HVAC SYMBOLS
CEILING REGISTER
1 WAY THROW
FMC 603.15
RECTANGULAR
DUCTWORK
FMC SECTION 603
THERMOSTAT @ 60"
ABOVE FLOOR
FEC 13-613
CEILING
REGISTER
2 WAY THROW
FMC 603.15
FLEXIBLE
DUCTWORK
FMC SECTION 603
WALL MOUNTED
HUMIDISTAT @ 60"
ABOVE FLOOR
AIR DISTRIBUTION
BOXES FMC
SECTION 603
CEILING REGISTER
4 WAY THROW
FMC 603.15
RETURN AIR
PLENUM TRUNK
FMC SECTION 602
EQUIPMENT
ACCESS PANEL
FMC SECTION 306
CEILING REGISTER
CORNER THROW
FMC 603.15
SUPPLY AIR
PLENUM TRUNK
FMC SECTION 602
EXHAUST FAN
EF-1 or as NOTED
FMC SECTION 403
WALL REGISTER
2 WAY THROW
FMC 603.15
AIR VOLUME
CONTROL DAMPER
FMC 603.15
ZD
ZONE CONTROL
AIR DAMPER
FMC 303 -- 312
FLOOR REGISTER
2 WAY THROW
FMC 603.15
DUCT MOUNTED
FIRE DAMPER
FMC SECTION 607
BP
BYPASS AIR
DAMPER
FMC 303 -- 312
FLOOR GRILLE
FILTER RETURN
AIR FMC 603.15
DRYER VENT
ROOF / WALL
CAP FMC 504
RANGE VENT
ROOF / WALL CAP
FMC 505 - 506
CEILING GRILLE
FILTER RETURN
AIR FMC 603.15
CEILING GRILLE
DUCTED T/A
FMC 603.15
CONDENSATE
DRAIN TO GRASS
FMC SECTION 307
WALL GRILLE
DIRECT T/ A
FMC 603.15
CONDENSATE
TO DRYWELL
FMC SECTION 307
ZONE
ROOM NAME
OCCUPANTS
DURATION
1
1
1
1
1
1
X
ZONE
Class
Science
Corridor 1
Locker G
Restroom G
Restroom B
X
ROOM NAME
17
17
0
0
0
0
X
OCCUPANTS
> 3 HRS
> 3 HRS
N/A
N/A
N/A
N/A
X
DURATION
797
686
97
51
88
81
X
SUPPLY AIR CFM
795
685
0
0
0
0
X
RETURN AIR CFM
0
0
0
300
300
300
X
EXHAUST AIR CFM
255
255
0
0
0
0
X
FRESH AIR CFM
2
2
2
2
2
2
2
X
ZONE
Mech
Locker B
Restroom
Lobby
Office
Reading
Corridor 2
X
ROOM NAME
0
0
0
0
2
17
0
X
OCCUPANTS
> 3 HRS
N/A
N/A
N/A
> 3 HRS
> 3 HRS
N/A
X
DURATION
51
36
29
535
527
485
137
X
SUPPLY AIR CFM
0
0
0
520
500
460
0
X
RETURN AIR CFM
0
325
50
0
0
0
0
X
EXHAUST AIR CFM
0
0
0
0
40
255
0
X
FRESH AIR CFM
3
3
3
3
3
X
ZONE
Media
Electric
Office 102
Office 101
Corridor 3
X
ROOM NAME
17
0
1
1
0
X
OCCUPANTS
> 3 HRS
N/A
> 3 HRS
> 3 HRS
N/A
X
DURATION
900
67
336
412
85
X
SUPPLY AIR CFM
860
67 T/A
620
0
0
X
RETURN AIR CFM
0
0
0
0
0
X
EXHAUST AIR CFM
255
0
20
20
0
X
FRESH AIR CFM
4
4
4
4
4
4
4
4
4
X
ZONE
Computers
Break
Office 120
Office 121
Office 123
Office 125
Pricipal
Office 122
Corridor 4
X
ROOM NAME
17
0
1
1
1
1
1
1
0
X
OCCUPANTS
> 3 HRS
N/A
> 3 HRS
> 3 HRS
> 3 HRS
> 3 HRS
> 3 HRS
> 3 HRS
N/A
X
DURATION
955
86
93
157
157
174
103
70
5
X
SUPPLY AIR CFM
889
86 T/A
93 T/A
157
157
174
103
70 T/A
0
X
RETURN AIR CFM
0
0
0
0
0
0
0
0
0
X
EXHAUST AIR CFM
255
0
20
20
20
20
20
20
0
X
FRESH AIR CFM
SERVER
N/A
600
405
200
95
> 3 HRS
7800
6325
1475
1475
CLASSIFICATION
OCCUPANTS
DURATION
ADJUSTED AIR
TOTAL AIR
PEAK
PEAK
Classrooms
Office
85
10
1.00
1.00
15
20
15
20
1275
200
15
20
BUILDING TOTALS
95
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
TYPICAL AIR
DEVICE
Walk In Closet
VERTICAL AIR
HANDLER ON
STAND
FMC SECTIONS
303 --- 312
Bedroom
TYPICAL ROOM
SF = SUPPLY FAN
T/A = TRANSFER AIR
VTE = VENT TO EXTERIOR
ZD = ZONE DAMPER
1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS.
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER.
1475
EF-3
TYPICAL
BRANCH
DUCT
CONDENSING UNIT
ON SLAB
FMC SECTIONS
303 -- 312
ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.
22x22,9",263 CFM
PACKAGE UNIT
ROOF MOUNTED
FMC SECTIONS
303 -- 312
THIS HVAC DDRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
Lobby
PACKAGE UNIT
SLAB MOUNTED
FMC SECTIONS
303 -- 312
HVAC NOTES
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
Office
DUCTLESS
AIR
HANDLER
FMC
SECTIONS
303 -- 312
1" UNDERCUT
DOOR
30 CFM T/A
EF = EXHAUST FAN
FPM = FEET PER MINUTE
MUA = MAKE UP AIR
O/A = OUTSIDE AIR
BUILDING TOTALS
CONTROL /
REFRIGERANT
PIPING FMC 1101
WALL GRILLE
FILTER RETURN
AIR FMC 603.15
22x22,9",263 CFM
DUCT MOUNTED
SMOKE DETECTOR
FMC SECTION 606
CEILING REGISTER
3 WAY THROW
FMC 603.15
HORIZONTAL AIR
HANDLER
MOUNT
FROM
STRUCTURE
FMC SECTIONS
303 --- 312
VTE
Restroom G
Locker G
Restroom B
16x16,9",-300 CFM
10x10
Mech
Locker B
12x12,7",-125 CFM
16x16,9",-300 CFM
Reading
Media
Electric
22x22,9",300 CFM
Office 101
Office 102
22x22,5",67 CFM
22x22,8",168 CFM
10x14
10x14
12x16
22x22,8",161 CFM
10x12
8x4,4",36 CFM
8x4,4",51 CFM
16x16,9",-200 CFM
22x22,5",88 CFM
22x22,5",81 CFM
22x22,9",300 CFM
22x22,8",161 CFM
EF-1
6x12
Restroom
24x12
14x12
14x12
TRANE EQUIPMENT
22x22,9",206 CFM
22x22,9",300 CFM
22x22,8",168 CFM
22x22,16",-860 CFM
Corridor
24x12 2
14x16
24x18
AHU-2
10x12
MECH ROOM
ABOVE CEILING
Corridor 1
22x22,6",97 CFM
22x22,7",140 CFM
24x18
Office 122
Pricipal Office
24x12
22x22,7",-103 CFM
22x22,9",238 CFM
22x22,6",93 CFM
24x12
22x22,9",199 CFM
22x22,8",171 CFM
14x12
22x22,8",171 CFM
14x12
TRANSFER AIR
FROM BREAK
- CORRIDOR
HIGH WALL
22x22,9",171 CFM
8x12
14x12
24x12
Class
22x22,9",238 CFM
Science
22x22,9",238 CFM
AHU-5
CU-2
2TTR4060A
208/230/ 1 / 60
34 / 50
46.4X35.1X38.7
ON SLAB
ON SLAB
ON SLAB
44,500
16,500
34,120
CU-3
2.5
GRADE
CU-5
EQUIPMENT SLAB
CCW18000
200/230/ 1 / 60
12.5 / 20
35X12X28
UNIT WEIGHT:
TOTAL COOLING BTUH:
156
18,400
11,200
7,200
17,000
SEER:
0.73
14
FASTENER
FMC 301.13
29
* FRESH
AIR
DUCT
FMC 401
REFRIGERANT PIPING +
CONTROL WIRING FMC
1101
13
THERMOSTAT MODEL:
RETURN DUCT
FMC 601
T8411R1002
Office 123
Office 125
EF-3
GREENHECK
690
QT-200
CSP-264
EXHAUST
EXHAUST
INLINE EXHAUST
50
200
1225
0.25
.25
.5
120/1/60
120 / 1 / 60
FAN VOLTAGE:
EF-2
NUTONE
FAN CFM:
TOTAL PRESSURE:
EF-1
NUTONE
FAN TYPE:
MODEL NUMBER:
ON SLAB
279
61,000
FLOOR
42X12X8
CONDENSER MARK:
UNIT VOLTAGE:
WALL
200/230/ 1 / 60
CONDENSING UNIT
FMC 303
HEATSTRIP KW:
50 / 60
120/1/60
FAN AMPERAGE:
0.5
1.0
7.8
9X11X8
14X10X9
24X14X14
3.25X10 TO 7
19X8
12X11
15X11
23X13
10
1,2
14
59
1,3
1,2
1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS
CU-5
.35
UNIT WEIGHT:
CU-1,2,3,4
FAN WEIGHT:
NOTES:
CU-1
600 / .40
* CEILING
Office 121
NOTE: AHU-5, CU-5 ARE
OPTIONAL ONLY IF
THIS ROOM IS USED
FOR COMPUTER SERVERS
FOR OFFICE - USE 7" S/A
DUCT AND 22x22 GRILLE
WALL MOUNT
Computers
DUCTLESS
CONDENSER MARK:
NOMINAL A/C TONS :
MANUFACTURER:
22x22,8",171 CFM
UNIT VOLTAGE:
208 / 240
7.2 / 9.6
FAN MARK:
22x22,9",199 CFM
DUCTLESS
HEATER BREAKER:
Corridor 4
DUCTLESS
AIR HANDLER
600 CFM S/A
600 CFM R/A
NO OCCUPANCY
1.5
368
1 / 60
ACWH1800
Server
VTE
1800 / .40
1
THERMOSTAT MODEL:
EF-2
SENSIBLE HEAT %
SEER:
22x22,6",103 CFM
12x16
10x12
24X12
24X18
UNIT WEIGHT:
TOTAL COOLING BTUH:
22x22,9",238 CFM
16x12
24x18
Office 120
22x22,5",86 CFM
22x22,18",-686
22x22,5",85 CFM
MECH ROOM
ABOVE CEILING
Break
AHU-4
22x22,16",-889 CFM
TWE065E
AHU-5
63X26X21
218
UNIT VOLTAGE:
HEATER KW:
MECH ROOM
ABOVE CEILING
Corridor 3
MECH ROOM
ABOVE CEILING
22x22,14",-620 CFM
AHU-3
AHU-1
24x12
24x12
24x18
8x4,4",29 CFM
AHU-1,2,3,4
24x12
22x22,9",199 CFM
22x22,9",206 CFM
VTE
8x4,4",51 CFM
22x22,9",199 CFM
10x12
22x22,8",161 CFM
ENCLOSED MECHANICAL
ROOM IN ATTIC, R-19
INSULATION + SEALED
GWB, PROVIDE ACCESS
CU-4
ON SLAB
North
Designed By:
Neil Fimbel
HVAC Designs
813-885-2258
FL BERS #884
DRAWING DATE
8/26/2008
PERMIT SET
SCALE
1/8"=1'-0"
HVAC
DRAWING
1 OF 1
* FRESH
AIR DUCT
FMC 401
HVAC NOTES
SUPPLY
AIR DUCT
FMC 601
* CEILING
THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
HVAC SYMBOL, HVAC CONTRACTOR MUST REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.
AIR HANDLER
FMC 303
22x22,10",300 CFM
Unit J1
22x22,10",300 CFM
AIR HANDLER
STAND
22x22,10",284 CFM
22x22,10",284 CFM
22x22,10",284 CFM
B
B
Unit J2
VERTICAL AIR
HANDLER DETAIL
22x22,10",300 CFM
Toilet 10
EF-1
CONDENSATE
DRAIN
FMC 307
22x22,10",300 CFM
ON STAND
8x4,5",63 CFM
1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS.
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING
IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES)
SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.
FLOOR
16"
AHU-10A
16"
ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT INTERIOR DOOR = ONLY 30 CFM OF RELIEF AIR.
REFRIGERANT
PIPING
+ CONTROL
WIRING
FMC 1101
22x22,10",284 CFM
VTE
AHU-10B
10' MINIMUM
FROM PARKING
RAIL
PIPE COVER
ON STAND
Toilet 9
AHU-9
8x4,4",47 CFM
CONDENSING UNIT
FMC 303
ON STAND
22x22,10",311 CFM
22x22,10",311 CFM
FASTENER
FMC 301.13
16"
B
EQUIPMENT
PLATFORM
RAISED
PLATFORM
WALL
CU-10A
HVAC SYMBOLS
FLOOR
CU-10B
22x22,10",311 CFM
RECTANGULAR
DUCTWORK
FMC SECTION 603
CEILING REGISTER
2 WAY THROW
FMC 603.15
FLEXIBLE
DUCTWORK
FMC SECTION 603
CEILING REGISTER
3 WAY THROW
FMC 603.15
AIR DISTRIBUTION
BOXES FMC
SECTION 603
CEILING REGISTER
4 WAY THROW
FMC 603.15
RETURN AIR
PLENUM TRUNK
FMC SECTION 602
EQUIPMENT
ACCESS PANEL
FMC SECTION 306
CEILING REGISTER
CORNER THROW
FMC 603.15
SUPPLY AIR
PLENUM TRUNK
FMC SECTION 602
EXHAUST FAN
EF-1 or as NOTED
FMC SECTION 403
WALL REGISTER
2 WAY THROW
FMC 603.15
AIR VOLUME
CONTROL DAMPER
FMC 603.15
ZD
ZONE CONTROL
AIR DAMPER
FMC 303 -- 312
FLOOR REGISTER
2 WAY THROW
FMC 603.15
DUCT MOUNTED
FIRE DAMPER
FMC SECTION 607
BP
BYPASS AIR
DAMPER
FMC 303 -- 312
FLOOR GRILLE
FILTER RETURN
AIR FMC 603.15
CEILING GRILLE
FILTER RETURN
AIR FMC 603.15
THERMOSTAT @ 60"
ABOVE FLOOR
FEC 13-613
WALL MOUNTED
HUMIDISTAT @ 60"
ABOVE FLOOR
CEILING GRILLE
DUCTED T/A
FMC 603.15
CONDENSATE
DRAIN TO GRASS
FMC SECTION 307
WALL GRILLE
DIRECT T/ A
FMC 603.15
CONDENSATE
TO DRYWELL
FMC SECTION 307
DUCTLESS AIR
HANDLER
FMC SECTIONS
303 -- 312
PACKAGE UNIT
SLAB MOUNTED
FMC SECTIONS
303 -- 312
PACKAGE UNIT
ROOF MOUNTED
FMC SECTIONS
303 -- 312
RANGE VENT
ROOF / WALL CAP
FMC 505 - 506
CONTROL /
REFRIGERANT
PIPING FMC 1101
HORIZONTAL AIR
HANDLER MOUNT
FROM STRUCTURE
FMC SECTIONS
303 --- 312
DUCT MOUNTED
SMOKE DETECTOR
FMC SECTION 606
DRYER VENT
ROOF / WALL
CAP FMC 504
WALL GRILLE
FILTER RETURN
AIR FMC 603.15
TYPICAL
BRANCH
DUCT
CONDENSING UNIT
ON SLAB
FMC SECTIONS
303 -- 312
8x4
4"
32
TYPICAL AIR
DEVICE
Walk In Closet
VERTICAL AIR
HANDLER ON STAND
FMC SECTIONS
303 --- 312
Bedroom
TYPICAL ROOM
SF = SUPPLY FAN
T/A = TRANSFER AIR
VTE = VENT TO EXTERIOR
ZD = ZONE DAMPER
EF = EXHAUST FAN
FPM = FEET PER MINUTE
MUA = MAKE UP AIR
O/A = OUTSIDE AIR
22x22,10",311 CFM
22x22,10",311 CFM
Unit I
CU-9
CEILING REGISTER
1 WAY THROW
FMC 603.15
CU-6
UNCONDITIONED
LOBBY
Unit H
CU-7
10' MINIMUM
FROM PARKING
CU-8
10" O/A DUCT
22x22,10",326 CFM
Unit G
Unit D
Unit E
Unit F
Unit B
Unit C
22x22,10",300 CFM
22x22,10",312 CFM
22x22,10",300 CFM
Unit A1
22x22,10",312 CFM
12" O/A DUCT
22x22,10",310 CFM
22x22,10",310 CFM
C
22x22,10",312 CFM
18"
22x22,10",326 CFM
22x22,10",326 CFM
22x22,10",300 CFM
16"
22x22,10",300 CFM
22x22,10",310 CFM
22x22,10",310 CFM
22x22,10",312 CFM
Unit A2
16"
16"
22x22,10",287 CFM
AHU-2
ON STAND
2 STG
AHU-1B
22x22,10",287 CFM
ON STAND
16"
B
22x22,10",310 CFM
AHU-6
22x22,10",326 CFM
22x22,10",326 CFM
AHU-8
AHU-7
ON STAND
ON STAND
ON STAND
AHU-4
AHU-5
AHU-3
ON STAND
ON STAND
ON STAND
AHU-1A
22x22,10",312 CFM
ON STAND
Toilet 3
8x4,4",42 CFM
EF-1
EF-1
VTE
VTE
Toilet 8
8x4,4",48 CFM
Toilet 6
Toilet 7
Toilet 4
VTE
8x4,4",42 CFM
Toilet 5
Toilet 1
Toilet 2
CU-4
CU-5
CU-3
CU-2
22x22,10",287 CFM
EF-1
EF-1
VTE
22x22,10",287 CFM
8x4,4",53 CFM
CU-1A CU-1B
RAISED PLATFORM
ROOM NAME
OCCUPANTS
DURATION
1
X
ZONE
UNIT A1
X
ROOM NAME
6
X
OCCUPANTS
> 3 HRS
X
DURATION
1200
X
SUPPLY AIR CFM
960
X
RETURN AIR CFM
240
X
EXHAUST AIR CFM
240
X
FRESH AIR CFM
2
2
X
ZONE
UNIT B
TOILET
X
ROOM NAME
9
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
1558
42
X
SUPPLY AIR CFM
1240
0
X
RETURN AIR CFM
360
80 SWITCHED
X
EXHAUST AIR CFM
360
0
X
FRESH AIR CFM
3
3
X
ZONE
UNIT C
TOILET
X
ROOM NAME
9
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
1558
42
X
SUPPLY AIR CFM
1240
0
X
RETURN AIR CFM
360
80 SWITCHED
X
EXHAUST AIR CFM
360
0
X
FRESH AIR CFM
4
4
X
ZONE
UNIT D
TOILET
X
ROOM NAME
9
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
1558
42
X
SUPPLY AIR CFM
1240
0
X
RETURN AIR CFM
360
80 SWITCHED
X
EXHAUST AIR CFM
360
0
X
FRESH AIR CFM
5
5
X
ZONE
UNIT E
TOILET
X
ROOM NAME
9
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
1558
42
X
SUPPLY AIR CFM
1240
0
X
RETURN AIR CFM
360
80 SWITCHED
X
EXHAUST AIR CFM
360
0
X
FRESH AIR CFM
6
6
X
ZONE
UNIT F
TOILET
X
ROOM NAME
9
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
1558
42
X
SUPPLY AIR CFM
1240
0
X
RETURN AIR CFM
360
80 SWITCHED
X
EXHAUST AIR CFM
360
0
X
FRESH AIR CFM
FAN MARK:
7
7
X
ZONE
UNIT G
TOILET
X
ROOM NAME
9
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
1552
48
X
SUPPLY AIR CFM
1240
0
X
RETURN AIR CFM
360
80 SWITCHED
X
EXHAUST AIR CFM
360
0
X
FRESH AIR CFM
FAN TYPE:
EXHAUST
FAN CFM:
80
HEATER BREAKER:
TOTAL PRESSURE:
.25
8
8
X
ZONE
UNIT H
TOILET
X
ROOM NAME
12
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
1958
42
X
SUPPLY AIR CFM
1600
0
X
RETURN AIR CFM
400
80 SWITCHED
X
EXHAUST AIR CFM
400
0
X
FRESH AIR CFM
FAN VOLTAGE:
120/1/60
9
9
X
ZONE
UNIT I
TOILET
X
ROOM NAME
10
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
1553
47
X
SUPPLY AIR CFM
1200
0
X
RETURN AIR CFM
400
80 SWITCHED
X
EXHAUST AIR CFM
400
0
X
FRESH AIR CFM
10
10
X
ZONE
UNIT J1
TOILET
X
ROOM NAME
5
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
1137
63
X
SUPPLY AIR CFM
960
0
X
RETURN AIR CFM
240
80 SWITCHED
X
EXHAUST AIR CFM
240
0
X
FRESH AIR CFM
8,800
13,200
18,000
13,200
11
11
X
ZONE
UNIT A2
TOILET
X
ROOM NAME
6
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
1147
53
X
SUPPLY AIR CFM
960
0
X
RETURN AIR CFM
240
80 SWITCHED
X
EXHAUST AIR CFM
240
0
X
FRESH AIR CFM
25,590
34,120
34,120
34,120
0.74
0.72
0.69
0.72
13
13
13.5
13
12
UNIT J2
> 3 HRS
1200
960
240
240
THERMOSTAT MODEL:
T8411R1002
T8411R1002
T8411R1002
T8411R1002
97
> 3 HRS
18000
14080
3920
3920
BUILDING TOTALS
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
AHU-2,3,4,5,6,7
AHU-8
AHU-9
TIME
CLASSIFICATION
OCCS / SF
DURATION
ADJUSTED AIR
TOTAL AIR
CFM / SF
2TEC3F36A
2TEC3F48A
2TEC3F60A
2TEC3F48A
PEAK
97 / 13066
1.00
0.3
0.3
3919.8
0.3
46.5X24X23.5
59.5X26X23.5
59.5X26X23.5
59.5X26X23.5
125
151
155
151
12.02X19.22
12.02X21.22
12.02X21.22
12.02X21.22
18.07X19.5
18.07X21.5
18.07X21.5
18.07X21.5
1200 / .40
1600 / .40
2000 / .40
1600 / .40
MANUFACTURER:
NUTONE
MODEL NUMBER:
QT-80
FAN AMPERAGE:
FAN DIMEN LWH:
DUCT INLET SIZE:
FAN WEIGHT:
NOTES:
1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS
.7
9X9X6
4
10X10
1/3
1/2
1/2
240
360
420
400
1 / 60
1 / 60
1 / 60
1 / 60
UNIT VOLTAGE:
208 / 240
208 / 240
208 / 240
208 / 240
HEATER KW:
5.76 / 7.68
7.2 / 9.6
7.2 / 9.6
7.2 / 9.6
40 / 45
50 / 60
50 / 60
50 / 60
CONDENSER MARK:
CU-1A,1B,10A,10B
CU-2,3,4,5,6,7
CU-8
CU-9
2TTR3036A
2TTR3048A
2TTR3060A
2TTR3048A
208/230/ 1 / 60
208/230/ 1 / 60
208/230/ 1 / 60
208/230/ 1 / 60
18 / 30
25 / 40
32 / 50
25 / 40
38X30.1X33
46.4X35.1X38.7
46.4X35.1X38.7
46.4X35.1X38.7
12
UNIT WEIGHT:
194
273
269
273
1,2
34,200
47,000
58,000
47,000
25,400
33,800
40,000
33,800
SENSIBLE HEAT %
SEER:
BUILDING TOTALS
3920 PROVIDED
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
North
Designed By:
Neil Fimbel
HVAC Designs
813-885-2258
FL BERS R#884
FL BERS C#8508
DRAWING DATE
9/19/2008
PERMIT SET
SCALE 1/8"=1'-0"
HVAC
DRAWING
1 OF 1
HVAC SYMBOLS
CEILING REGISTER
1 WAY THROW
FMC 603.15
RECTANGULAR
DUCTWORK
FMC SECTION 603
THERMOSTAT @ 60"
ABOVE FLOOR
FEC 13-613
CEILING REGISTER
2 WAY THROW
FMC 603.15
FLEXIBLE
DUCTWORK
FMC SECTION 603
WALL MOUNTED
HUMIDISTAT @ 60"
ABOVE FLOOR
CEILING REGISTER
3 WAY THROW
FMC 603.15
AIR DISTRIBUTION
BOXES FMC
SECTION 603
CEILING REGISTER
4 WAY THROW
FMC 603.15
RETURN AIR
PLENUM TRUNK
FMC SECTION 602
EQUIPMENT
ACCESS PANEL
FMC SECTION 306
CEILING REGISTER
CORNER THROW
FMC 603.15
SUPPLY AIR
PLENUM TRUNK
FMC SECTION 602
EXHAUST FAN
EF-1 or as NOTED
FMC SECTION 403
WALL REGISTER
2 WAY THROW
FMC 603.15
AIR VOLUME
CONTROL DAMPER
FMC 603.15
ZD
ZONE CONTROL
AIR DAMPER
FMC 303 -- 312
FLOOR REGISTER
2 WAY THROW
FMC 603.15
DUCT MOUNTED
FIRE DAMPER
FMC SECTION 607
BP
BYPASS AIR
DAMPER
FMC 303 -- 312
FLOOR GRILLE
FILTER RETURN
AIR FMC 603.15
CEILING GRILLE
FILTER RETURN
AIR FMC 603.15
8x4,4",13 CFM
M Toilet
M Bed
M Bath
10x6,5",77 CFM
10x6,5",77 CFM
8x4,4",43 CFM
Dining / Living
12x8,116 CFM
A
WYE
12x6,6",106 CFM
10x6,6",89 CFM
ABOVE CEILING
IN SEALED MECH
ROOM R-19 ISUL
14"
Foyer
Bed 4
AHU-1
10"
14"
14"
12x8,8",116 CFM
Powder
18x18 R/A
@ CHASE
-500 CFM
12"
12" BYPASS
BP
ZD ZD
8x4,4",31 CFM
12x12,7",-89 CFM
ACCESS TO
ATTIC
12x6,6",113 CFM
DUCTS DOWN
Lav
14"
CU-1
ON SLAB
8x4,4",24 CFM
Laundry
8x4,4",35 CFM
8x4,4",5 CFM
Bath 2
12x12,7",-99 CFM
CONDENSATE
DRAIN TO GRASS
FMC SECTION 307
WALL GRILLE
DIRECT T/ A
FMC 603.15
CONDENSATE
TO DRYWELL
FMC SECTION 307
TYPICAL
BRANCH
DUCT
CONDENSING UNIT
ON SLAB
FMC SECTIONS
303 -- 312
TYPICAL AIR
DEVICE
8x4
4"
32
Walk In Closet
VERTICAL AIR
HANDLER ON STAND
FMC SECTIONS
303 --- 312
EF = EXHAUST FAN
FPM = FEET PER MINUTE
MUA = MAKE UP AIR
O/A = OUTSIDE AIR
Bedroom
TYPICAL ROOM
SF = SUPPLY FAN
T/A = TRANSFER AIR
VTE = VENT TO EXTERIOR
ZD = ZONE DAMPER
1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS.
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING
IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES)
SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.
FIRST
FLOOR
10x6,6",91 CFM
SECOND
FLOOR
CEILING GRILLE
DUCTED T/A
FMC 603.15
12x12,7",-91 CFM
10x6,6",99 CFM
PACKAGE UNIT
ROOF MOUNTED
FMC SECTIONS
303 -- 312
ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.
12x8,116 CFM
Stair / Otb
PACKAGE UNIT
SLAB MOUNTED
FMC SECTIONS
303 -- 312
THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.
M Wic
10"
CONTROL /
REFRIGERANT
PIPING FMC 1101
DUCTLESS AIR
HANDLER
FMC SECTIONS
303 -- 312
HVAC NOTES
12x8,334 CFM
8x4,4",5 CFM
RANGE VENT
ROOF / WALL CAP
FMC 505 - 506
12x12,9",-215 CFM
12x6,6",106 CFM
WALL GRILLE
FILTER RETURN
AIR FMC 603.15
DUCT MOUNTED
SMOKE DETECTOR
FMC SECTION 606
DRYER VENT
ROOF / WALL
CAP FMC 504
HORIZONTAL AIR
HANDLER MOUNT
FROM STRUCTURE
FMC SECTIONS
303 --- 312
Bed2 3
Bed
AHU-1
2TEC3F48A
59.5X26X23.5
151
12.02X21.22
18.07X21.5
1600 / .40
1/2
0
1 / 60
208 / 240
7.2 / 9.6
50 / 60
CU-1
4
2TWR3048A
208/230/ 1 / 60
25 / 40
46.4X35.1X38.7
279
46,000
33,200
12,800
43,500
0.72
13 / 8.4
THERMOSTAT MODEL:
PROGRAM
FLOOR
FASTENER
FMC 301.13
RETURN DUCT
FMC 601
CONDENSING UNIT
FMC 303
WALL
* CEILING
GRADE
EQUIPMENT SLAB
REDUCER - BOX
W
W2
EF-1
NUTONE
690
EXHAUST
50
0.25
120/1/60
0.5
9X11X8
3
12X11
10
1,2
REFRIGERANT PIPING
+ CONTROL WIRING
FMC 1101
* FRESH
AIR
DUCT
FMC 401
13
13
18
N/A
17
17
18
N/A
C
D
21
21
18
N/A
13
13
18
17
17
18
21
21
18
*
*
*
1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS
North
PROJECT NAME: HDS Model Residence 1964 s
PROJECT ADDRESS:
PROJECT STATE, ZIP:
CONDITIONED SQ. FT.: 1991
CLASSIFICATION : New Residence
Designed By:
Neil Fimbel
HVAC Designs
813-885-2258
FL BERS R#884
DRAWING DATE
9/12/2008
Permit Set
SCALE 1/4"=1'-0"
HVAC
DRAWING
1 OF 1
HVAC SYMBOLS
Cooler
CEILING REGISTER
1 WAY THROW
FMC 603.15
RECTANGULAR
DUCTWORK
FMC SECTION 603
THERMOSTAT @ 60"
ABOVE FLOOR
FEC 13-613
CEILING REGISTER
2 WAY THROW
FMC 603.15
FLEXIBLE
DUCTWORK
FMC SECTION 603
WALL MOUNTED
HUMIDISTAT @ 60"
ABOVE FLOOR
CEILING REGISTER
3 WAY THROW
FMC 603.15
AIR DISTRIBUTION
BOXES FMC
SECTION 603
CEILING REGISTER
4 WAY THROW
FMC 603.15
RETURN AIR
PLENUM TRUNK
FMC SECTION 602
EQUIPMENT
ACCESS PANEL
FMC SECTION 306
CEILING REGISTER
CORNER THROW
FMC 603.15
SUPPLY AIR
PLENUM TRUNK
FMC SECTION 602
EXHAUST FAN
EF-1 or as NOTED
FMC SECTION 403
WALL REGISTER
2 WAY THROW
FMC 603.15
AIR VOLUME
CONTROL DAMPER
FMC 603.15
ZD
ZONE CONTROL
AIR DAMPER
FMC 303 -- 312
FLOOR REGISTER
2 WAY THROW
FMC 603.15
DUCT MOUNTED
FIRE DAMPER
FMC SECTION 607
BP
BYPASS AIR
DAMPER
FMC 303 -- 312
FLOOR GRILLE
FILTER RETURN
AIR FMC 603.15
CEILING GRILLE
FILTER RETURN
AIR FMC 603.15
CEILING GRILLE
DUCTED T/A
FMC 603.15
CONDENSATE
DRAIN TO GRASS
FMC SECTION 307
WALL GRILLE
DIRECT T/ A
FMC 603.15
CONDENSATE
TO DRYWELL
FMC SECTION 307
DUCTLESS AIR
HANDLER
FMC SECTIONS
303 -- 312
PACKAGE UNIT
SLAB MOUNTED
FMC SECTIONS
303 -- 312
PACKAGE UNIT
ROOF MOUNTED
FMC SECTIONS
303 -- 312
TYPICAL
BRANCH
DUCT
CONDENSING UNIT
ON SLAB
FMC SECTIONS
303 -- 312
8x4
4"
32
TYPICAL AIR
DEVICE
Walk In Closet
VERTICAL AIR
HANDLER ON STAND
FMC SECTIONS
303 --- 312
EF = EXHAUST FAN
FPM = FEET PER MINUTE
MUA = MAKE UP AIR
O/A = OUTSIDE AIR
Kitchen
RANGE VENT
ROOF / WALL CAP
FMC 505 - 506
CONTROL /
REFRIGERANT
PIPING FMC 1101
DUCT MOUNTED
SMOKE DETECTOR
FMC SECTION 606
DRYER VENT
ROOF / WALL
CAP FMC 504
WALL GRILLE
FILTER RETURN
AIR FMC 603.15
HORIZONTAL AIR
HANDLER MOUNT
FROM STRUCTURE
FMC SECTIONS
303 --- 312
Bedroom
TYPICAL ROOM
SF = SUPPLY FAN
T/A = TRANSFER AIR
VTE = VENT TO EXTERIOR
ZD = ZONE DAMPER
HVAC NOTES
22x22,10",320 CFM
22x22,10",320 CFM
THIS HVAC DDRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.
ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.
12x12
1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS.
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER.
12x12
24x12
RTU-1
ON ROOF
22x22,10",320 CFM
22x22,10",320 CFM
KITCHEN HOOD
BY OTHERS 380
CFM MUA BY
A/C EQUIPMENT
ROOM NAME
OCCUPANTS
DURATION
1
1
X
ZONE
COOLER ROOM
KITCHEN
X
ROOM NAME
0
5
X
OCCUPANTS
N/A
> 3 HRS
X
DURATION
78
1922
X
SUPPLY AIR CFM
0
1840
X
RETURN AIR CFM
0
380 CFM @ HOOD
X
EXHAUST AIR CFM
0
160
X
FRESH AIR CFM
2
2
X
RESTROOM
ORDER / CASHIER
X
0
9
X
N/A
VARIES
X
18
1582
X
0
1380
X
50 INTERMITTENT
0
X
0
220
X
BUILDING TOTALS
14
VARIES
3600
3220
380
CONDENSATE DRAIN
TO GUTTER / GRASS
TYPICAL OF 2
22x22,10",320 CFM
22x22,10",320 CFM
RTU-2
380
EXISTING
ON ROOF
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
RTU-1
RTU-2
UNIT MANUFACTURER:
TRANE
EXISTING
4
DOWNFLOW
37X45X70
37X45X70
682
669
17X15
17X15
23X14
23X14
2000 / .4
1600 / .4
160
220
UNIT WEIGHT:
CLASSIFICATION
Dining / Order
HOOD MUA
Kitchen / Prep
BUILDING TOTALS
OCCUPANTS
9
0
5
14
DURATION
1.00
1.00
1.00
ADJUSTED AIR
20
125
15
20x12
TOTAL AIR
180
125
75
20
0
15
380
Restroom
EF-1
VTE
8x4,4",18 CFM
UNIT VOLTAGE:
22x22, 16"
-1380 CFM
UNIT MCA:
UNIT MAX BREAKER:
HEATER KW:
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
HEATER MCA:
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
3/60
3/60
208/230
208/230
28.8
22.6
40
35
9/12
9/12
37.5/42.4
37.5/42.4
HEATER BREAKER:
45/45
40/45
62,400
49,800
47,300
39,400
15,100
10,400
40,944
40,944
0.76
0.79
COOLING EFFICIENCY:
13
13
THERMOSTAT MODEL:
T8411R1002
T8411R1002
SENS. HEAT %
THC043A3
DOWNFLOW
UNIT CONFIGURATION:
UNIT DIMEN H/W/D:
TIME
THC063A3
DUCT
CONNECTION
CURB
CONNECTION
ROOFTOP
EQUIPMENT
3/8 BOLT
@ 18" O.C.
MASTIC
SEAL
CURB
ROOF
DUCT
JOIST
EQUIPMENT
CONNECTION
1/2"
SCREWS
@ 8" O.C.
ROOFTOP
EQUIPMENT
CURB
3/8"
SCREWS
1/4" PLATE
OR ANGLE
@ 18"" O.C.
2" U CHANNEL X
1/4" THK
SPAN 3 JOISTS
ROOFTOP
EQUIPMENT
FMC 303
R/A
DUCT
FMC
601
S/A
DUCT
FMC
601
CURB
MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD
MECHANICALLY FASTEN AND SEAL DUCTS PER FMC SECTIONS 603 AND 604
MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOAD
18x12
FAN MARK:
MANUFACTURER:
NUTONE
MODEL NUMBER:
FAN TYPE:
690
EXHAUST
FAN CFM:
TOTAL PRESSURE:
FAN VOLTAGE:
0.5
9X11X8
North
120/1/60
FAN AMPERAGE:
DUCT OUTLET SIZE:
Order - Cashier
50
0.25
3
12X11
10
1,2
1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS
PROJECT NAME:
PROJECT ADDRESS:
PROJECT STATE, ZIP:
CONDITIONED SQ. FT.:
CLASSIFICATION :
Designed By:
Neil Fimbel
HVAC Designs
813-885-2258
FL BERS #884
DRAWING DATE
8/14/2008
Permit Set
SCALE 1/4"=1'-0"
HVAC
DRAWING
1 OF 1
HVAC SYMBOLS
ZONE
ROOM NAME
OCCUPANTS
DURATION
1
1
1
1
1
1
1
1
1
1
1
1
X
ZONE
Office
Exam
Exam
Reception
Restroom
Restroom
Exam
Consult
Exam
Exam
Lab
Work Stations
X
ROOM NAME
1
1
1
1
0
0
1
1
1
1
0
0
X
OCCUPANTS
> 3 HRS
VARIES
VARIES
> 3 HRS
N/A
N/A
VARIES
> 3 HRS
VARIES
VARIES
VARIES
VARIES
X
DURATION
256
147
261
304
38
31
94
37
64
64
39
665
X
SUPPLY AIR CFM
256
147
261
304
0
0
94
37 T/A
64
64
39 T/A
680
X
RETURN AIR CFM
0
0
0
0
90
90
0
0
0
0
0
0
X
EXHAUST AIR CFM
20
15
15
20
0
0
10
20
15
15
0
0
X
FRESH AIR CFM
CEILING REGISTER
1 WAY THROW
FMC 603.15
RECTANGULAR
DUCTWORK
FMC SECTION 603
CEILING REGISTER
2 WAY THROW
FMC 603.15
FLEXIBLE
DUCTWORK
FMC SECTION 603
CEILING REGISTER
3 WAY THROW
FMC 603.15
AIR DISTRIBUTION
BOXES FMC
SECTION 603
CEILING REGISTER
4 WAY THROW
FMC 603.15
RETURN AIR
PLENUM TRUNK
FMC SECTION 602
EQUIPMENT
ACCESS PANEL
FMC SECTION 306
2
2
2
2
2
X
ZONE
Break
Waiting
Reception
P Restroom
E Restroom
X
ROOM NAME
2
20
2
0
0
X
OCCUPANTS
VARIES
VARIES
> 3 HRS
N/A
N/A
X
DURATION
243
1389
335
10
23
X
SUPPLY AIR CFM
243
1292
335
0
0
X
RETURN AIR CFM
0
0
0
90
90
X
EXHAUST AIR CFM
15
75
40
0
0
X
FRESH AIR CFM
CEILING REGISTER
CORNER THROW
FMC 603.15
SUPPLY AIR
PLENUM TRUNK
FMC SECTION 602
EXHAUST FAN
EF-1 or as NOTED
FMC SECTION 403
WALL REGISTER
2 WAY THROW
FMC 603.15
AIR VOLUME
CONTROL DAMPER
FMC 603.15
ZD
ZONE CONTROL
AIR DAMPER
FMC 303 -- 312
3
3
3
3
3
3
3
3
3
X
ZONE
Office
Exam
Exam
Reception
Corridor
Exam
Exam
Restroom
Restroom
X
ROOM NAME
1
1
1
1
0
1
1
0
0
X
OCCUPANTS
> 3 HRS
VARIES
VARIES
> 3 HRS
N/A
VARIES
VARIES
N/A
N/A
X
DURATION
118
124
100
108
83
120
99
24
24
X
SUPPLY AIR CFM
118
124
100
119
0
120
99
0
0
X
RETURN AIR CFM
0
0
0
0
0
0
0
90
90
X
EXHAUST AIR CFM
20
20
20
20
0
20
20
0
0
X
FRESH AIR CFM
FLOOR REGISTER
2 WAY THROW
FMC 603.15
DUCT MOUNTED
FIRE DAMPER
FMC SECTION 607
BP
BYPASS AIR
DAMPER
FMC 303 -- 312
4
4
4
4
X
ZONE
Reception
Waiting
U Restroom
Storage
X
ROOM NAME
1
4
0
0
X
OCCUPANTS
> 3 HRS
VARIES
N/A
N/A
X
DURATION
253
514
21
12
X
SUPPLY AIR CFM
253
427
0
12 T/A
X
RETURN AIR CFM
0
0
90
0
X
EXHAUST AIR CFM
20
100
0
0
X
FRESH AIR CFM
5
5
5
5
5
5
5
Exam
Office
Corridor
Exam
Exam
Exam
Waiting
1
1
0
1
1
1
20
VARIES
> 3 HRS
N/A
VARIES
VARIES
VARIES
VARIES
89
130
257
101
89
105
1229
89
130
127
101
89
105
1229
0
0
0
0
0
0
0
15
20
0
15
15
15
50
68
VARIES
7600
6970
630
630
BUILDING TOTALS
FLOOR GRILLE
FILTER RETURN
AIR FMC 603.15
CEILING GRILLE
FILTER RETURN
AIR FMC 603.15
TIME
CLASSIFICATION
OCCUPANTS
DURATION
ADJUSTED AIR
TOTAL AIR
CFM / PERSON
PEAK
PEAK
PEAK
Office
Waiting
Exam Office
8
47
13
1.00
0.50
0.50
20
15
15
20
7.5
7.5
160
352.5
97.5
20
7.5
7.5
BUILDING TOTALS
68
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
CALCULATIONS BASED ON ASHRAE 62.1 - 2007 TABLE 6-1 - PROCEDURE PROVIDES VENTILATION FOR VARIABLE / INTERMITTENT OCCUPANTS
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
Exam
Exam
22x22,6",120 CFM
Reception
22x22,9",253
22x22,6",99 CFM
22x22,10",-253
22x22,7",-120
22x22,7",129 CFM
22x22,7",-99
22x22,6",89 CFM
Exam
22x22,10",307 CFM
22x22,14",-615
6x10
22x22,7",-89
Waiting
22x22,7",-105
22x22,5",82 CFM
Corridor
22x22,10",307 CFM
Exam
22x22,7",-101
22x22,6",100 CFM
RELOCATED TO
MEZZANINE
ABOVE
22x22,9",257
22x22,6",105 CFM
MAY CONFIGURE
EXISTING AHU
VERTICAL OR
HORIZONTAL
CU-3
ON SLAB
U Restroom
CU-4
8x4,4",21 CFM
12x8
14x12
10x12
8x4,4",24 CFM
ON SLAB
Exam
22x22,7",130 CFM
Restroom
22x22,14",-615
22x22,8",-127
22x22,12",-427
22x22,8",-130
Storage
Restroom
Office
8x4,4",24 CFM
22x22,7",-118
16x12
Office
22x22,7"-100
22x22,8",-124
22x22,6",101 CFM
Exam
20x12
CONTROL /
REFRIGERANT
PIPING FMC 1101
CEILING GRILLE
DUCTED T/A
FMC 603.15
CONDENSATE
DRAIN TO GRASS
FMC SECTION 307
WALL GRILLE
DIRECT T/ A
FMC 603.15
CONDENSATE
TO DRYWELL
FMC SECTION 307
CU-5
22x22,6",108 CFM
22x22,6",118 CFM
14x14
Reception
Exam
Consult
22x22,6",93 CFM
Exam
22x22,8",-119
22x22,4",37 CFM
22x22,5",64 CFM
EXISTING ON
MEZZANINE
ABOVE
EXISTING ON
MEZZANINE
ABOVE
Exam
22x22,5",64 CFM
P Restroom
10x10
8x4,4",31 CFM
22x22, 14",-680
Work Stations
14x12
22x22,10",332 CFM
Waiting
Restroom
CU-2
Restroom
ON SLAB
AHU-1
ON STAND
8x4,4",38 CFM
22x22,10",335 CFM
22x22,14",-646
22x22,10",332 CFM
24x12
111
12.02X19.22
19.5X18.07
2000 / .70
1
800 / .60
1/4
120 / 120
UNIT VOLTAGE:
HEATER KW:
*
*
*
*
HEATER BREAKER:
CONDENSER MARK:
CU-1,2,5
CU-3,4
EXISTING
*
EXISTING
*
*
46.4X35.1X38.7
*
37.2X26.7X30
UNIT WEIGHT:
TOTAL COOLING BTUH:
269
58,000
175
22,800
40,000
16,600
18,000
6,200
34,120
17,060
0.69
13
0.73
13
SENSIBLE HEAT %
SEER:
Reception
22x22,14",-646
22x22,10",-261
22x22,10", -256
TYPICAL ROOM
SF = SUPPLY FAN
T/A = TRANSFER AIR
VTE = VENT TO EXTERIOR
ZD = ZONE DAMPER
* FRESH
AIR DUCT
FMC 401
SUPPLY
AIR DUCT
FMC 601
* CEILING
REFRIGERANT PIPING
+ CONTROL WIRING
FMC 1101
* FRESH
AIR
DUCT
FMC 401
AIR HANDLER
FMC 303
* RETURN AIR
RISER DUCT
FMC 601
AIR HANDLER
STAND
REFRIGERANT
PIPING
+ CONTROL
WIRING
FMC 1101
CONDENSATE
DRAIN
FMC 307
FLOOR
* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN
DRAWING FOR EXACT CONFIGURATION.
RETURN DUCT
FMC 601
* CEILING
VERTICAL AIR
HANDLER DETAIL
PIPE COVER - MAY MOUNT INTERIOR
REFRIGERANT PIPING + CONTROL WIRING
FMC 1101 - MAY ALSO ROUTE BELOW SLAB
CONDENSING UNIT
FMC 303
WALL
FLOOR
FASTENER
FMC 301.13
GRADE
EQUIPMENT SLAB
22x22,10",347 CFM
22x22,10",347 CFM
22x22,9",261 CFM
Exam
Reception
22x22,10",304 CFM
EF-1
NUTONE
FAN TYPE:
QT-80
EXHAUST
FAN CFM:
90
MODEL NUMBER:
Exam
Bedroom
EF = EXHAUST FAN
FPM = FEET PER MINUTE
MUA = MAKE UP AIR
O/A = OUTSIDE AIR
= AIRFLOW CFM
ADJUSTMENTS
22x22,8",-147
Office
VERTICAL AIR
HANDLER ON STAND
FMC SECTIONS
303 --- 312
22x22,10",347 CFM
22x22,10",347 CFM
12x14
22x22,7",146 CFM
Walk In Closet
22x22,10", -304
22x22,9",258 CFM
8x4
4"
32
TYPICAL AIR
DEVICE
THERMOSTAT MODEL:
T8411R1002
T8411R1002
NOTES: * EQUIPMENT IS EXISTING,SEE NAME PLATE
20x12
20x14
(TYPICAL x7)
6" FRESH AIR
DUCT VTE
MAY CONFIGURE
EXISTING AHU
VERTICAL OR
HORIZONTAL VERIFY EXISTING
AHU TYPE
24x12
22x22,10",-335
12x12
CU-1
155
12.02X21.22
18.07X21.5
22"
ON SLAB
44.5X24X23.5
22x22,6",-64
18x12
22x22,7",-94
(TYPICAL x7)
22x22,6",-64
EXISTING
59.5X26X23.5
AHU-3,4
EXISTING
UNIT WEIGHT:
E Restroom
8x4,4",10 CFM
AHU-1,2,5
22x22,9",243 CFM
VTE
TYPICAL
BRANCH
DUCT
CONDENSING UNIT
ON SLAB
FMC SECTIONS
303 -- 312
1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS.
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING
IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES)
SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.
RELOCATED
ABOVE
CEILING
EF-1
Waiting
Corridor
18x16
AHU-2
PACKAGE UNIT
ROOF MOUNTED
FMC SECTIONS
303 -- 312
Lab
8x4,4",39 CFM
PACKAGE UNIT
SLAB MOUNTED
FMC SECTIONS
303 -- 312
ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT INTERIOR DOOR = ONLY 30 CFM OF RELIEF AIR.
22x22,10",-243
DUCTLESS AIR
HANDLER
FMC SECTIONS
303 -- 312
THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
HVAC SYMBOL, HVAC CONTRACTOR MUST REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.
Break
22x22,10",307 CFM
22x22,10",307 CFM
AHU-5
DUCT MOUNTED
SMOKE DETECTOR
FMC SECTION 606
HVAC NOTES
22x22,7",-89
ON SLAB
AHU-4
HORIZONTAL AIR
HANDLER MOUNT
FROM STRUCTURE
FMC SECTIONS
303 --- 312
22x22,6",89 CFM
22x22,7",129 CFM
MAY CONFIGURE
EXISTING AHU
VERTICAL OR
HORIZONTAL
8x4,4",12 CFM
14x16
22x22,7",124 CFM
12x16
22x22,9",257
24x12
AHU-3
Exam
10x12
8x10
12x10
Exam
WALL MOUNTED
HUMIDISTAT @ 60"
ABOVE FLOOR
RANGE VENT
ROOF / WALL CAP
FMC 505 - 506
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
CALCULATIONS BASED ON ASHRAE 62.1 - 2007 TABLE 6-1 - PROCEDURE PROVIDES VENTILATION FOR VARIABLE / INTERMITTENT OCCUPANTS
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
THERMOSTAT @ 60"
ABOVE FLOOR
FEC 13-613
DRYER VENT
ROOF / WALL
CAP FMC 504
WALL GRILLE
FILTER RETURN
AIR FMC 603.15
TOTAL PRESSURE:
FAN VOLTAGE:
FAN AMPERAGE:
FAN DIMEN LWH:
DUCT OUTLET SIZE:
DUCT INLET SIZE:
FAN WEIGHT:
NOTES:
.2
120/1/60
.7
9X9X6
4
10X10
12
1,2
1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS
North
x
Designed By:
Neil Fimbel
HVAC Designs
813-885-2258
FL BERS R#884
FL BERS C#959
DRAWING DATE
9/28/2008
PERMIT SET
SCALE 1/8"=1'-0"
HVAC
DRAWING
1 OF 1
HVAC SYMBOLS
OPEN PARKING
10.00
% OF OPENING
GROSS PERIMETER
RESULT
54
597
PASSES
3280
BUILDING TOTALS
CEILING REGISTER
1 WAY THROW
FMC 603.15
RECTANGULAR
DUCTWORK
FMC SECTION 603
THERMOSTAT @ 60"
ABOVE FLOOR
FEC 13-613
CEILING REGISTER
2 WAY THROW
FMC 603.15
FLEXIBLE
DUCTWORK
FMC SECTION 603
WALL MOUNTED
HUMIDISTAT @ 60"
ABOVE FLOOR
CEILING REGISTER
3 WAY THROW
FMC 603.15
AIR DISTRIBUTION
BOXES FMC
SECTION 603
CEILING REGISTER
4 WAY THROW
FMC 603.15
RETURN AIR
PLENUM TRUNK
FMC SECTION 602
EQUIPMENT
ACCESS PANEL
FMC SECTION 306
CEILING REGISTER
CORNER THROW
FMC 603.15
SUPPLY AIR
PLENUM TRUNK
FMC SECTION 602
EXHAUST FAN
EF-1 or as NOTED
FMC SECTION 403
WALL REGISTER
2 WAY THROW
FMC 603.15
AIR VOLUME
CONTROL DAMPER
FMC 603.15
ZD
ZONE CONTROL
AIR DAMPER
FMC 303 -- 312
FLOOR REGISTER
2 WAY THROW
FMC 603.15
DUCT MOUNTED
FIRE DAMPER
FMC SECTION 607
BP
BYPASS AIR
DAMPER
FMC 303 -- 312
FLOOR GRILLE
FILTER RETURN
AIR FMC 603.15
DRYER VENT
ROOF / WALL
CAP FMC 504
RANGE VENT
ROOF / WALL CAP
FMC 505 - 506
CEILING GRILLE
FILTER RETURN
AIR FMC 603.15
597
OPENINGS ARE UNIFORMLY DISTRIBUTED ON ALL 4 WALLS, THE OPENING AREA EXCEEDS THE MINIMUM OF 20% OPENING TO PERIMETER WALL AREA.
CALCULATIONS BASED ON THE 2004 + SUPPLEMENTS FLORIDA MECHANICAL CODE SECTION 403.1, 403.3 AND FLORIDA BUILDING CODE 406.3.3.1
CONTROL /
REFRIGERANT
PIPING FMC 1101
WALL GRILLE
FILTER RETURN
AIR FMC 603.15
HORIZONTAL AIR
HANDLER MOUNT
FROM STRUCTURE
FMC SECTIONS
303 --- 312
DUCT MOUNTED
SMOKE DETECTOR
FMC SECTION 606
DUCTLESS AIR
HANDLER
FMC SECTIONS
303 -- 312
PACKAGE UNIT
SLAB MOUNTED
FMC SECTIONS
303 -- 312
PACKAGE UNIT
ROOF MOUNTED
FMC SECTIONS
303 -- 312
CONDENSING UNIT
ON SLAB
FMC SECTIONS
303 -- 312
TYPICAL
BRANCH
DUCT
TYPICAL AIR
DEVICE
Walk In Closet
CEILING GRILLE
DUCTED T/ A
FMC 603.15
CONDENSATE
DRAIN TO GRASS
FMC SECTION 307
WALL GRILLE
DIRECT T/ A
FMC 603.15
CONDENSATE
TO DRYWELL
FMC SECTION 307
AHU-1
20x18
10x12
12x12,8",-105 CFM
22x22,16",-895 CFM
Lobby
22x22,9",250 CFM
EQUIPMENT
CONNECTION
CURB
CONNECTION
CURB
3/8 BOLT
@ 18" O.C.
ROOFTOP
EQUIPMENT
ROOF
REFRIGERANT PIPING
+ CONTROL WIRING
FMC 1101
RETURN DUCT
FMC 601
JOIST
CURB
CONNECT TO
TRUSS
MEMBER
AIR HANDLER
FMC 303
* CEILING
3/8"
SCREWS
1/4" PLATE
OR ANGLE
@ 18""
O.C.
TRANE EQUIPMENT
AIR HANDLER MARK:
AHU-1
MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD
MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOAD
12.02X19.22
18.07X19.5
1000 / .40
1/3
105
1 / 60
UNIT VOLTAGE:
HEATER KW:
208 / 240
3.6 / 4.8
HEATER BREAKER:
25 / 30
CONDENSER MARK:
CU-1
ROOM NAME
OCCUPANTS
DURATION
1
X
LOBBY
X
14
X
0.5
X
1000
X
895
X
105
X
105
X
14
0.5
1000
895
105
105
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
TIME
CLASSIFICATION
OCCUPANTS
DURATION
ADJUSTED AIR
TOTAL AIR
CFM / SQ FOOT
PEAK
Reception / Wait
14
0.50
15
7.5
105
7.5
105
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
2.5
2TTR3030A
208/230/ 1 / 60
13 / 20
38X30.1X33
UNIT WEIGHT:
TOTAL COOLING BTUH:
198
27,600
20,400
7,200
17,060
SENSIBLE HEAT %
SEER:
46.5X24X23.5
125
2TEC3F30A
CURB
SF = SUPPLY FAN
T/A = TRANSFER AIR
VTE = VENT TO EXTERIOR
ZD = ZONE DAMPER
1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS.
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING
IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES)
SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.
THIS DESIGN IS FOR PEAK LOAD CONDITIONS ONLY, CONSIDER USING STAGED COOLING EQUIPMENT OR STAND ALONE DEHUMIDIFICATION FOR PART LOAD.
FIRST FLOOR
22x22,9",250 CFM
TYPICAL ROOM
ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.
22x22,9",250 CFM
* FRESH
AIR
DUCT
FMC 401
= AIRFLOW CFM
ADJUSTMENTS
THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.
ON ROOF
ABOVE
20x12
Bedroom
EF = EXHAUST FAN
FPM = FEET PER MINUTE
MUA = MAKE UP AIR
O/A = OUTSIDE AIR
HVAC NOTES
CU-1
22x22,9",250 CFM
ABOVE
CEILING
VERTICAL AIR
HANDLER ON STAND
FMC SECTIONS
303 --- 312
8x4
4"
32
THERMOSTAT MODEL:
0.74
13
T8411R1002
North
PROJECT NAME:
PROJECT ADDRESS:
PROJECT STATE, ZIP:
CONDITIONED SQ. FT.:
CLASSIFICATION :
x
Designed By:
Neil Fimbel
HVAC Designs
813-885-2258
FLORIDA BERS
R#884 C#959
DRAWING DATE
1/31/2009
PERMIT SET
SCALE 1/8"=1'-0"
HVAC
DRAWING
1 OF 3
PEAK
PEAK
PEAK
Conference
Office
Reception / Wait
10
56
23
VARIES
1.00
0.50
ADJUSTED AIR
TOTAL AIR
CFM / SQ FOOT
19.75
20
7.5
197.5
1120
172.5
19.75
20
7.5
20
20
15
89
AIR HANDLER
FMC 303
RETURN DUCT
FMC 601
1490
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
* CEILING
TYPICAL
PIPE CHASE
TO ROOF
10x6,5",63 CFM
14x12
Dr Off 1
22x22,5",63 CFM
18x20
18x21
Corridor
10x12
18x12
18x14
SR-82,8",165 CFM
PIPING UP FROM
LOBBY BELOW
CU-7
ON ROOF
CURB
ABOVE 3rd
FLOOR
22x22,8",165 CFM
22x22,8",165 CFM
Recep / Wait
8x4,4",51 CFM
16x10
22x22,8",165 CFM
22x22,7",-78 CFM
8x4,4",20 CFM
10x6,5",66 CFM
EF-2
Infusion
22x22,14",-640 CFM
22x22,9",213 CFM
22x22,9",213 CFM
SECOND FLOOR
EF-1
8x4,4",43 CFM
VTE
Restroom
AHU-8
18x20
22x22,8",198 CFM
EF-2
VTE
TYPICAL
UNLESS
NOTED
8x4,4",13 CFM
ABOVE
CEILING
127
CFM
T/A
20x12
22x22,8",198 CFM
22x22,8",198 CFM
12x12
12x8
8x12
22x22,8",198 CFM
22x22,16",-1060 CFM
CU-8
ON ROOF
CURB
ABOVE 3rd
FLOOR
Restroom
8x4,4",12 CFM
22x22,8",198 CFM
Unit 2 F
18x20
22x22,8",198 CFM
AHU-9
22x22,9",231 CFM
ABOVE
CEILING
20x12
148
CFM
T/A
22x22,9",231 CFM
22x22,9",231 CFM
16x12
10x12
10x12
22x22,16",-1240 CFM
22x22,9",231 CFM
22x22,9",231 CFM
CU-9
ON ROOF
CURB
ABOVE 3rd
FLOOR
Restroom
107
CFM
T/A
Unit 2 G
AHU-10
18x20
22x22,9",231 CFM
ABOVE
CEILING
8x4,4",13 CFM
20x12
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM
12x12
12x8
8x12
22x22,8",198 CFM
22x22,16",-1080 CFM
CU-10
22x22,8",198 CFM
ON ROOF
CURB
ABOVE 3rd
FLOOR
22x22,8",198 CFM
North
FAN AMPERAGE:
1.0
.7
14X10X9
9X9X6
3.25X10 TO 7
15X11
10X10
14
12
ON ROOF
CURB
ABOVE 3rd
FLOOR
8x4,4",14 CFM
18x20
Unit 2 H
12x8
12x8
12x12
CEILING REGISTER
2 WAY THROW
FMC 603.15
FLEXIBLE
DUCTWORK
FMC SECTION 603
WALL MOUNTED
HUMIDISTAT @ 60"
ABOVE FLOOR
CEILING REGISTER
3 WAY THROW
FMC 603.15
AIR DISTRIBUTION
BOXES FMC
SECTION 603
CEILING REGISTER
4 WAY THROW
FMC 603.15
RETURN AIR
PLENUM TRUNK
FMC SECTION 602
EQUIPMENT
ACCESS PANEL
FMC SECTION 306
CEILING REGISTER
CORNER THROW
FMC 603.15
SUPPLY AIR
PLENUM TRUNK
FMC SECTION 602
EXHAUST FAN
EF-1 or as NOTED
FMC SECTION 403
WALL REGISTER
2 WAY THROW
FMC 603.15
AIR VOLUME
CONTROL DAMPER
FMC 603.15
ZD
ZONE CONTROL
AIR DAMPER
FMC 303 -- 312
FLOOR REGISTER
2 WAY THROW
FMC 603.15
DUCT MOUNTED
FIRE DAMPER
FMC SECTION 607
BP
BYPASS AIR
DAMPER
FMC 303 -- 312
FLOOR GRILLE
FILTER RETURN
AIR FMC 603.15
DRYER VENT
ROOF / WALL
CAP FMC 504
RANGE VENT
ROOF / WALL CAP
FMC 505 - 506
1,2
CU-1
VTE
TYPICAL
UNLESS
NOTED
1,2
20x12
CEILING GRILLE
FILTER RETURN
AIR FMC 603.15
EQUIPMENT
CONNECTION
CURB
CONNECTION
TYPICAL
CURB
AHU-1
3/8 BOLT
@ 18" O.C.
ROOFTOP
EQUIPMENT
ROOF
ABOVE
CEILING
JOIST
CURB
22x22,8",198 CFM
22x22,8",198 CFM
ROOFTOP
EQUIPMENT
FMC 303
HORIZONTAL AIR
HANDLER MOUNT
FROM STRUCTURE
FMC SECTIONS
303 --- 312
DUCT MOUNTED
SMOKE DETECTOR
FMC SECTION 606
DUCTLESS AIR
HANDLER
FMC SECTIONS
303 -- 312
PACKAGE UNIT
SLAB MOUNTED
FMC SECTIONS
303 -- 312
PACKAGE UNIT
ROOF MOUNTED
FMC SECTIONS
303 -- 312
CONDENSING UNIT
ON SLAB
FMC SECTIONS
303 -- 312
CONTROL /
REFRIGERANT
PIPING FMC 1101
TYPICAL AIR
DEVICE
Walk In Closet
CEILING GRILLE
DUCTED T/ A
FMC 603.15
CONDENSATE
DRAIN TO GRASS
FMC SECTION 307
WALL GRILLE
DIRECT T/ A
FMC 603.15
CONDENSATE
TO DRYWELL
FMC SECTION 307
22x22,8",164 CFM
22x22,8",164 CFM
WALL GRILLE
FILTER RETURN
AIR FMC 603.15
3/8"
SCREWS
1/4"
PLATE
OR
ANGLE
@ 18""
O.C.
22x22,8",164 CFM
22x22,8",164 CFM
22x22,8",198 CFM
22x22,8",198 CFM
Unit 2 B
22x22,8",164 CFM
22x22,8",164 CFM
VERTICAL AIR
HANDLER ON STAND
FMC SECTIONS
303 --- 312
Bedroom
TYPICAL ROOM
EF = EXHAUST FAN
FPM = FEET PER MINUTE
MUA = MAKE UP AIR
O/A = OUTSIDE AIR
8x4
4"
32
SF = SUPPLY FAN
T/A = TRANSFER AIR
VTE = VENT TO EXTERIOR
ZD = ZONE DAMPER
Unit 2 A
HVAC NOTES
VTE
ZONE
ROOM NAME
OCCUPANTS
DURATION
1
1
X
ZONE
Unit 2 A
Restroom
X
ROOM NAME
6
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
986
14
X
SUPPLY AIR CFM
880
0
X
RETURN AIR CFM
0
120
X
EXHAUST AIR CFM
120
0
X
FRESH AIR CFM
2
2
X
ZONE
Unit 2 B
Restroom
X
ROOM NAME
8
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
1187
13
X
SUPPLY AIR CFM
1040
0
X
RETURN AIR CFM
0
160
X
EXHAUST AIR CFM
160
0
X
FRESH AIR CFM
3
3
X
ZONE
Unit 2 C
Restroom
X
ROOM NAME
7
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
986
14
X
SUPPLY AIR CFM
860
0
X
RETURN AIR CFM
0
120
X
EXHAUST AIR CFM
120
0
X
FRESH AIR CFM
4
4
4
4
4
4
4
4
4
4
4
X
ZONE
Server
Dr Off 4
Dr Off 3
Restroom
Dr Off 2
Restroom
Dr Off 1
Admin
Billing
F Office
Corridor
X
ROOM NAME
0
1
1
0
1
0
1
1
1
0
0
X
OCCUPANTS
N/A
> 3 HRS
> 3 HRS
N/A
> 3 HRS
N/A
> 3 HRS
> 3 HRS
> 3 HRS
N/A
N/A
X
DURATION
100
75
75
19
184
63
195
90
278
18
103
X
SUPPLY AIR CFM
100 T/A
75
75
0
184
0
195
90
278
0
183
X
RETURN AIR CFM
0
0
0
96
0
96
0
0
0
0
0
X
EXHAUST AIR CFM
0
20
20
0
20
0
20
20
20
0
0
X
FRESH AIR CFM
5
5
5
5
X
ZONE
Lunch
Restroom
Conference
Storage
X
ROOM NAME
4
0
10
0
X
OCCUPANTS
< 3 HRS
N/A
< 3 HRS
N/A
X
DURATION
307
14
868
11
X
SUPPLY AIR CFM
192
0
868
0
X
RETURN AIR CFM
0
95
0
0
X
EXHAUST AIR CFM
40
0
120
0
X
FRESH AIR CFM
6
6
6
6
6
X
ZONE
Files
Storage
Recep / Wait
Restroom
Phone
X
ROOM NAME
0
0
10
0
0
X
OCCUPANTS
N/A
N/A
VARIES
N/A
N/A
X
DURATION
28
28
825
54
65
X
SUPPLY AIR CFM
0
0
860
0
0
X
RETURN AIR CFM
0
0
0
95
0
X
EXHAUST AIR CFM
0
0
140
0
0
X
FRESH AIR CFM
7
7
7
7
7
7
7
7
7
7
7
7
7
7
X
ZONE
Infusion
Restroom
Pharmacy
Cold
P Infusion
Restroom
Exam 2
Exam 1
Lab
Restroom
Exam 3
Exam 4
Exam 5
Corridor
X
ROOM NAME
9
0
1
0
1
0
1
1
1
0
1
1
1
0
X
OCCUPANTS
VARIES
N/A
> 3 HRS
N/A
> 3 HRS
N/A
> 3 HRS
> 3 HRS
> 3 HRS
N/A
> 3 HRS
> 3 HRS
> 3 HRS
N/A
X
DURATION
640
43
249
51
66
20
223
63
92
92
252
63
65
81
X
SUPPLY AIR CFM
640
0
300
0
66
0
223
63
0
0
252
63
65
78
X
RETURN AIR CFM
0
96
0
0
0
96
0
0
0
96
0
0
0
0
X
EXHAUST AIR CFM
90
0
20
0
20
0
20
20
20
0
20
20
20
0
X
FRESH AIR CFM
8
8
X
ZONE
Unit 2 F
Restroom
X
ROOM NAME
7
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
1187
13
X
SUPPLY AIR CFM
1060
0
X
RETURN AIR CFM
0
140
X
EXHAUST AIR CFM
140
0
X
FRESH AIR CFM
9
9
X
ZONE
Unit 2 F
Restroom
X
ROOM NAME
8
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
1388
12
X
SUPPLY AIR CFM
1240
0
X
RETURN AIR CFM
0
160
X
EXHAUST AIR CFM
160
0
X
FRESH AIR CFM
10
10
Unit 2 F
Restroom
VTE
Cold
Restroom
22x22,8",164 CFM
EF-2
8x4,4",54 CFM
12x14
16x12
Lab
22x22,9",213 CFM
120/1/60
22x22,5",65 CFM
Restroom
22x22,5",63 CFM
Pharmacy
120/1/60
THERMOSTAT @ 60"
ABOVE FLOOR
FEC 13-613
22x22,14",-880 CFM
Unit 2 C
22x22,5",81 CFM
Restroom
P Infusion
.25
22x22,8",165 CFM
22x22,6",91 CFM
22x22,9",249 CFM
Phone
22x22,4",28 CFM
12x12,6",-66 CFM
TOTAL PRESSURE:
.25
CONNECT TO
TRUSS
MEMBER
22x22,8",164 CFM
22x22,14",-860 CFM
Exam 2
22x22,10",-300 CFM
92.85
Dr Off 4
Restroom
22x22,9",223 CFM
140
RECTANGULAR
DUCTWORK
FMC SECTION 603
22x22,5",75 CFM
Files
ABOVE
CEILING
22x22,6",-63 CFM
FAN CFM:
22x22,5",75 CFM
ABOVE
CEILING
AHU-7
VTE
EXHAUST
CURB
Exam 3
22x22,6",-63 CFM
EXHAUST
CEILING REGISTER
1 WAY THROW
FMC 603.15
1 = VENT TO EXTERIOR
EF-1
22x22,16",-1040 CFM
ABOVE
CEILING
ON ROOF
CURB
ABOVE 3rd
FLOOR
AHU-6
20x12
21x12
FAN TYPE:
F Office
Server
8x12
22x22,10",-252 CFM
20x12
AHU-2
ABOVE
CEILING
Dr Off 3
ON ROOF
CURB
ABOVE 3rd
FLOOR
8x4,4",13 CFM
18x20
Restroom
CU-2
8x12
18x20
22x22,6",-65 CFM
Exam 4
QT-110
NOTES:
106
CFM
T/A
22x22,16",-860 CFM
AHU-3
CU-5
8x4,4",19 CFM
10x6,6",100 CFM
TYPICAL
12x12,9" T/A
DUCT
22x22,6",-75 CFM
22x22,4",28 CFM
22x22,9",252 CFM
Exam 1
ON ROOF
CURB
ABOVE 3rd
FLOOR
Storage
Exam 5
20x12
8x12
12x12 T/A
HIGH WALL
22x22,5",65 CFM
18x20
CU-6
Corridor
VTE
ON ROOF
CURB
ABOVE 3rd
FLOOR
22x22,6",-75 CFM
22x22,6",103 CFM
EF-2
22x22,10",-223 CFM
Restroom
8x4,4",14 CFM
22x22,9",-183 CFM
8x12
20x12
AHU-5
ABOVE
CEILING
10x6,6",92 CFM
147
CFM
T/A
CU-3
Restroom
22x22,7",-90 CFM
Restroom
EF-2
126
CFM
T/A
VTE
12x12
Billing
QT-150
FAN WEIGHT:
8x4,4",19 CFM
22x22,9",-192 CFM
MODEL NUMBER:
22x22,8",164 CFM
22x22,8",164 CFM
22x22,8",198 CFM
14x12
16x12
22x22,6",90 CFM
Restroom
EF-2
ABOVE
CEILING
8x4,4",11 CFM
8x4,4",14 CFM
22x22,8",198 CFM
22x22,8",164 CFM
CU-4
ON ROOF
CURB
ABOVE 3rd
FLOOR
AHU-4
22x22,10",289 CFM
10' SEPERATION
22x22,9",-184 CFM
12x12
Admin
22x22,14",-868 CFM
22x22,8",164 CFM
18x20
22x22,8",195 CFM
Storage
NUTONE
22x22,10",278 CFM
NUTONE
10' SEPERATION
22x22,8",184 CFM
VTE
22x22,10",289 CFM
MANUFACTURER:
FAN VOLTAGE:
EF-2
22x22,10",307 CFM
22x22,10",289 CFM
TYPICAL
EXHAUST AIR EQUAL TO FRESH AIR
10' SEPERATION REQUIRED
Dr Off 2
Lunch
22x22,12",-278 CFM
TYPICAL
12x12 LOUVER + 9"
FRESH AIR INTAKE
SEE AIR BALANCE
SCHEDULE FOR CFM
Restroom
Conference
EF-2
22x22,9",-195 CFM
EF-1
FAN MARK:
12x8
OCCUPANTS
HVAC SYMBOLS
12x12
CLASSIFICATION
8x12
TIME
REFRIGERANT PIPING +
CONTROL WIRING FMC
1101
* FRESH
AIR
DUCT
FMC 401
6
0
89
> 3 HRS
N/A
VARIES
1187
13
12400
1080
0
10910
0
120
1490
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.
1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS.
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING
IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES)
SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.
THIS DESIGN IS FOR PEAK LOAD CONDITIONS ONLY, CONSIDER USING STAGED COOLING EQUIPMENT OR STAND ALONE DEHUMIDIFICATION FOR PART LOAD.
AHU-2,4,5,8,10
AHU-7
AHU-9
2TEC3F30A
2TEC3F36A
2TEC3F60A
2TEC3F42A
46.5X24X23.5
46.5X24X23.5
59.5X26X23.5
53.25X26X23.5
125
125
155
150
12.02X19.22
12.02X19.22
12.02X21.22
12.02X21.22
18.07X19.5
18.07X19.5
18.07X21.5
18.07X21.5
1000 / .40
1200 / .40
2000 / .40
1400 / .40
1/3
1/3
1/2
120/140/140
160/120/140/140/120
250
160
1 / 60
1 / 60
1 / 60
1 / 60
UNIT VOLTAGE:
208 / 240
208 / 240
208 / 240
208 / 240
HEATER KW:
3.6 / 4.8
3.6 / 4.8
7.2 / 9.6
3.6 / 4.8
HEATER BREAKER:
25 / 30
25 / 30
50 / 60
25 / 30
CONDENSER MARK:
CU-1,3,6
CU-2,4,5,8,10
CU-7
CU-9
2.5
3.5
2TTR3030A
2TTR3036A
2TTR3060A
2TTR3042A
208/230/ 1 / 60
208/230/ 1 / 60
208/230/ 1 / 60
208/230/ 1 / 60
13 / 20
18 / 30
32 / 50
21 / 35
38X30.1X33
38X30.1X33
46.4X35.1X38.7
38.4X35.1X38.7
198
194
269
250
27,600
34,200
58,000
41,000
20,400
25,400
40,000
29,800
7,200
8,800
18,000
11,200
17,060
17,060
34,120
17,060
0.74
0.74
0.69
0.73
13
13
13.5
13.5
T8411R1002
T8411R1002
T8411R1002
T8411R1002
SENSIBLE HEAT %
SEER:
THERMOSTAT MODEL:
120
0
1490
PROJECT NAME:
PROJECT ADDRESS:
PROJECT STATE, ZIP:
CONDITIONED SQ. FT.:
CLASSIFICATION :
Designed By:
Neil Fimbel
HVAC Designs
813-885-2258
FLORIDA BERS
R#884 C#959
DRAWING DATE
1/31/2009
PERMIT SET
SCALE 1/8"=1'-0"
HVAC
DRAWING
2 OF 3
HVAC SYMBOLS
TYPICAL
EXHAUST AIR EQUAL TO FRESH AIR
Unit 3 Dwest
Unit 3 Deast
22x22,8",197 CFM
22x22,8",197 CFM
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM
22x22,9",267 CFM
22x22,9",267 CFM
125
CFM
T/A
22x22,18",-1400 CFM
Restroom
TYPICAL
12x12,9"
T/A DUCT
148
CFM
T/A
12x12
22x22,18",-1400 CFM
12x12
16x14
8x14
12x14
22x22,9",267 CFM
22x22,16",-1060 CFM
22x22,9",267 CFM
EF-1
RTU-3
ON ROOF
ON ROOF
22x14
8x4,4",12 CFM
RTU-4
RTU-2
ON ROOF
22x14
22x14
106
CFM
T/A
Restroom
TYPICAL
UNLESS
NOTED
WALL MOUNTED
HUMIDISTAT @ 60"
ABOVE FLOOR
CEILING REGISTER
3 WAY THROW
FMC 603.15
AIR DISTRIBUTION
BOXES FMC
SECTION 603
CEILING REGISTER
4 WAY THROW
FMC 603.15
RETURN AIR
PLENUM TRUNK
FMC SECTION 602
EQUIPMENT
ACCESS PANEL
FMC SECTION 306
CEILING REGISTER
CORNER THROW
FMC 603.15
SUPPLY AIR
PLENUM TRUNK
FMC SECTION 602
EXHAUST FAN
EF-1 or as NOTED
FMC SECTION 403
WALL REGISTER
2 WAY THROW
FMC 603.15
AIR VOLUME
CONTROL DAMPER
FMC 603.15
ZD
ZONE CONTROL
AIR DAMPER
FMC 303 -- 312
FLOOR REGISTER
2 WAY THROW
FMC 603.15
DUCT MOUNTED
FIRE DAMPER
FMC SECTION 607
BP
BYPASS AIR
DAMPER
FMC 303 -- 312
FLOOR GRILLE
FILTER RETURN
AIR FMC 603.15
DRYER VENT
ROOF / WALL
CAP FMC 504
RANGE VENT
ROOF / WALL CAP
FMC 505 - 506
RTU-1
ON ROOF
22x14
22x14
ON ROOF
22x22,8",198 CFM
HORIZONTAL AIR
HANDLER MOUNT
FROM STRUCTURE
FMC SECTIONS
303 --- 312
DUCT MOUNTED
SMOKE DETECTOR
FMC SECTION 606
DUCTLESS AIR
HANDLER
FMC SECTIONS
303 -- 312
PACKAGE UNIT
SLAB MOUNTED
FMC SECTIONS
303 -- 312
16x14
22x22,198 CFM
22x22,8",197 CFM
22x14
22x22,8",198 CFM
Unit 3 B
Unit 3 C
22x22,9",267 CFM
22x22,9",267 CFM
ON ROOF
ZONE
ROOM NAME
OCCUPANTS
DURATION
1
1
X
ZONE
Unit 3 A
Restroom
X
ROOM NAME
6
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
1186
14
X
SUPPLY AIR CFM
1080
0
X
RETURN AIR CFM
0
120
X
EXHAUST AIR CFM
120
0
X
FRESH AIR CFM
2
2
X
ZONE
Unit 3 B
Restroom
X
ROOM NAME
8
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
1188
12
X
SUPPLY AIR CFM
1040
0
X
RETURN AIR CFM
0
160
X
EXHAUST AIR CFM
160
0
X
FRESH AIR CFM
3
3
X
ZONE
Unit 3 C
Restroom
X
ROOM NAME
7
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
1185
15
X
SUPPLY AIR CFM
1060
0
X
RETURN AIR CFM
0
140
X
RELIEF AIR CFM
140
0
X
FRESH AIR CFM
4
X
ZONE
Unit 3 Deast
X
ROOM NAME
10
X
OCCUPANTS
> 3 HRS
X
DURATION
1600
X
SUPPLY AIR CFM
1400
X
RETURN AIR CFM
200
X
RELIEF AIR CFM
200
X
FRESH AIR CFM
5
X
ZONE
Unit 3 Dwest
X
ROOM NAME
10
X
OCCUPANTS
> 3 HRS
X
DURATION
1600
X
SUPPLY AIR CFM
1400
X
RETURN AIR CFM
200
X
RELIEF AIR CFM
200
X
FRESH AIR CFM
6
X
ZONE
Unit 3 Enorth
X
ROOM NAME
10
X
OCCUPANTS
> 3 HRS
X
DURATION
1600
X
SUPPLY AIR CFM
1400
X
RETURN AIR CFM
200
X
RELIEF AIR CFM
200
X
FRESH AIR CFM
7
X
ZONE
Unit 3 Esouth
X
ROOM NAME
10
X
OCCUPANTS
> 3 HRS
X
DURATION
1600
X
SUPPLY AIR CFM
1400
X
RETURN AIR CFM
200
X
EXHAUST AIR CFM
200
X
FRESH AIR CFM
8
8
X
ZONE
Unit 3 F
Restroom
X
ROOM NAME
7
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
1187
13
X
SUPPLY AIR CFM
1060
0
X
RETURN AIR CFM
0
140
X
EXHAUST AIR CFM
140
0
X
FRESH AIR CFM
9
9
X
ZONE
Unit 3 G
Restroom
X
ROOM NAME
8
0
X
OCCUPANTS
> 3 HRS
N/A
X
DURATION
1587
13
X
SUPPLY AIR CFM
1440
0
X
RETURN AIR CFM
0
160
X
EXHAUST AIR CFM
160
0
X
FRESH AIR CFM
22x22,9",267 CFM
22x14
22x22,18",-1400 CFM
22x22,9",267 CFM
18x16
12x14
RTU-7
22x22,9",267 CFM
ON ROOF
22x22,9",267 CFM
THIRD FLOOR
22x22,9",267 CFM
Restroom
22x22,8",198 CFM
22x22,8",198 CFM
22x14
8x4,4",13 CFM
12x12
Unit 3 F
12x12
18x16
22x22,16",-1060 CFM
RTU-8
ON ROOF
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM
Restroom
8x4,4",13 CFM
CURB
CONNECTION
DUCT
CONNECTION
ROOFTOP
EQUIPMENT
22x22,9",265 CFM
22x22,9",265 CFM
3/8 BOLT
@ 18" O.C.
ROOF
18x16
Unit 3 G
12x14
22x22,18",-1440 CFM
RTU-9
ON ROOF
22x22,9",265 CFM
22x22,9",265 CFM
22x22,9",265 CFM
Restroom
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM
CURB
DUCT
JOIST
DUCT
SEAL
FMC 601
1/2"
SCREWS
@ 8" O.C.
EQUIPMENT
CONNECTION
ROOFTOP
EQUIPMENT
CURB
(4) 3/8x2
SCREWS
(1) 1/4x2x2
ANGLE
EACH
CORNER
2" U CHANNEL X
1/4" THK
SPAN 3 JOISTS
22x14
12x14
10
10
Unit 3 H
Restroom
R/A
DUCT
FMC
601
S/A
DUCT
FMC
601
CURB
MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD
MECHANICALLY FASTEN AND SEAL DUCTS PER FMC SECTIONS 603 AND 604
MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOAD
6
0
> 3 HRS
N/A
82
> 3 HRS
1187
13
14000
1080
0
12360
0
120
1640
120
0
1640
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
CLASSIFICATION
OCCUPANTS
DURATION
ADJUSTED AIR
TOTAL AIR
CFM / SQ FOOT
PEAK
Office
82
1.00
20
20
1640
20
82
TYPICAL ROOM
SF = SUPPLY FAN
T/A = TRANSFER AIR
VTE = VENT TO EXTERIOR
ZD = ZONE DAMPER
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
12x12
RTU-10
22x22,8",198 CFM
22x22,8",198 CFM
RTU-4,5,6,7,9
FAN MARK:
UNIT MANUFACTURER:
TRANE
TRANE
MANUFACTURER:
NUTONE
THC033A3
THC043A3
MODEL NUMBER:
QT-150
FAN TYPE:
EXHAUST
DOWNFLOW
DOWNFLOW
FAN CFM:
140
37X45X70
37X45X70
TOTAL PRESSURE:
.25
627
669
17X15
17X15
23X14
23X14
1200 / .4
1600 / .4
120/160/140/140/120
200/200/200/200/160
3/60
3/60
208/230
208/230
19.9
22.6
30
35
HEATER KW:
4.5/6
9/12
HEATER MCA:
UNIT CONFIGURATION:
UNIT DIMEN H/W/D:
UNIT WEIGHT:
21.9/24.3
37.5/42.4
HEATER BREAKER:
25/25
40/45
38,000
49,800
28,800
39,400
9,200
10,400
20,472
40,944
0.76
0.79
COOLING EFFICIENCY:
13
13
THERMOSTAT MODEL:
T8411R1002
T8411R1002
SENS. HEAT %
22x22,8",198 CFM
RTU-1,2,3,8,10
1640
22x22,16",-1080CFM
ON ROOF
Bedroom
EF = EXHAUST FAN
FPM = FEET PER MINUTE
MUA = MAKE UP AIR
O/A = OUTSIDE AIR
= AIRFLOW CFM
ADJUSTMENTS
1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007.
2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY
REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO
INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE
THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED.
3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE
GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND
THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY.
4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A
MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL
MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL.
5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD
EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS
ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL
DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER
LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT.
PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA.
PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS.
6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107.
EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS
FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS.
7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON
INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR).
8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING
PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN
6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION.
9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING
TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN
CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE
OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE,
STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS.
MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS
TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER.
10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT
SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING
IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES)
SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.
THIS DESIGN IS FOR PEAK LOAD CONDITIONS ONLY, CONSIDER USING STAGED COOLING EQUIPMENT OR STAND ALONE DEHUMIDIFICATION FOR PART LOAD.
Unit 3 H
18x16
22x14
8x4,4",13 CFM
12x12
CONDENSATE
TO DRYWELL
FMC SECTION 307
ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.
22x22,9",267 CFM
12x14
WALL GRILLE
DIRECT T/ A
FMC 603.15
VERTICAL AIR
HANDLER ON STAND
FMC SECTIONS
303 --- 312
THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.
RTU-6
Unit 3 Esouth
CONDENSATE
DRAIN TO GRASS
FMC SECTION 307
8x4
4"
32
Unit 3 A
22x22,18",-1400 CFM
Unit 3 Enorth
TYPICAL AIR
DEVICE
HVAC NOTES
12x14
18x16
TYPICAL
BRANCH
DUCT
CONDENSING UNIT
ON SLAB
FMC SECTIONS
303 -- 312
CONTROL /
REFRIGERANT
PIPING FMC 1101
22x22,198 CFM
22x22,8",198 CFM
CEILING GRILLE
DUCTED T/ A
FMC 603.15
12x14
22x22,8",197 CFM
22x22,9",267 CFM
PACKAGE UNIT
ROOF MOUNTED
FMC SECTIONS
303 -- 312
Walk In Closet
12x12
TYPICAL
FRESH AIR INTAKE @
ROOFTOP EQUIPMENT
22x22,8",198 CFM
12x12
22x22,8",197 CFM
WALL GRILLE
FILTER RETURN
AIR FMC 603.15
22x22,198 CFM
22x22,198 CFM
12x12
22x22,9",267 CFM
22x22,9",267 CFM
22x22,9",267 CFM
22x22,8",197 CFM
18x16
18x16
18x16
12x14
8x14
22x22,9",267 CFM
CEILING GRILLE
FILTER RETURN
AIR FMC 603.15
TYPICAL
CONDENSATE DRAIN
TO GUTTER / GRASS
22x22,9",267 CFM
22x22,9",267 CFM
107
CFM
T/A
FLEXIBLE
DUCTWORK
FMC SECTION 603
8x4,4",14 CFM
18x16
18x16
8x4,4",15 CFM
RTU-5
22x22,9",267 CFM
147
CFM
T/A
CEILING REGISTER
2 WAY THROW
FMC 603.15
22x22,16",-1080 CFM
VTE
22x22,9",265 CFM
THERMOSTAT @ 60"
ABOVE FLOOR
FEC 13-613
22x22,8",198 CFM
22x22,16",-1040 CFM
Restroom
127
CFM
T/A
12x12
22x22,9",267 CFM
22x22,198 CFM
RECTANGULAR
DUCTWORK
FMC SECTION 603
22x22,9",267 CFM
22x22,9",267 CFM
22x22,9",267 CFM
CEILING REGISTER
1 WAY THROW
FMC 603.15
120/1/60
FAN VOLTAGE:
FAN AMPERAGE:
1.0
14X10X9
3.25X10 TO 7
15X11
FAN WEIGHT:
14
NOTES:
1,2
1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS
North
PROJECT NAME:
PROJECT ADDRESS:
PROJECT STATE, ZIP:
CONDITIONED SQ. FT.:
CLASSIFICATION :
x
Designed By:
Neil Fimbel
HVAC Designs
813-885-2258
FLORIDA BERS
R#884 C#959
DRAWING DATE
1/31/2009
PERMIT SET
SCALE 1/8"=1'-0"
HVAC
DRAWING
3 OF 3