24
X
SUPPLY AIR CFM

118
124
100
119
0
120
99
0
0
X
RETURN AIR CFM

0
0
0
0
0
0
0
90
90
X
EXHAUST AIR CFM

20
20
20
20
0
20
20
0
0
X
FRESH AIR CFM

FLOOR REGISTER
2 WAY THROW
FMC 603.15

DUCT MOUNTED
FIRE DAMPER
FMC SECTION 607

BP

BYPASS AIR
DAMPER
FMC 303 -- 312

4
4
4
4
X
ZONE

Reception
Waiting
U Restroom
Storage
X
ROOM NAME

1
4
0
0
X
OCCUPANTS

> 3 HRS
VARIES
N/A
N/A
X
DURATION

253
514
21
12
X
SUPPLY AIR CFM

253
427
0
12 T/A
X
RETURN AIR CFM

0
0
90
0
X
EXHAUST AIR CFM

20
100
0
0
X
FRESH AIR CFM

5
5
5
5
5
5
5

Exam
Office
Corridor
Exam
Exam
Exam
Waiting

1
1
0
1
1
1
20

VARIES
> 3 HRS
N/A
VARIES
VARIES
VARIES
VARIES

89
130
257
101
89
105
1229

89
130
127
101
89
105
1229

0
0
0
0
0
0
0

15
20
0
15
15
15
50

68

VARIES

7600

6970

630

630

BUILDING TOTALS

FLOOR GRILLE
FILTER RETURN
AIR FMC 603.15

CEILING GRILLE
FILTER RETURN
AIR FMC 603.15

TIME

CLASSIFICATION

OCCUPANTS

DURATION

MAX. REQ. AIR

ADJUSTED AIR

TOTAL AIR

CFM / PERSON

PEAK
PEAK
PEAK

Office
Waiting
Exam Office

8
47
13

1.00
0.50
0.50

20
15
15

20
7.5
7.5

160
352.5
97.5

20
7.5
7.5

BUILDING TOTALS

68

610 (630 provided)

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
CALCULATIONS BASED ON ASHRAE 62.1 - 2007 TABLE 6-1 - PROCEDURE PROVIDES VENTILATION FOR VARIABLE / INTERMITTENT OCCUPANTS
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

Exam

Exam

22x22,6",120 CFM

Reception
22x22,9",253

22x22,6",99 CFM
22x22,10",-253

22x22,7",-120

22x22,7",129 CFM

22x22,7",-99

22x22,6",89 CFM

Exam
22x22,10",307 CFM
22x22,14",-615

6x10

22x22,7",-89

Waiting

22x22,7",-105

22x22,5",82 CFM

Corridor

22x22,10",307 CFM

Exam
22x22,7",-101

22x22,6",100 CFM

RELOCATED TO
MEZZANINE
ABOVE

22x22,9",257

22x22,6",105 CFM

MAY CONFIGURE
EXISTING AHU
VERTICAL OR
HORIZONTAL

CU-3
ON SLAB

U Restroom

CU-4

8x4,4",21 CFM

12x8

14x12

10x12

8x4,4",24 CFM

ON SLAB

Exam

22x22,7",130 CFM

Restroom

22x22,14",-615

22x22,8",-127
22x22,12",-427

22x22,8",-130

Storage

Restroom

Office

8x4,4",24 CFM

22x22,7",-118

16x12

Office

22x22,7"-100
22x22,8",-124

22x22,6",101 CFM

Exam

20x12

CONTROL /
REFRIGERANT
PIPING FMC 1101

CEILING GRILLE
DUCTED T/A
FMC 603.15

CONDENSATE
DRAIN TO GRASS
FMC SECTION 307

WALL GRILLE
DIRECT T/ A
FMC 603.15

CONDENSATE
TO DRYWELL
FMC SECTION 307

CFM = CUBIC FEET / MINUTE


CU = CONDENSING UNIT
DH = DE-HUMIDIFIER
E/A = EXHAUST AIR

CU-5
22x22,6",108 CFM

22x22,6",118 CFM

14x14

Reception

Exam

Consult
22x22,6",93 CFM

Exam

22x22,8",-119

22x22,4",37 CFM

22x22,5",64 CFM

EXISTING ON
MEZZANINE
ABOVE

EXISTING ON
MEZZANINE
ABOVE

Exam
22x22,5",64 CFM

P Restroom

10x10

8x4,4",31 CFM
22x22, 14",-680

Work Stations

14x12

22x22,10",332 CFM

Waiting

Restroom

CU-2

Restroom

ON SLAB

AHU-1
ON STAND

8x4,4",38 CFM

22x22,10",335 CFM

22x22,14",-646

22x22,10",332 CFM

24x12

111
12.02X19.22
19.5X18.07

SUPPLY FAN CFM / SP :


SUPPLY FAN H/P :

2000 / .70
1

800 / .60
1/4

130 / 130 / 130

120 / 120

UNIT PHASE / HERTZ:

UNIT VOLTAGE:
HEATER KW:

*
*

*
*

HEATER BREAKER:

CONDENSER MARK:

CU-1,2,5

CU-3,4

UNIT MODEL NUMBER:


UNIT VOLTAGE:

EXISTING
*

EXISTING
*

UNIT MCA / BREAKER:


UNIT DIMEN H/W/D:

*
46.4X35.1X38.7

*
37.2X26.7X30

UNIT WEIGHT:
TOTAL COOLING BTUH:

269
58,000

175
22,800

SENS. COOLING BTUH:

40,000

16,600

LAT. COOLING BTUH:

18,000

6,200

TOTAL HEATING BTUH:

34,120

17,060

0.69
13

0.73
13

SENSIBLE HEAT %
SEER:

Reception

22x22,14",-646

22x22,10",-261

22x22,10", -256

TYPICAL ROOM
SF = SUPPLY FAN
T/A = TRANSFER AIR
VTE = VENT TO EXTERIOR
ZD = ZONE DAMPER

* FRESH
AIR DUCT
FMC 401

SUPPLY
AIR DUCT
FMC 601

* CEILING

REFRIGERANT PIPING
+ CONTROL WIRING
FMC 1101

* FRESH
AIR
DUCT
FMC 401

1/2 THREADED ROD


SUSPEND FROM
TOP CHORD
AIR HANDLER
FMC 303

AIR HANDLER
FMC 303

* RETURN AIR
RISER DUCT
FMC 601

AIR HANDLER
STAND

REFRIGERANT
PIPING
+ CONTROL
WIRING
FMC 1101
CONDENSATE
DRAIN
FMC 307

FLOOR
* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN
DRAWING FOR EXACT CONFIGURATION.

RETURN DUCT
FMC 601

SUPPLY AIR DUCT FMC 601

AUX. DRAIN PAN + FLOAT


SWITCH FMC 301.2.3
CONDENSATE DRAIN FMC 307

* CEILING

* ACCESS PANEL FMC 306.3


* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN
DRAWING FOR EXACT CONFIGURATION.

HORIZONTAL AIR HANDLER DETAIL

VERTICAL AIR
HANDLER DETAIL
PIPE COVER - MAY MOUNT INTERIOR
REFRIGERANT PIPING + CONTROL WIRING
FMC 1101 - MAY ALSO ROUTE BELOW SLAB

CONDENSING UNIT
FMC 303

WALL
FLOOR

FASTENER
FMC 301.13
GRADE

EQUIPMENT SLAB

CONDENSING UNIT DETAIL

22x22,10",347 CFM

EXHAUST FAN SCHEDULE


FAN MARK:
MANUFACTURER:

22x22,10",347 CFM
22x22,9",261 CFM

Exam

Reception

22x22,10",304 CFM

EF-1
NUTONE

FAN TYPE:

QT-80
EXHAUST

FAN CFM:

90

MODEL NUMBER:

Exam

Bedroom

PKG = PACKAGE UNIT


R/A = RETURN AIR
RTU = ROOFTOP UNIT
S/A = SUPPLY AIR

EF = EXHAUST FAN
FPM = FEET PER MINUTE
MUA = MAKE UP AIR
O/A = OUTSIDE AIR

= AIRFLOW CFM
ADJUSTMENTS

SIZE AND INSTALL STAND ALONE DEHUMIDIFICATION


AT THE INDOOR FOUNTAIN AREA.

22x22,8",-147

Office

VERTICAL AIR
HANDLER ON STAND
FMC SECTIONS
303 --- 312

= BRANCH DUCT SIZE

EQUIPMENT TO INSURE PROPER OPERATION.

22x22,10",347 CFM
22x22,10",347 CFM

12x14

22x22,7",146 CFM

Walk In Closet

= DEVICE NECK SIZE

DATA FOR EXACT INFORMATION. CLEAN AND CHECK

22x22,10", -304

22x22,9",258 CFM

8x4
4"
32

TYPICAL AIR
DEVICE

THERMOSTAT MODEL:
T8411R1002
T8411R1002
NOTES: * EQUIPMENT IS EXISTING,SEE NAME PLATE

20x12

20x14

(TYPICAL x7)
6" FRESH AIR
DUCT VTE

MAY CONFIGURE
EXISTING AHU
VERTICAL OR
HORIZONTAL VERIFY EXISTING
AHU TYPE

24x12

22x22,10",-335

12x12

CU-1

155
12.02X21.22
18.07X21.5

22"

THIS AREA CONTAINS A


FOUNTAIN - CALCULATE
AND PROVIDE STAND
ALONE DEHUMIDIFICATION

ON SLAB

44.5X24X23.5

NOMINAL A/C TONS :

22x22,6",-64

18x12

22x22,7",-94

(TYPICAL x7)

22x22,6",-64

EXISTING

59.5X26X23.5

SUPPLY PLENUM SIZE :


RETURN PLENUM SIZE :

OUTDOOR AIR CFM:


8x4,4",23 CFM

AHU-3,4

EXISTING

UNIT WEIGHT:

E Restroom

8x4,4",10 CFM

AHU-1,2,5

UNIT MODEL NUMBER:

22x22,9",243 CFM
VTE

TYPICAL
BRANCH
DUCT

CONDENSING UNIT
ON SLAB
FMC SECTIONS
303 -- 312

1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS.
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING
IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES)
SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.

AIR HANDLER MARK:

RELOCATED
ABOVE
CEILING

EF-1

1" UNDERCUT DOOR


30 CFM T/A

Waiting

Corridor

18x16

AHU-2

PACKAGE UNIT
ROOF MOUNTED
FMC SECTIONS
303 -- 312

HVAC SCHEDULES + DETAILS

Lab
8x4,4",39 CFM

PACKAGE UNIT
SLAB MOUNTED
FMC SECTIONS
303 -- 312

ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT INTERIOR DOOR = ONLY 30 CFM OF RELIEF AIR.

UNIT DIMEN H/W/D:

22x22,10",-243

DUCTLESS AIR
HANDLER
FMC SECTIONS
303 -- 312

THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
HVAC SYMBOL, HVAC CONTRACTOR MUST REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.

SPLIT SYSTEM EQUIPMENT SCHEDULE

Break

22x22,10",307 CFM

22x22,10",307 CFM

AHU-5

DUCT MOUNTED
SMOKE DETECTOR
FMC SECTION 606

HVAC NOTES

22x22,7",-89

ON SLAB

AHU-4

HORIZONTAL AIR
HANDLER MOUNT
FROM STRUCTURE
FMC SECTIONS
303 --- 312

22x22,6",89 CFM

22x22,7",129 CFM

MAY CONFIGURE
EXISTING AHU
VERTICAL OR
HORIZONTAL

8x4,4",12 CFM

14x16

22x22,7",124 CFM

12x16

22x22,9",257

24x12

AHU-3

Exam

10x12

8x10

12x10

Exam

WALL MOUNTED
HUMIDISTAT @ 60"
ABOVE FLOOR

RANGE VENT
ROOF / WALL CAP
FMC 505 - 506

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
CALCULATIONS BASED ON ASHRAE 62.1 - 2007 TABLE 6-1 - PROCEDURE PROVIDES VENTILATION FOR VARIABLE / INTERMITTENT OCCUPANTS
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

BUILDING VENTILATION CALCULATION

THERMOSTAT @ 60"
ABOVE FLOOR
FEC 13-613

DRYER VENT
ROOF / WALL
CAP FMC 504

WALL GRILLE
FILTER RETURN
AIR FMC 603.15

AFF = ABOVE FINISH FLOOR


AHU = AIR HANDLING UNIT
BP = BYPASS DAMPER
BD = BAROMETRIC DAMPER

TOTAL PRESSURE:
FAN VOLTAGE:
FAN AMPERAGE:
FAN DIMEN LWH:
DUCT OUTLET SIZE:
DUCT INLET SIZE:
FAN WEIGHT:
NOTES:

.2
120/1/60
.7
9X9X6
4
10X10
12
1,2

1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS

North

PROJECT NAME: 14378 Spring Hill Dr Office Renovation


PROJECT ADDRESS: 14378 Spring Hill Drive
PROJECT STATE, ZIP: Spring Hill Florida (Hernando)
CONDITIONED SQ. FT.: 7563 Revised 9/28/08
CLASSIFICATION : Commercial Office Renovation

x
Designed By:
Neil Fimbel
HVAC Designs
813-885-2258
FL BERS R#884
FL BERS C#959

DRAWING DATE
9/28/2008
PERMIT SET
SCALE 1/8"=1'-0"

HVAC
DRAWING
1 OF 1

HVAC SYMBOLS

PARKING GARAGE NATURAL VENTILATION CALCULATION


FLOOR CLASSIFICATION
1

OPEN PARKING

OPEN WALL PERIMETER OPEN WALL HEIGHT GROSS OPEN AREA


328

10.00

% OF OPENING

GROSS PERIMETER

RESULT

54

597

PASSES

3280

BUILDING TOTALS

CEILING REGISTER
1 WAY THROW
FMC 603.15

RECTANGULAR
DUCTWORK
FMC SECTION 603

THERMOSTAT @ 60"
ABOVE FLOOR
FEC 13-613

CEILING REGISTER
2 WAY THROW
FMC 603.15

FLEXIBLE
DUCTWORK
FMC SECTION 603

WALL MOUNTED
HUMIDISTAT @ 60"
ABOVE FLOOR

CEILING REGISTER
3 WAY THROW
FMC 603.15

AIR DISTRIBUTION
BOXES FMC
SECTION 603

CEILING REGISTER
4 WAY THROW
FMC 603.15

RETURN AIR
PLENUM TRUNK
FMC SECTION 602

EQUIPMENT
ACCESS PANEL
FMC SECTION 306

CEILING REGISTER
CORNER THROW
FMC 603.15

SUPPLY AIR
PLENUM TRUNK
FMC SECTION 602

EXHAUST FAN
EF-1 or as NOTED
FMC SECTION 403

WALL REGISTER
2 WAY THROW
FMC 603.15

AIR VOLUME
CONTROL DAMPER
FMC 603.15

ZD

ZONE CONTROL
AIR DAMPER
FMC 303 -- 312

FLOOR REGISTER
2 WAY THROW
FMC 603.15

DUCT MOUNTED
FIRE DAMPER
FMC SECTION 607

BP

BYPASS AIR
DAMPER
FMC 303 -- 312

FLOOR GRILLE
FILTER RETURN
AIR FMC 603.15

DRYER VENT
ROOF / WALL
CAP FMC 504

RANGE VENT
ROOF / WALL CAP
FMC 505 - 506

CEILING GRILLE
FILTER RETURN
AIR FMC 603.15

597

OPENINGS ARE UNIFORMLY DISTRIBUTED ON ALL 4 WALLS, THE OPENING AREA EXCEEDS THE MINIMUM OF 20% OPENING TO PERIMETER WALL AREA.
CALCULATIONS BASED ON THE 2004 + SUPPLEMENTS FLORIDA MECHANICAL CODE SECTION 403.1, 403.3 AND FLORIDA BUILDING CODE 406.3.3.1

CONTROL /
REFRIGERANT
PIPING FMC 1101

WALL GRILLE
FILTER RETURN
AIR FMC 603.15

HORIZONTAL AIR
HANDLER MOUNT
FROM STRUCTURE
FMC SECTIONS
303 --- 312

DUCT MOUNTED
SMOKE DETECTOR
FMC SECTION 606

DUCTLESS AIR
HANDLER
FMC SECTIONS
303 -- 312

PACKAGE UNIT
SLAB MOUNTED
FMC SECTIONS
303 -- 312

PACKAGE UNIT
ROOF MOUNTED
FMC SECTIONS
303 -- 312

1" UNDERCUT DOOR


30 CFM T/A

CONDENSING UNIT
ON SLAB
FMC SECTIONS
303 -- 312

TYPICAL
BRANCH
DUCT
TYPICAL AIR
DEVICE

Walk In Closet

CEILING GRILLE
DUCTED T/ A
FMC 603.15

CONDENSATE
DRAIN TO GRASS
FMC SECTION 307

WALL GRILLE
DIRECT T/ A
FMC 603.15

CONDENSATE
TO DRYWELL
FMC SECTION 307

CFM = CUBIC FEET / MINUTE


CU = CONDENSING UNIT
DH = DE-HUMIDIFIER
E/A = EXHAUST AIR

AFF = ABOVE FINISH FLOOR


AHU = AIR HANDLING UNIT
BP = BYPASS DAMPER
BD = BAROMETRIC DAMPER

OPEN PARKING GARAGE


NATURALLY VENTILATED
COMPLIES WITH FBC 406.3.3.1
PIPING UP TO ROOF
FIRE CAULK PENETRATIONS
PUMP CONDESATE DRAIN
TO GUTTER / GRASS AREA

AHU-1

20x18

10x12

12x12,8",-105 CFM

22x22,16",-895 CFM

12x12 OAL,8" RELIEF AIR


DUCT SET BAROMETRIC
RELIEF AIR DAMPER TO
RELIEVE 105 CFM

Lobby

22x22,9",250 CFM

12x12 OAL,6" FRESH AIR


DUCT SET TO 105 CFM

EQUIPMENT
CONNECTION

CURB
CONNECTION
CURB
3/8 BOLT
@ 18" O.C.

ROOFTOP
EQUIPMENT

ROOF

REFRIGERANT PIPING
+ CONTROL WIRING
FMC 1101

1/2 THREADED ROD


SUSPEND FROM
TOP CHORD

RETURN DUCT
FMC 601

JOIST

CURB

CONNECT TO
TRUSS
MEMBER

AIR HANDLER
FMC 303

* CEILING

3/8"
SCREWS
1/4" PLATE
OR ANGLE
@ 18""
O.C.

HVAC SCHEDULES + DETAILS


ROOFTOP
EQUIPMENT
FMC 303

TRANE EQUIPMENT
AIR HANDLER MARK:
AHU-1

SUPPLY AIR DUCT FMC 601

AUX. DRAIN PAN + FLOAT


SWITCH FMC 301.2.3
CONDENSATE DRAIN FMC 307

UNIT MODEL NUMBER:

MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD
MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOAD

* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN


DRAWING FOR EXACT CONFIGURATION.

SUPPLY PLENUM SIZE :


RETURN PLENUM SIZE :

12.02X19.22
18.07X19.5

SUPPLY FAN CFM / SP :


SUPPLY FAN H/P :

1000 / .40
1/3
105

UNIT PHASE / HERTZ:

ROOFTOP CONDENSING UNIT DETAIL

1 / 60

UNIT VOLTAGE:
HEATER KW:

208 / 240
3.6 / 4.8

HEATER BREAKER:

25 / 30

CONDENSER MARK:

CU-1

NOMINAL A/C TONS :

FIRST FLOOR AIR BALANCE SCHEDULE


ZONE

ROOM NAME

OCCUPANTS

DURATION

SUPPLY AIR CFM

RETURN AIR CFM

RELIEF AIR CFM

FRESH AIR CFM

1
X

LOBBY
X

14
X

0.5
X

1000
X

895
X

105
X

105
X

14

0.5

1000

895

105

105

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

TIME

CLASSIFICATION

OCCUPANTS

DURATION

MAX. REQ. AIR

ADJUSTED AIR

TOTAL AIR

CFM / SQ FOOT

PEAK

Reception / Wait

14

0.50

15

7.5

105

7.5

105

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

2.5

UNIT MODEL NUMBER:


UNIT VOLTAGE:

2TTR3030A
208/230/ 1 / 60

UNIT MCA / BREAKER:


UNIT DIMEN H/W/D:

13 / 20
38X30.1X33

UNIT WEIGHT:
TOTAL COOLING BTUH:

198
27,600

SENS. COOLING BTUH:

20,400

LAT. COOLING BTUH:


TOTAL HEATING BTUH:

7,200
17,060

SENSIBLE HEAT %
SEER:

FIRST FLOOR VENTILATION CALCULATION

FIRST FLOOR TOTALS

46.5X24X23.5
125

OUTDOOR AIR CFM:

HORIZONTAL AIR HANDLER DETAIL

FIRST FLOOR TOTALS

2TEC3F30A

UNIT DIMEN H/W/D:


UNIT WEIGHT:

CURB

* ACCESS PANEL FMC 306.3

TYPICAL OPENING x10' HEIGHT

SF = SUPPLY FAN
T/A = TRANSFER AIR
VTE = VENT TO EXTERIOR
ZD = ZONE DAMPER

1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS.
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING
IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES)
SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.
THIS DESIGN IS FOR PEAK LOAD CONDITIONS ONLY, CONSIDER USING STAGED COOLING EQUIPMENT OR STAND ALONE DEHUMIDIFICATION FOR PART LOAD.

FIRST FLOOR

22x22,9",250 CFM

OPEN PARKING GARAGE


NATURALLY VENTILATED
COMPLIES WITH FBC 406.3.3.1

TYPICAL ROOM

ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.

22x22,9",250 CFM

* FRESH
AIR
DUCT
FMC 401

= AIRFLOW CFM
ADJUSTMENTS

THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.

ON ROOF
ABOVE

20x12

= BRANCH DUCT SIZE

Bedroom

PKG = PACKAGE UNIT


R/A = RETURN AIR
RTU = ROOFTOP UNIT
S/A = SUPPLY AIR

EF = EXHAUST FAN
FPM = FEET PER MINUTE
MUA = MAKE UP AIR
O/A = OUTSIDE AIR

= DEVICE NECK SIZE

HVAC NOTES

CU-1

22x22,9",250 CFM

ABOVE
CEILING

VERTICAL AIR
HANDLER ON STAND
FMC SECTIONS
303 --- 312

8x4
4"
32

THERMOSTAT MODEL:

0.74
13
T8411R1002

NOTES: ALTERNATE BRAND EQUIPMENT WITH


EQUAL PERFORMANCE ARE ACCEPTABLE.
SUBMIT PERFORMANCE DATA FOR APPROVAL.

North
PROJECT NAME:
PROJECT ADDRESS:
PROJECT STATE, ZIP:
CONDITIONED SQ. FT.:
CLASSIFICATION :

Prieto Office Building 1st Floor


Corner of Lakewood & Oakfield
Hillsborough County Florida
721 of 22,597
New Office Building

x
Designed By:
Neil Fimbel
HVAC Designs
813-885-2258
FLORIDA BERS
R#884 C#959

DRAWING DATE
1/31/2009
PERMIT SET
SCALE 1/8"=1'-0"

HVAC
DRAWING
1 OF 3

SECOND FLOOR VENTILATION CALCULATION


DURATION

PEAK
PEAK
PEAK

Conference
Office
Reception / Wait

10
56
23

VARIES
1.00
0.50

SECOND FLOOR TOTALS

MAX. REQ. AIR

ADJUSTED AIR

TOTAL AIR

CFM / SQ FOOT

19.75
20
7.5

197.5
1120
172.5

19.75
20
7.5

20
20
15

89

AIR HANDLER
FMC 303

RETURN DUCT
FMC 601

1490

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

SUPPLY AIR DUCT FMC 601


AUX. DRAIN PAN + FLOAT
SWITCH FMC 301.2.3
CONDENSATE DRAIN FMC 307

* CEILING

TYPICAL
PIPE CHASE
TO ROOF

10x6,5",63 CFM

14x12

Dr Off 1

22x22,5",63 CFM

18x20

18x21

Corridor

10x12

18x12

18x14

SR-82,8",165 CFM

PIPING UP FROM
LOBBY BELOW

CU-7
ON ROOF
CURB
ABOVE 3rd
FLOOR

22x22,8",165 CFM

22x22,8",165 CFM

Recep / Wait

8x4,4",51 CFM

16x10

22x22,8",165 CFM

22x22,7",-78 CFM
8x4,4",20 CFM

10x6,5",66 CFM

EF-2

Infusion
22x22,14",-640 CFM

22x22,9",213 CFM
22x22,9",213 CFM

SECOND FLOOR

EF-1

8x4,4",43 CFM

VTE

Restroom

AHU-8

18x20

22x22,8",198 CFM

EF-2
VTE

TYPICAL
UNLESS
NOTED

8x4,4",13 CFM

ABOVE
CEILING

127
CFM
T/A

20x12

22x22,8",198 CFM
22x22,8",198 CFM
12x12

12x8

8x12
22x22,8",198 CFM

22x22,16",-1060 CFM

CU-8
ON ROOF
CURB
ABOVE 3rd
FLOOR

Restroom
8x4,4",12 CFM

22x22,8",198 CFM

Unit 2 F
18x20

22x22,8",198 CFM

AHU-9

22x22,9",231 CFM

ABOVE
CEILING

20x12

148
CFM
T/A

22x22,9",231 CFM
22x22,9",231 CFM
16x12

10x12

10x12

22x22,16",-1240 CFM

22x22,9",231 CFM

22x22,9",231 CFM

CU-9
ON ROOF
CURB
ABOVE 3rd
FLOOR

Restroom
107
CFM
T/A

Unit 2 G
AHU-10

18x20

22x22,9",231 CFM

ABOVE
CEILING

8x4,4",13 CFM

20x12

22x22,8",198 CFM
22x22,8",198 CFM

22x22,8",198 CFM
12x12

12x8

8x12

22x22,8",198 CFM

22x22,16",-1080 CFM

CU-10
22x22,8",198 CFM

ON ROOF
CURB
ABOVE 3rd
FLOOR

22x22,8",198 CFM

North

FAN AMPERAGE:

1.0

.7

FAN DIMEN LWH:

14X10X9

9X9X6

3.25X10 TO 7

15X11

10X10

14

12

ON ROOF
CURB
ABOVE 3rd
FLOOR

8x4,4",14 CFM

18x20

Unit 2 H

12x8

12x8
12x12

CEILING REGISTER
2 WAY THROW
FMC 603.15

FLEXIBLE
DUCTWORK
FMC SECTION 603

WALL MOUNTED
HUMIDISTAT @ 60"
ABOVE FLOOR

CEILING REGISTER
3 WAY THROW
FMC 603.15

AIR DISTRIBUTION
BOXES FMC
SECTION 603

CEILING REGISTER
4 WAY THROW
FMC 603.15

RETURN AIR
PLENUM TRUNK
FMC SECTION 602

EQUIPMENT
ACCESS PANEL
FMC SECTION 306

CEILING REGISTER
CORNER THROW
FMC 603.15

SUPPLY AIR
PLENUM TRUNK
FMC SECTION 602

EXHAUST FAN
EF-1 or as NOTED
FMC SECTION 403

WALL REGISTER
2 WAY THROW
FMC 603.15

AIR VOLUME
CONTROL DAMPER
FMC 603.15

ZD

ZONE CONTROL
AIR DAMPER
FMC 303 -- 312

FLOOR REGISTER
2 WAY THROW
FMC 603.15

DUCT MOUNTED
FIRE DAMPER
FMC SECTION 607

BP

BYPASS AIR
DAMPER
FMC 303 -- 312

FLOOR GRILLE
FILTER RETURN
AIR FMC 603.15

DRYER VENT
ROOF / WALL
CAP FMC 504

RANGE VENT
ROOF / WALL CAP
FMC 505 - 506

1,2

2 = INTERLOCK WITH LIGHTS

CU-1

VTE

TYPICAL
UNLESS
NOTED

1,2

20x12

CEILING GRILLE
FILTER RETURN
AIR FMC 603.15

EQUIPMENT
CONNECTION

CURB
CONNECTION

TYPICAL

CURB

AHU-1

3/8 BOLT
@ 18" O.C.

ROOFTOP
EQUIPMENT

ROOF

ABOVE
CEILING

JOIST

CURB

22x22,8",198 CFM

22x22,8",198 CFM

ROOFTOP
EQUIPMENT
FMC 303

HORIZONTAL AIR
HANDLER MOUNT
FROM STRUCTURE
FMC SECTIONS
303 --- 312

DUCT MOUNTED
SMOKE DETECTOR
FMC SECTION 606

DUCTLESS AIR
HANDLER
FMC SECTIONS
303 -- 312

PACKAGE UNIT
SLAB MOUNTED
FMC SECTIONS
303 -- 312

PACKAGE UNIT
ROOF MOUNTED
FMC SECTIONS
303 -- 312

1" UNDERCUT DOOR


30 CFM T/A
TYPICAL
BRANCH
DUCT

CONDENSING UNIT
ON SLAB
FMC SECTIONS
303 -- 312

CONTROL /
REFRIGERANT
PIPING FMC 1101

TYPICAL AIR
DEVICE

Walk In Closet

CEILING GRILLE
DUCTED T/ A
FMC 603.15

CONDENSATE
DRAIN TO GRASS
FMC SECTION 307

WALL GRILLE
DIRECT T/ A
FMC 603.15

CONDENSATE
TO DRYWELL
FMC SECTION 307

22x22,8",164 CFM
22x22,8",164 CFM

WALL GRILLE
FILTER RETURN
AIR FMC 603.15

3/8"
SCREWS
1/4"
PLATE
OR
ANGLE
@ 18""
O.C.

AFF = ABOVE FINISH FLOOR


AHU = AIR HANDLING UNIT
BP = BYPASS DAMPER
BD = BAROMETRIC DAMPER

CFM = CUBIC FEET / MINUTE


CU = CONDENSING UNIT
DH = DE-HUMIDIFIER
E/A = EXHAUST AIR

22x22,8",164 CFM

22x22,8",164 CFM

22x22,8",198 CFM

22x22,8",198 CFM

Unit 2 B

22x22,8",164 CFM

MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND


LOAD
MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND
LOAD

22x22,8",164 CFM

VERTICAL AIR
HANDLER ON STAND
FMC SECTIONS
303 --- 312

= DEVICE NECK SIZE


= BRANCH DUCT SIZE
= AIRFLOW CFM
ADJUSTMENTS

Bedroom

TYPICAL ROOM

PKG = PACKAGE UNIT


R/A = RETURN AIR
RTU = ROOFTOP UNIT
S/A = SUPPLY AIR

EF = EXHAUST FAN
FPM = FEET PER MINUTE
MUA = MAKE UP AIR
O/A = OUTSIDE AIR

8x4
4"
32

SF = SUPPLY FAN
T/A = TRANSFER AIR
VTE = VENT TO EXTERIOR
ZD = ZONE DAMPER

Unit 2 A

HVAC NOTES

ROOFTOP CONDENSING UNIT DETAIL


THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.

SECOND FLOOR AIR BALANCE SCHEDULE

VTE

ZONE

ROOM NAME

OCCUPANTS

DURATION

SUPPLY AIR CFM

RETURN AIR CFM

EXHAUST AIR CFM

FRESH AIR CFM

1
1
X
ZONE

Unit 2 A
Restroom
X
ROOM NAME

6
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

986
14
X
SUPPLY AIR CFM

880
0
X
RETURN AIR CFM

0
120
X
EXHAUST AIR CFM

120
0
X
FRESH AIR CFM

2
2
X
ZONE

Unit 2 B
Restroom
X
ROOM NAME

8
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

1187
13
X
SUPPLY AIR CFM

1040
0
X
RETURN AIR CFM

0
160
X
EXHAUST AIR CFM

160
0
X
FRESH AIR CFM

3
3
X
ZONE

Unit 2 C
Restroom
X
ROOM NAME

7
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

986
14
X
SUPPLY AIR CFM

860
0
X
RETURN AIR CFM

0
120
X
EXHAUST AIR CFM

120
0
X
FRESH AIR CFM

4
4
4
4
4
4
4
4
4
4
4
X
ZONE

Server
Dr Off 4
Dr Off 3
Restroom
Dr Off 2
Restroom
Dr Off 1
Admin
Billing
F Office
Corridor
X
ROOM NAME

0
1
1
0
1
0
1
1
1
0
0
X
OCCUPANTS

N/A
> 3 HRS
> 3 HRS
N/A
> 3 HRS
N/A
> 3 HRS
> 3 HRS
> 3 HRS
N/A
N/A
X
DURATION

100
75
75
19
184
63
195
90
278
18
103
X
SUPPLY AIR CFM

100 T/A
75
75
0
184
0
195
90
278
0
183
X
RETURN AIR CFM

0
0
0
96
0
96
0
0
0
0
0
X
EXHAUST AIR CFM

0
20
20
0
20
0
20
20
20
0
0
X
FRESH AIR CFM

5
5
5
5
X
ZONE

Lunch
Restroom
Conference
Storage
X
ROOM NAME

4
0
10
0
X
OCCUPANTS

< 3 HRS
N/A
< 3 HRS
N/A
X
DURATION

307
14
868
11
X
SUPPLY AIR CFM

192
0
868
0
X
RETURN AIR CFM

0
95
0
0
X
EXHAUST AIR CFM

40
0
120
0
X
FRESH AIR CFM

6
6
6
6
6
X
ZONE

Files
Storage
Recep / Wait
Restroom
Phone
X
ROOM NAME

0
0
10
0
0
X
OCCUPANTS

N/A
N/A
VARIES
N/A
N/A
X
DURATION

28
28
825
54
65
X
SUPPLY AIR CFM

0
0
860
0
0
X
RETURN AIR CFM

0
0
0
95
0
X
EXHAUST AIR CFM

0
0
140
0
0
X
FRESH AIR CFM

7
7
7
7
7
7
7
7
7
7
7
7
7
7
X
ZONE

Infusion
Restroom
Pharmacy
Cold
P Infusion
Restroom
Exam 2
Exam 1
Lab
Restroom
Exam 3
Exam 4
Exam 5
Corridor
X
ROOM NAME

9
0
1
0
1
0
1
1
1
0
1
1
1
0
X
OCCUPANTS

VARIES
N/A
> 3 HRS
N/A
> 3 HRS
N/A
> 3 HRS
> 3 HRS
> 3 HRS
N/A
> 3 HRS
> 3 HRS
> 3 HRS
N/A
X
DURATION

640
43
249
51
66
20
223
63
92
92
252
63
65
81
X
SUPPLY AIR CFM

640
0
300
0
66
0
223
63
0
0
252
63
65
78
X
RETURN AIR CFM

0
96
0
0
0
96
0
0
0
96
0
0
0
0
X
EXHAUST AIR CFM

90
0
20
0
20
0
20
20
20
0
20
20
20
0
X
FRESH AIR CFM

8
8
X
ZONE

Unit 2 F
Restroom
X
ROOM NAME

7
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

1187
13
X
SUPPLY AIR CFM

1060
0
X
RETURN AIR CFM

0
140
X
EXHAUST AIR CFM

140
0
X
FRESH AIR CFM

9
9
X
ZONE

Unit 2 F
Restroom
X
ROOM NAME

8
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

1388
12
X
SUPPLY AIR CFM

1240
0
X
RETURN AIR CFM

0
160
X
EXHAUST AIR CFM

160
0
X
FRESH AIR CFM

10
10

Unit 2 F
Restroom

VTE

Cold

Restroom

22x22,8",164 CFM

EF-2
8x4,4",54 CFM

12x14

16x12

Lab

22x22,9",213 CFM

120/1/60

22x22,5",65 CFM

Restroom

22x22,5",63 CFM

Pharmacy

120/1/60

THERMOSTAT @ 60"
ABOVE FLOOR
FEC 13-613

22x22,14",-880 CFM

Unit 2 C

22x22,5",81 CFM

Restroom
P Infusion

.25

22x22,8",165 CFM

22x22,6",91 CFM

22x22,9",249 CFM

Phone

22x22,4",28 CFM

12x12,6",-66 CFM

TOTAL PRESSURE:

.25

CONNECT TO
TRUSS
MEMBER

22x22,8",164 CFM

22x22,14",-860 CFM

Exam 2

22x22,10",-300 CFM

92.85

Dr Off 4

Restroom

22x22,9",223 CFM

140

RECTANGULAR
DUCTWORK
FMC SECTION 603

22x22,5",75 CFM

Files

ABOVE
CEILING

22x22,6",-63 CFM

FAN CFM:

22x22,5",75 CFM

ABOVE
CEILING

AHU-7

VTE

EXHAUST

CURB

Exam 3
22x22,6",-63 CFM

EXHAUST

CEILING REGISTER
1 WAY THROW
FMC 603.15

1 = VENT TO EXTERIOR

EF-1

22x22,16",-1040 CFM

ABOVE
CEILING

ON ROOF
CURB
ABOVE 3rd
FLOOR

AHU-6
20x12

21x12

FAN TYPE:

F Office

Server

8x12

22x22,10",-252 CFM

20x12

AHU-2

ABOVE
CEILING

Dr Off 3

ON ROOF
CURB
ABOVE 3rd
FLOOR

8x4,4",13 CFM

18x20

Restroom

CU-2

8x12

18x20

22x22,6",-65 CFM

Exam 4

QT-110

NOTES:
106
CFM
T/A

22x22,16",-860 CFM

AHU-3

CU-5

8x4,4",19 CFM

10x6,6",100 CFM

TYPICAL
12x12,9" T/A
DUCT

22x22,6",-75 CFM

22x22,4",28 CFM

22x22,9",252 CFM

Exam 1

ON ROOF
CURB
ABOVE 3rd
FLOOR

Storage

Exam 5

20x12

8x12

12x12 T/A
HIGH WALL

22x22,5",65 CFM

18x20

CU-6

Corridor

VTE

ON ROOF
CURB
ABOVE 3rd
FLOOR

22x22,6",-75 CFM

22x22,6",103 CFM

EF-2

22x22,10",-223 CFM

Restroom

8x4,4",14 CFM

22x22,9",-183 CFM

8x12

20x12

AHU-5
ABOVE
CEILING

10x6,6",92 CFM

147
CFM
T/A

CU-3

Restroom

22x22,7",-90 CFM

Restroom

EF-2

126
CFM
T/A

VTE

12x12

Billing

QT-150

FAN WEIGHT:

8x4,4",19 CFM

22x22,9",-192 CFM

MODEL NUMBER:

DUCT OUTLET SIZE:

22x22,8",164 CFM

22x22,8",164 CFM

22x22,8",198 CFM

14x12

16x12

22x22,6",90 CFM

Restroom

EF-2

ABOVE
CEILING

8x4,4",11 CFM

8x4,4",14 CFM

22x22,8",198 CFM

22x22,8",164 CFM

CU-4
ON ROOF
CURB
ABOVE 3rd
FLOOR

AHU-4

22x22,10",289 CFM

10' SEPERATION

22x22,9",-184 CFM

12x12

Admin

22x22,14",-868 CFM

22x22,8",164 CFM

18x20

22x22,8",195 CFM

Storage

NUTONE

DUCT INLET SIZE:


20x12

22x22,10",278 CFM

NUTONE

10' SEPERATION

22x22,8",184 CFM

VTE

22x22,10",289 CFM

MANUFACTURER:

FAN VOLTAGE:

EF-2

22x22,10",307 CFM

22x22,10",289 CFM

TYPICAL
EXHAUST AIR EQUAL TO FRESH AIR
10' SEPERATION REQUIRED

Dr Off 2

Lunch
22x22,12",-278 CFM

TYPICAL
12x12 LOUVER + 9"
FRESH AIR INTAKE
SEE AIR BALANCE
SCHEDULE FOR CFM

HORIZONTAL AIR HANDLER DETAIL

Restroom

Conference

EF-2

* ACCESS PANEL FMC 306.3


* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN
DRAWING FOR EXACT CONFIGURATION.

22x22,9",-195 CFM

EF-1

FAN MARK:

12x8

OCCUPANTS

HVAC SYMBOLS

EXHAUST FAN SCHEDULE

12x12

CLASSIFICATION

1/2 THREADED ROD


SUSPEND FROM
TOP CHORD

8x12

TIME

REFRIGERANT PIPING +
CONTROL WIRING FMC
1101

* FRESH
AIR
DUCT
FMC 401

SECOND FLOOR TOTALS

6
0

89

> 3 HRS
N/A

VARIES

1187
13

12400

1080
0

10910

0
120

1490

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.
1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS.
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING
IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES)
SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.
THIS DESIGN IS FOR PEAK LOAD CONDITIONS ONLY, CONSIDER USING STAGED COOLING EQUIPMENT OR STAND ALONE DEHUMIDIFICATION FOR PART LOAD.

HVAC SCHEDULES + DETAILS


TRANE SPLIT SYSTEM EQUIPMENT SCHEDULE
AHU-1,3,6

AHU-2,4,5,8,10

AHU-7

AHU-9

2TEC3F30A

2TEC3F36A

2TEC3F60A

2TEC3F42A

46.5X24X23.5

46.5X24X23.5

59.5X26X23.5

53.25X26X23.5

125

125

155

150

SUPPLY PLENUM SIZE :

12.02X19.22

12.02X19.22

12.02X21.22

12.02X21.22

RETURN PLENUM SIZE :

18.07X19.5

18.07X19.5

18.07X21.5

18.07X21.5

SUPPLY FAN CFM / SP :

1000 / .40

1200 / .40

2000 / .40

1400 / .40

1/3

1/3

1/2

120/140/140

160/120/140/140/120

250

160

1 / 60

1 / 60

1 / 60

1 / 60

UNIT VOLTAGE:

208 / 240

208 / 240

208 / 240

208 / 240

HEATER KW:

3.6 / 4.8

3.6 / 4.8

7.2 / 9.6

3.6 / 4.8

HEATER BREAKER:

25 / 30

25 / 30

50 / 60

25 / 30

CONDENSER MARK:

CU-1,3,6

CU-2,4,5,8,10

CU-7

CU-9

AIR HANDLER MARK:


UNIT MODEL NUMBER:
UNIT DIMEN H/W/D:
UNIT WEIGHT:

SUPPLY FAN H/P :


OUTDOOR AIR CFM:
UNIT PHASE / HERTZ:

NOMINAL A/C TONS :

2.5

3.5

2TTR3030A

2TTR3036A

2TTR3060A

2TTR3042A

208/230/ 1 / 60

208/230/ 1 / 60

208/230/ 1 / 60

208/230/ 1 / 60

13 / 20

18 / 30

32 / 50

21 / 35

38X30.1X33

38X30.1X33

46.4X35.1X38.7

38.4X35.1X38.7

198

194

269

250

TOTAL COOLING BTUH:

27,600

34,200

58,000

41,000

SENS. COOLING BTUH:

20,400

25,400

40,000

29,800

UNIT MODEL NUMBER:


UNIT VOLTAGE:
UNIT MCA / BREAKER:
UNIT DIMEN H/W/D:
UNIT WEIGHT:

LAT. COOLING BTUH:

7,200

8,800

18,000

11,200

TOTAL HEATING BTUH:

17,060

17,060

34,120

17,060

0.74

0.74

0.69

0.73

13

13

13.5

13.5

T8411R1002

T8411R1002

T8411R1002

T8411R1002

SENSIBLE HEAT %
SEER:
THERMOSTAT MODEL:

NOTES: ALTERNATE BRAND EQUIPMENT WITH EQUAL PERFORMANCE ARE ACCEPTABLE.


SUBMIT PERFORMANCE DATA FOR APPROVAL.

120
0

1490

PROJECT NAME:
PROJECT ADDRESS:
PROJECT STATE, ZIP:
CONDITIONED SQ. FT.:
CLASSIFICATION :

Prieto Office Building 2nd Floor


Corner of Lakewood & Oakfield
Hillsborough County Florida
10,938 of 22,597
New Office Building

Designed By:
Neil Fimbel
HVAC Designs
813-885-2258
FLORIDA BERS
R#884 C#959

DRAWING DATE
1/31/2009
PERMIT SET
SCALE 1/8"=1'-0"

HVAC
DRAWING
2 OF 3

HVAC SYMBOLS

TYPICAL 12x12 LOUVER + BAROMETRIC


RELIEF AIR DAMPER + 12x12 RELIEF AIR
GRILLE -- FOR INTERIOR AIR PRESSURE
RELIEF / TYPICAL OF 4 ZONES

TYPICAL
EXHAUST AIR EQUAL TO FRESH AIR

Unit 3 Dwest

Unit 3 Deast

22x22,8",197 CFM

22x22,8",197 CFM

22x22,8",198 CFM

22x22,8",198 CFM

22x22,8",198 CFM

22x22,9",267 CFM

22x22,9",267 CFM

125
CFM
T/A

22x22,18",-1400 CFM

Restroom

TYPICAL
12x12,9"
T/A DUCT

148
CFM
T/A

12x12

22x22,18",-1400 CFM

12x12

16x14

8x14

12x14

22x22,9",267 CFM

22x22,16",-1060 CFM

22x22,9",267 CFM

EF-1

RTU-3

ON ROOF

ON ROOF

22x14

8x4,4",12 CFM

RTU-4

RTU-2

ON ROOF

22x14

22x14

106
CFM
T/A

Restroom

TYPICAL
UNLESS
NOTED

WALL MOUNTED
HUMIDISTAT @ 60"
ABOVE FLOOR

CEILING REGISTER
3 WAY THROW
FMC 603.15

AIR DISTRIBUTION
BOXES FMC
SECTION 603

CEILING REGISTER
4 WAY THROW
FMC 603.15

RETURN AIR
PLENUM TRUNK
FMC SECTION 602

EQUIPMENT
ACCESS PANEL
FMC SECTION 306

CEILING REGISTER
CORNER THROW
FMC 603.15

SUPPLY AIR
PLENUM TRUNK
FMC SECTION 602

EXHAUST FAN
EF-1 or as NOTED
FMC SECTION 403

WALL REGISTER
2 WAY THROW
FMC 603.15

AIR VOLUME
CONTROL DAMPER
FMC 603.15

ZD

ZONE CONTROL
AIR DAMPER
FMC 303 -- 312

FLOOR REGISTER
2 WAY THROW
FMC 603.15

DUCT MOUNTED
FIRE DAMPER
FMC SECTION 607

BP

BYPASS AIR
DAMPER
FMC 303 -- 312

FLOOR GRILLE
FILTER RETURN
AIR FMC 603.15

DRYER VENT
ROOF / WALL
CAP FMC 504

RANGE VENT
ROOF / WALL CAP
FMC 505 - 506

RTU-1

ON ROOF

22x14

22x14

ON ROOF

22x22,8",198 CFM

HORIZONTAL AIR
HANDLER MOUNT
FROM STRUCTURE
FMC SECTIONS
303 --- 312

DUCT MOUNTED
SMOKE DETECTOR
FMC SECTION 606

DUCTLESS AIR
HANDLER
FMC SECTIONS
303 -- 312

PACKAGE UNIT
SLAB MOUNTED
FMC SECTIONS
303 -- 312

16x14

22x22,198 CFM

22x22,8",197 CFM

22x14

22x22,8",198 CFM

Unit 3 B

Unit 3 C

22x22,9",267 CFM

22x22,9",267 CFM

ON ROOF

ZONE

ROOM NAME

OCCUPANTS

DURATION

SUPPLY AIR CFM

RETURN AIR CFM

EXHAUST AIR CFM

FRESH AIR CFM

1
1
X
ZONE

Unit 3 A
Restroom
X
ROOM NAME

6
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

1186
14
X
SUPPLY AIR CFM

1080
0
X
RETURN AIR CFM

0
120
X
EXHAUST AIR CFM

120
0
X
FRESH AIR CFM

2
2
X
ZONE

Unit 3 B
Restroom
X
ROOM NAME

8
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

1188
12
X
SUPPLY AIR CFM

1040
0
X
RETURN AIR CFM

0
160
X
EXHAUST AIR CFM

160
0
X
FRESH AIR CFM

3
3
X
ZONE

Unit 3 C
Restroom
X
ROOM NAME

7
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

1185
15
X
SUPPLY AIR CFM

1060
0
X
RETURN AIR CFM

0
140
X
RELIEF AIR CFM

140
0
X
FRESH AIR CFM

4
X
ZONE

Unit 3 Deast
X
ROOM NAME

10
X
OCCUPANTS

> 3 HRS
X
DURATION

1600
X
SUPPLY AIR CFM

1400
X
RETURN AIR CFM

200
X
RELIEF AIR CFM

200
X
FRESH AIR CFM

5
X
ZONE

Unit 3 Dwest
X
ROOM NAME

10
X
OCCUPANTS

> 3 HRS
X
DURATION

1600
X
SUPPLY AIR CFM

1400
X
RETURN AIR CFM

200
X
RELIEF AIR CFM

200
X
FRESH AIR CFM

6
X
ZONE

Unit 3 Enorth
X
ROOM NAME

10
X
OCCUPANTS

> 3 HRS
X
DURATION

1600
X
SUPPLY AIR CFM

1400
X
RETURN AIR CFM

200
X
RELIEF AIR CFM

200
X
FRESH AIR CFM

7
X
ZONE

Unit 3 Esouth
X
ROOM NAME

10
X
OCCUPANTS

> 3 HRS
X
DURATION

1600
X
SUPPLY AIR CFM

1400
X
RETURN AIR CFM

200
X
EXHAUST AIR CFM

200
X
FRESH AIR CFM

8
8
X
ZONE

Unit 3 F
Restroom
X
ROOM NAME

7
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

1187
13
X
SUPPLY AIR CFM

1060
0
X
RETURN AIR CFM

0
140
X
EXHAUST AIR CFM

140
0
X
FRESH AIR CFM

9
9
X
ZONE

Unit 3 G
Restroom
X
ROOM NAME

8
0
X
OCCUPANTS

> 3 HRS
N/A
X
DURATION

1587
13
X
SUPPLY AIR CFM

1440
0
X
RETURN AIR CFM

0
160
X
EXHAUST AIR CFM

160
0
X
FRESH AIR CFM

22x22,9",267 CFM

22x14

22x22,18",-1400 CFM

22x22,9",267 CFM

18x16

12x14

RTU-7

22x22,9",267 CFM

ON ROOF

22x22,9",267 CFM

THIRD FLOOR

22x22,9",267 CFM

Restroom
22x22,8",198 CFM
22x22,8",198 CFM

22x14

8x4,4",13 CFM

12x12

Unit 3 F

12x12

18x16

22x22,16",-1060 CFM

RTU-8
ON ROOF

22x22,8",198 CFM

22x22,8",198 CFM

22x22,8",198 CFM

Restroom
8x4,4",13 CFM

CURB
CONNECTION

DUCT
CONNECTION
ROOFTOP
EQUIPMENT

22x22,9",265 CFM

22x22,9",265 CFM

3/8 BOLT
@ 18" O.C.
ROOF

18x16

Unit 3 G

12x14

22x22,18",-1440 CFM

RTU-9
ON ROOF

22x22,9",265 CFM

22x22,9",265 CFM

22x22,9",265 CFM

Restroom

22x22,8",198 CFM

22x22,8",198 CFM

22x22,8",198 CFM

CURB

DUCT

JOIST

DUCT
SEAL
FMC 601
1/2"
SCREWS
@ 8" O.C.

EQUIPMENT
CONNECTION

ROOFTOP
EQUIPMENT
CURB

(4) 3/8x2
SCREWS
(1) 1/4x2x2
ANGLE
EACH
CORNER

2" U CHANNEL X
1/4" THK
SPAN 3 JOISTS

22x14
12x14

10
10

Unit 3 H
Restroom

THIRD FLOOR TOTALS


ROOFTOP
EQUIPMENT
FMC 303

R/A
DUCT
FMC
601

S/A
DUCT
FMC
601

CURB

NOTE: TIE DOWN METHOD MAY VARY


A/C CONTRACTOR MAY USE FLAT PLATE,
ANGLE PLATE, OR STRAP FOR TIE DOWN
BOLT AND SCREW SIZES MAY VARY - TIE
DOWN FOR A MAXIMUM OF 140 MPH WIND

MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD
MECHANICALLY FASTEN AND SEAL DUCTS PER FMC SECTIONS 603 AND 604
MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOAD

ROOFTOP PACKAGE UNIT DETAIL

6
0

> 3 HRS
N/A

82

> 3 HRS

1187
13

14000

1080
0

12360

0
120

1640

120
0

1640

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

THIRD FLOOR VENTILATION CALCULATION


TIME

CLASSIFICATION

OCCUPANTS

DURATION

MAX. REQ. AIR

ADJUSTED AIR

TOTAL AIR

CFM / SQ FOOT

PEAK

Office

82

1.00

20

20

1640

20

THIRD FLOOR TOTALS

82

TYPICAL ROOM
SF = SUPPLY FAN
T/A = TRANSFER AIR
VTE = VENT TO EXTERIOR
ZD = ZONE DAMPER

HVAC SCHEDULES + DETAILS


ROOFTOP EQUIPMENT SCHEDULE

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

12x12

RTU-10
22x22,8",198 CFM

22x22,8",198 CFM

RTU-4,5,6,7,9

EXHAUST FAN SCHEDULE


EF-1

FAN MARK:

UNIT MANUFACTURER:

TRANE

TRANE

MANUFACTURER:

NUTONE

UNIT MODEL NUMBER:

THC033A3

THC043A3

MODEL NUMBER:

QT-150

NOMINAL A/C TONS :

FAN TYPE:

EXHAUST

DOWNFLOW

DOWNFLOW

FAN CFM:

140

37X45X70

37X45X70

TOTAL PRESSURE:

.25

627

669

SUPPLY PLENUM SIZE :

17X15

17X15

RETURN PLENUM SIZE :

23X14

23X14

SUPPLY FAN CFM / SP :

1200 / .4

1600 / .4

120/160/140/140/120

200/200/200/200/160

3/60

3/60

208/230

208/230

19.9

22.6

30

35

HEATER KW:

4.5/6

9/12

HEATER MCA:

UNIT CONFIGURATION:
UNIT DIMEN H/W/D:
UNIT WEIGHT:

UNIT PHASE / HERTZ:


UNIT VOLTAGE:
UNIT MCA:

21.9/24.3

37.5/42.4

HEATER BREAKER:

25/25

40/45

TOTAL COOLING BTUH:

38,000

49,800

SENS. COOLING BTUH:

28,800

39,400

LAT. COOLING BTUH:

9,200

10,400

TOTAL HEATING BTUH:

20,472

40,944

0.76

0.79

COOLING EFFICIENCY:

13

13

THERMOSTAT MODEL:

T8411R1002

T8411R1002

SENS. HEAT %

22x22,8",198 CFM

RTU-1,2,3,8,10

PACKAGE UNIT MARK:

UNIT MAX BREAKER:

1640

22x22,16",-1080CFM

ON ROOF

Bedroom

PKG = PACKAGE UNIT


R/A = RETURN AIR
RTU = ROOFTOP UNIT
S/A = SUPPLY AIR

EF = EXHAUST FAN
FPM = FEET PER MINUTE
MUA = MAKE UP AIR
O/A = OUTSIDE AIR

= AIRFLOW CFM
ADJUSTMENTS

1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS.
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING
IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES)
SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.
THIS DESIGN IS FOR PEAK LOAD CONDITIONS ONLY, CONSIDER USING STAGED COOLING EQUIPMENT OR STAND ALONE DEHUMIDIFICATION FOR PART LOAD.

OUTDOOR AIR CFM:

Unit 3 H
18x16

CFM = CUBIC FEET / MINUTE


CU = CONDENSING UNIT
DH = DE-HUMIDIFIER
E/A = EXHAUST AIR

SUPPLY FAN H/P :

22x14

8x4,4",13 CFM

12x12

CONDENSATE
TO DRYWELL
FMC SECTION 307

= BRANCH DUCT SIZE

ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.

THIRD FLOOR AIR BALANCE SCHEDULE

22x22,9",267 CFM

12x14

WALL GRILLE
DIRECT T/ A
FMC 603.15

VERTICAL AIR
HANDLER ON STAND
FMC SECTIONS
303 --- 312

= DEVICE NECK SIZE

THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.

RTU-6

Unit 3 Esouth

CONDENSATE
DRAIN TO GRASS
FMC SECTION 307

8x4
4"
32

Unit 3 A

22x22,18",-1400 CFM

Unit 3 Enorth

TYPICAL AIR
DEVICE

HVAC NOTES

12x14

18x16

TYPICAL
BRANCH
DUCT

CONDENSING UNIT
ON SLAB
FMC SECTIONS
303 -- 312

CONTROL /
REFRIGERANT
PIPING FMC 1101

22x22,198 CFM

22x22,8",198 CFM

1" UNDERCUT DOOR


30 CFM T/A

CEILING GRILLE
DUCTED T/ A
FMC 603.15

AFF = ABOVE FINISH FLOOR


AHU = AIR HANDLING UNIT
BP = BYPASS DAMPER
BD = BAROMETRIC DAMPER

12x14

22x22,8",197 CFM

22x22,9",267 CFM

PACKAGE UNIT
ROOF MOUNTED
FMC SECTIONS
303 -- 312

Walk In Closet

12x12

TYPICAL CURB MOUNTED


CONDENSING UNIT ON ROOF ABOVE
SPLIT SYSTEMS SERVE FIRST AND
SECOND FLOORS

TYPICAL
FRESH AIR INTAKE @
ROOFTOP EQUIPMENT

22x22,8",198 CFM
12x12

22x22,8",197 CFM

WALL GRILLE
FILTER RETURN
AIR FMC 603.15

22x22,198 CFM

22x22,198 CFM

12x12

22x22,9",267 CFM

22x22,9",267 CFM

22x22,9",267 CFM

22x22,8",197 CFM

18x16

18x16

18x16
12x14

8x14

22x22,9",267 CFM

CEILING GRILLE
FILTER RETURN
AIR FMC 603.15

TYPICAL
CONDENSATE DRAIN
TO GUTTER / GRASS

22x22,9",267 CFM

22x22,9",267 CFM

107
CFM
T/A

FLEXIBLE
DUCTWORK
FMC SECTION 603

8x4,4",14 CFM

18x16

18x16

8x4,4",15 CFM

RTU-5

22x22,9",267 CFM

147
CFM
T/A

CEILING REGISTER
2 WAY THROW
FMC 603.15

22x22,16",-1080 CFM

VTE

22x22,9",265 CFM

THERMOSTAT @ 60"
ABOVE FLOOR
FEC 13-613

22x22,8",198 CFM

22x22,16",-1040 CFM

Restroom

127
CFM
T/A

12x12

22x22,9",267 CFM

22x22,198 CFM

RECTANGULAR
DUCTWORK
FMC SECTION 603

22x22,9",267 CFM

22x22,9",267 CFM

22x22,9",267 CFM

CEILING REGISTER
1 WAY THROW
FMC 603.15

120/1/60

FAN VOLTAGE:
FAN AMPERAGE:

1.0

FAN DIMEN LWH:

14X10X9

DUCT OUTLET SIZE:

3.25X10 TO 7

DUCT INLET SIZE:

15X11

FAN WEIGHT:

14

NOTES:

1,2

1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS

NOTES: ALTERNATE BRAND EQUIPMENT WITH


EQUAL PERFORMANCE ARE ACCEPTABLE.
SUBMIT PERFORMANCE DATA FOR APPROVAL.

North
PROJECT NAME:
PROJECT ADDRESS:
PROJECT STATE, ZIP:
CONDITIONED SQ. FT.:
CLASSIFICATION :

Prieto Office Building 2nd Floor


Corner of Lakewood & Oakfield
Hillsborough County Florida
10,938 of 22,597
New Office Building

x
Designed By:
Neil Fimbel
HVAC Designs
813-885-2258
FLORIDA BERS
R#884 C#959

DRAWING DATE
1/31/2009
PERMIT SET
SCALE 1/8"=1'-0"

HVAC
DRAWING
3 OF 3