Electrical Switchgear
Electrical Switchgear
MS-E
IEC 62271-200
7.2 /12 / 15 kV
25, 31.5, 40 kA
The MS-E conforms to IEC 62271-200 standard and is designed and manufactured
utilising Mitsubishi Electric state-of-the-art technology, fully taking into account
present and future power system requirements.
Page
FEATURES
APPLICATIONS
STANDARD RATINGS
up-to-date and reliable medium voltage panels, and possesses a supply record
that comprises satisfied customers from all across the globe.
CONSTRUCTION
SWITCHGEAR ARRANGEMENT
13
1. EXAMPLE
2. STANDARD SECTION VIEW AND DIMENSIONS
3. FOUNDATION
STANDARD DESIGN
MS-E with gas exhaust duct
Type testing of the MS-E was first performed at Mitsubishi Electrics High Power
18
21
ACCESSORIES
1. STANDARD ACCESSORIES
2. OPTIONAL ACCESSORIES
3. EARTHING DEVICES
4. GAS EXHAUST DUCT
5. GAS SCREEN
OPTIONS
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
24
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
FEAT URES
A PP L I C AT I ONS
HIGH RELIABILITY
Type testing of the MS-E was performed by an independent external testing and
Mitsubishi MS-E provide control and protection of the power supply to motors,
MS-E is designed with the benefit of Mitsubishis vast medium voltage panels production
experience of hundreds of thousands of panels over the last almost 60 years.
The MS-E is available at rated voltages of 7.2 to 15 kV, with rated short-circuit breaking
MS-E is designed for indoor use and is particularly suitable for electric power plants,
which circuit breakers up to 3150 A are self-cooled (i.e. cooling fans not required).
SAFETY
Partitions between compartments and an automatic shutter system (for withdrawable
equipment primary junctions) completely isolate live parts.
Safe operation and maintenance is ensured with the adoption of comprehensive
interlocking mechanisms.
In the event of an internal arc fault, the MS-E is designed to withstand the huge
pressure and burning effect of the arc. (Relief flaps located on top of the panel open to
limit pressure.)
Multiple
protection relay
Withdrawable equipments are inserted / withdrawn whilst the front panel door is closed
so that any arc proof rating is not compromised (in line with IEC 62271-200
requirements).
EASY INSTALLATION
Installation and testing duration are considerably reduced as the panel is tested and
Withdrawable
vacuum circuit breaker
Self-cooled horizontal
busbars
FLEXIBLE DESIGN
Panels with main circuit and control cable entry from either the top or bottom are
available.
Reinforced
inspection windows
PROTECTION
Mitsubishi MP or EMC Multiple Protection relays are installed as standard. The MP or
Cable compartment
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
3
1. SWITCHGEAR AND CONTROLGEAR
Manufacturer
Mitsubishi Electric
Type designation
6/10-VPR-MMC1
Applied standard
Rated voltage
Ratings
Type designation
Rated frequency
MS-E
Applied standard
IEC 62271-200 1
Rated voltage2
[kV, rms] Ur
Rated frequency
7.2
[Hz] fr
12
15 3
50, 60
20
60
28
75
36
95
[sec] tk
LSC2B-PM
1, 3
IAC
[kA]
[sec]
AFL, AFLR
25, 31.5, 40
0.1, 0.5, 1.0
IEC 62271-100
[kV, rms] Ur
[C]
-5 ~ 40
Altitude a.s.l.
[m]
1000 max.
[%]
[kPa]
95 max.
2.2 average
[m/s2]
[m/s2]
9.80
3.23
Humidity
R.H.
Water vapour pressure
Earthquake protection
Horizontal seismic withstand8
Vertical seismic withstand
50, 60
630, 1250, 2000, 31503
Type test9
Withdrawable equipment10 position
Withdrawal / insertion method
Maintenance access
KEMA (Netherlands)
Mid-mount
20
60
28
75
36
95
[kA, rms] Ik
25, 31.5, 40
[sec] tk
[A, rms] Ic
10, 25
25, 31.5, 40
12.3
[kV] uc
[kV/s] uc /t3 0.24
[cycles]
[kA, peak]
[V DC] Ua
Closing operation
Motor current (at 110 V DC)
Spring charging time
20.6
0.34
3
63, 78.8, 100
48, 110, 220
[A]
[sec]
1.2 (peak 6 A)
Approx. 6 (after closing)
[A]
3.4
[A]
3.4
Weight
25.7
0.34
O 3 minCO3 minCO
O 0.3 secCO 3 minCO
CO 15 secCO
152
[A] Ir
Indoor
Ambient temperature
12
[Hz] fr
Location
7.2
5a, 5b
[kg] M
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
Manufacturer
Mitsubishi Electric
MMFKVN1
Type designation
Applied standard
IEC 60470
Rated voltage
[kV, rms] Ur
6.6
[kV, rms]
7.2
Rated frequency
Rated operational current (self-cooling)
[Hz] fr
50, 60
[A] Ie
200, 400
The front of the MS-E is divided into three kinds of compartments. The upper
compartment is the control compartment, and the middle one is the withdrawable
equipment compartment. The bottom-most compartment can be used for maintenance
20
60
access. (See Figure 4-1.) The multi-function relay (or meters, protective relays, control
switches, etc.) is semi-flush mounted on the door of the control compartment.
40 (Power fuse)
[V AC/DC] Ua
[A]
4.8
[A]
[kg] M
Weight
1. Power fuse rating
20 A
50 A
100 A
150 A
200 A
300 A
400 A
Contactor rating
200 A
400 A
/
/
z
z
x
c
v
L1
Operation system
L2
L3
200 A: 90
400 A: 90 (for 3.3 kV)
100 (for 6.6 kV)
x
b
/
b
/
/
/
w
r
3.3 kV
(kVA)
(kVar)
02F2VN
75
100
75
05F2VN
200
250
10F2VN
400
15F2VN
(kW)
(kVA)
(kVar)
02F2VN
150
200
100
200
05F2VN
400
500
300
500
400
10F2VN
800
1000
500
630
750
500
15F2VN
1250
1500
750
20F2VN
800
1000
750
20F2VN
1600
2000
1000
30F4VN
1250
1500
1000
30F4VN
2000
3000
2000
40F4VN
1500
2000
1200
40F4VN
2800
3500
2000
6.6 kV
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
The VCB is easy to operate, with the closing spring charge indicator, the manual close
The fused vacuum contactor is easy to operate, with the manual trip button for
and trip buttons, the operation counter and mechanical ON / OFF indicator all being
mechanical latch type, the operation counter and mechanical ON / OFF indicator all
being located on the front of the fused contactor. (See Figure 4-4.)
The circuit breaker has two positions, Service and Test/Disconnected, and may be
The fused contactor has two positions, Service and Test/Disconnected, and may be
optionally padlocked at each position. When the VCB is closed, the VCB locks in each
optionally padlocked at each position. When the contactor is closed, the fused
position by mechanical interlock. When the VCB is opened, the interlock pin is released.
contactor locks in each position by mechanical interlock. When the contactor is opened,
The circuit breaker can be easily drawn out or inserted by a simple rotation action. (See
Figure 4-3.) This is accomplished with the circuit breaker compartment door closed.
The fused contactor can be easily drawn out or inserted by a simple rotation action. (See
Unauthorised racking can be prevented by padlocking the shutter for the draw-out
Figure 4-4.) This is accomplished with the fused contactor compartment door closed.
handle aperture.
Unauthorised racking can be prevented by padlocking the shutter for the draw-out
The control circuit terminal of the circuit breaker is of manual connection type. The
handle aperture.
connector (see Figure 4-3) can be only attached when the VCB is in the Test/
The control circuit terminal of the fused contactor is of manual connection type. The
connector (see Figure 4-4) can be only attached when the fused contactor is in the
The circuit breaker cannot be inserted to the Service position when the control
The fused vacuum contactor cannot be inserted to the Service position when the
The control circuit terminals cannot be disconnected when the circuit breaker is
The control circuit terminals cannot be disconnected when the fused vacuum
contactor is in the Service position.
Circuit breakers of different ratings other than specified are mechanically prevented
from being inserted into the Service position.
Rating nameplate
Rating nameplate
Operation counter
Operation counter
ON / OFF indicator
ON / OFF indicator
Control circuit
plug-in terminal
Racking truck
Wheels
Wheels
Racking truck
Power fuse
Racking
Auxiliary VT
(optional)
Racking
Front face-plate
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
Vacuum Magnetic
Contactor (VMC)
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
10
5. AUTOMATIC SHUTTERS
Inserting the withdrawable equipment into the Service position causes the shutters to
As shown below, the shutters operate on the busbar and cable sides. The shutters for
the upper and lower primary junctions can be closed and opened individually, and can
be (optionally) padlocked in the closed position.
7. WIRING
Necessary control equipment such as auxiliary relays, terminal blocks and fuses are
located in the control compartment.
Ducting and bundling ensure that control wiring is systematic and neat.
External control cable can be terminated to both sides of the compartment.
Wiring to devices mounted on the door are protected from damage during opening or
closing by vinyl tubing.
8. EARTHING BUSBAR
Figure 4-8 Optional padlocking of top and bottom shutters
The shutters are made of metal and the following labels can be (optionally) provided.
be optionally tin-plated.
The shutters can be (optionally) provided with a manually operated device to keep it in
11
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
12
1. EXAMPLE
Panel
type
Rated
voltage
(kV)
Section view
A. SINGLE-LINE DIAGRAM
TR
25
TR
7.2
12
3VT
3VT
Shortcircuit
current
(kA)
1900
300
31.5
CT
CT
CT
CT
ES
550
ES
3VT
250
3VT
L1
VCB
40
L2
VCB
L3
Incomer
VCB
2600
CT
PF
VCB
PF
VMC
VCB
VCB
VCB
VCB
PF
VMC
ES
CT
CT
ES
CT
CT
CR
ZCT
ZCT
ES
ZCT
ES
CT
LA
LA
ZCT
ZCT
ES
CT
2300
PF
VMC
ES
ES
CTS
25
ES
CT
15
31.5
CR
ZCT
ZCT
ZCT
TR
TR
25
B. PANEL LAYOUT
1900
PF
PF
VMC
VMC
VCB
VCB
VCB
VCB
VCB
VCB
VCB
PF
PF
VMC
VMC
7.2
12
300
31.5
ES
ES
CT
ES
CT
CT
CR
ES
550
CT
LA
3VT
ES
CT
3VT
CT
ES
CT
CT
3VT
CT
ES
ES
CT
ES
CT
LA
ES
CT
CT
CR
L1
Incomer
+
VT
(fixed type)
40
L2
L3
CTS
2600
VCB
2300
25
ZCT
ZCT
ZCT
ZCT
630
630
1250
2000
2000
3150
3150
630
630
1250
1250
2000
2000
3150
3150
630
630
1250
1250
2000
2000
3150
3150
630
630
1250
1250
ZCT
ZCT
ZCT
ZCT
630
630
1250
1250
630
630
1250
2000
2000
630
630
1250
1250
2000
2000
3150
3150
630
630
1250
1250
2000
2000
3150
3150
TR
TR
630
630
1250
1250
2000
2000
3150
3150
630
630
1250
1250
2000
15
31.5
630
630
1250
1250
2000
CT:
E. BUS:
ES:
LA:
M:
CR:
VCB:
VT:
ZCT:
TR:
VMC:
PF:
13
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
Current Transformer
Earthing Busbar
Earthing Switch
Lightning Arrester
Motor
CR suppressor
Vacuum Circuit Breaker
Voltage Transformer
Zero-phase sequence Current Transformer
Transformer
Vacuum Magnetic Contactor
Power Fuse
Depth3 Height4
(D)
(H)
1500
1900
(2200)
1500
1900
(2200)
1500
1900
(2200)
800
2600
(2850)
1500
1900
(2200)
1500
1900
(2200)
2000
1250
2000
VT
Width
(W)
2000
E. BUS
Dimensions (mm)
1500
1900
(2200)
1500
1900
(2200)
1500
1900
(2200)
Weight
(t)
Heat
loss
(W)
0.9
200
1.0
500
1.2
800
1.4
1200
0.9
200
1.0
500
1.2
800
1.4
1200
0.9
200
1.0
500
1.2
800
1.4
1200
0.9
200
1.0
500
1.2
800
0.9
200
1.0
500
1.2
800
0.9
200
1.0
500
1.2
800
1.0
200
1.1
500
1.3
800
1.5
1200
1.0
200
1.1
500
1.3
800
1.5
1200
1.0
200
1.1
500
250
3VT
VCB
1250
2000
40
M
Busbar
2000
VMC
CT
40
2000
630
630
1250
1250
2000
2000
1500
1900
(2200)
800
1500
1900
(2200)
1500
1900
(2200)
1500
1900
(2200)
2600
(2850)
1.3
800
1.5
1200
1.0
200
1.1
500
1.3
800
1.0
200
1.1
500
1.3
800
1.0
200
1.1
500
1.3
800
1. Gas exhaust duct or gas screen (shown dashed) is required when Internal Arc Classification (IAC) be selected.
2. Arc proof ventilator (shown dashed) is required when AFLR of IAC be selected.
3. Depth given in parentheses applies when AFLR of IAC be selected.
And if more than 2 cables / phase required, or CT is non-standard, then the depth will increase.
4. Height given in parentheses applies when IAC be selected.
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
14
Panel
type
Rated
voltage
(kV)
Section view
Shortcircuit
current
(kA)
VCB
630
630
1250
1250
2000
2000
3150
3150
630
630
1250
1250
2000
2000
3150
3150
630
630
1250
1250
L2
2000
2000
L3
3150
3150
630
630
1250
1250
25
1900
7.2
12
300
31.5
Dimensions (mm)
Width
(W)
Depth
(D)
Weight
Height
(t)
(H)
4
1500
1900
(2200)
1500
1900
(2200)
Heat
loss
(W)
0.9
200
1.0
500
1.2
800
1.4
1200
0.9
200
1.0
500
1.2
800
1.4
1200
0.9
200
1.0
500
1.2
800
1.4
1200
0.9
200
1.0
500
Panel
type
Rated
voltage
(kV)
Section view
Shortcircuit
current
(kA)
1500
25
630 ~ 3150
550
250
L1
Outgoing
feeder
(transformer)
7.2
12
31.5
630 ~ 3150
L2
40
L3
2600
VCB
CT
25
2300
630 ~ 3150
630 ~ 2000
VCB / VT
Dimensions (mm)
Heat
Weight loss
Width Depth Height
(t)
(W)
(D)
(H)
(W)
2
630
0.9
300
1250
1.0
600
630
0.9
300
1250
1.0
600
630
0.9
300
1250
1.0
600
0.9
300
1250
1.0
600
630
0.9
300
1250
1.0
600
630
0.9
300
1250
1.0
600
630
0.9
300
1250
1.0
600
630
0.9
300
1250
1.0
600
630
0.9
300
1250
1.0
600
0.9
300
1250
1.0
600
630
0.9
300
1250
1.0
600
630
0.9
300
1250
1.0
600
0.8
100
800
1500
630
2600
(2850)
550
250
40
L1
Bus-tie
CTS
2600
VCB
2300
25
1500
1600
(2 800)
L3
15
31.5
2000
2000
630
630
1250
1250
2000
40
25
630
1250
1250
1500
1900
(2200)
2000
2000
630
630
1250
1250
2000
2000
1900
(2200)
1900
(2200)
3150
630
2000
2000
3150
3150
630
630
1250
1250
L2
2000
2000
L3
3150
3150
630
630
1250
1250
2000
2000
630
630
1250
1250
1500
(2200)
2000
1900
(2200)
250
40
Bus-tie
+
VT
(fixed type)
L1
CTS
2600
VCB
2300
25
L1
L2
L3
VT
15
31.5
2000
40
800
0.9
200
1.0
500
630 ~ 2000
1500
25
630 ~ 3150
550
250
L1
Outgoing
feeder
(motor)
7.2
12
31.5
630 ~ 3150
L2
40
L3
2600
VCB
25
2300
CT
15
630
630
1250
1250
2000
2000
800
1.0
200
1.1
500
1.3
800
1.5
1500
1900
(2200)
550
40
31.5
630 ~ 3150
630 ~ 2000
630 ~ 2000
40
ZCT
630 ~ 2000
630 ~ 3150
7.2
1500
1200
25
31.5
40
800
630
1500
2600
(2850)
1500
1600
(2 800)
1900
(2200)
1500
1900
(2200)
1500
1900
(2200)
2600
(2850)
1.0
200
1.1
500
1.3
800
1.5
1200
1.0
200
1.1
500
1.3
800
1.5
1200
1.0
200
1.1
500
1.3
800
1.0
200
1.1
500
1.3
800
1.0
200
1.1
500
1.3
800
3 VT
6600/110 V
3 EVT
630 ~ 3150
1250
31.5
500
1.2
1500
630
7.2
12
1.0
1.2
1500
1250
300
200
630 ~ 2000
LA4
800
0.9
31.5
CR
3150
1900
1.2
1500
2000
630
2600
(2850)
1900
(2200)
L1
L2
1900
(2200)
15
550
6600 110
3
3
190
V
3
250
L1
VT
(withdrawable)
630 ~ 3150
L2
L3
12
2600
VT
25
31.5
40
3 EVT
630 ~ 3150
2300
630 ~ 2000
15
25
31.5
40
3 VT
11000/110 V
11000 110
3
3
190
V
3
800
1500 2600
(1900) (2850)
3 VT
13800/110 V
3 EVT
190
V
3
1. Gas exhaust duct or gas screen (shown dashed) is required when Internal Arc Classification (IAC) be selected.
2. Depth given in parentheses applies in case of incoming VT.
And if CT is non-standard, then the depth will increase.
3. Height given in parentheses applies when IAC be selected.
4. Required only for dry-type transformers.
1. Gas exhaust duct or gas screen (shown dashed) is required when Internal Arc Classification (IAC) be selected.
2. Arc proof ventilator (shown dashed) is required when AFLR of IAC be selected.
3. Depth given in parentheses applies when AFLR of IAC be selected.
And if more than 2 cables / phase required, or CT is non-standard, then the depth will increase.
4. Height given in parentheses applies when IAC be selected.
15
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
16
Panel
type
Rated
voltage
(kV)
Section view
Shortcircuit
current
(kA)
Dimensions (mm)
VMC2
Busbar
1500
Heat
Weight
loss
(t)
(W)
700
200 / 200
25
1.5
630 ~ 3150
550
L1
400 / 400
1100
L2
700
200 / 200
L3
Outgoing
feeder
7.2
31.5
1200
630 ~ 3150
1500
400 / 400
2600
CT
VMC
1 x VT
2600
(2850)
1.5
1100
Frame: 2.0 mm
Door: 2.0 mm
2300
700
200 / 200
40
1.5
630 ~ 3150
ZCT
1.
2.
3.
4.
1100
400 / 400
Gas exhaust duct or gas screen (shown dashed) is required when Internal Arc Classification (IAC) be selected.
Two VMCs are built in one panel.
If CT is non-standard, then the depth will increase.
Height given in parentheses applies when IAC be selected.
Position
Structure
Hinge location
Handle location
Handle lock
Front
Hinged doors ( 3)
Left
Right
Optional
Rear
Bolted covers ( 2)
Degree of protection
Enclosure: IP3X
Internal partitions: IP2X
VT (withdrawable) Panel
Front space
1500 (1900)
1500
Rear space1
170 100
75
90
75
100 70
53
53
75
90
700 (200)
1500 (1900)
170 100
75
Front space
700 (200)
100 70
1500
Rear space1
75
70 100
800
75
75
75
70100
600
800
Standard dimensions: 6 mm 25 mm
VMC2 Panel
Front space
Rear space1
1500
700 (200)
1500
205 (500) 135
53
410
90
75
170 100
90
90
70 100
1 2 3 4
1 2 3 4
75
410
200
1200
Wire number
The VT / CT test terminals and terminal blocks shown below are adopted as standard.
VT secondary
CT secondary
Test terminals
17
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
Terminal block
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
18
8. SAFETY INTERLOCKS
Interlock Conditions
Action
1st phase
2nd phase
3rd phase
L1
L2
L3
(Viewed from front to back, top to bottom, or left to right from front.)
DC
1st wire
2nd wire
VCB / VMC
state
Positive
Negative
Withdrawable
Withdrawable Control circuit
equipment position equipment door connector
OFF
Closed
Earthing
Switch1
OFF
Cable
door
Disconnected2
Disconnected
Attached2
ON
Disconnected
Service /
Disconnected
Closed
(Viewed from front to back, top to bottom, or left to right from front.)
Main circuit colour identification is achieved with vinyl tape or coloured label at bus end
where main cables are connected.
AC
Red
Yellow
Blue
L1
L2
L3
Door
interlock
optionally installed.)
AC 3-phase
AC 1-phase
DC
L1
L2
L3
Neutral
Red
Yellow
Blue
Black
1st wire
2nd wire
Neutral
Red
Blue
Black
Positive
Negative
Red
Blue
Vacuum Circuit
Breaker
Fused Vacuum
Contactor
Main circuit
6. WITHDRAWABLE EQUIPMENT
Apparatus
Racking
interlock
Door
interlock
(Identifying colour tube markers, with the standard colours shown below, can be
Finish colour
Earthing circuit
(Carriage frame)
Control circuit
Automatic
connection
(self-aligning)
Manual connection
Automatic connection
(earthing shoe)
Voltage
Transformer
10. NAMEPLATES
Nameplates are of plastic with black lettering on white background, fastened by plastic
rivets, and are the following sizes:
Service
Test/Disconnected
The front door can be opened / closed when the withdrawable equipment is
Test/Disconnected position.
19
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
Rotary machine
(electric motor &
generator)
Dry-type
transformer
Oil-immersed
transformer
CR Suppressor
Lightning Arrester
Not required
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
20
In the case of cable-side earthing, the earthing switch is integrated within the cable
Lifter
compartment . A mechanical interlock between the earthing switch and circuit breaker
(or fused contactor) is provided.
Bucket
Draw-out handle
Bus-side earthing switches are usually integrated within a VT panel, and so employ
electrical interlocking with the adjacent panels circuit breaker.
The mechanical indicator for the earthing switchs state can be checked from the front of
the panel through a small, circular inspection window.
Control circuit extension cable for withdrawn VCB / VMC ON / OFF testing
Load cable
terminal
Earthing switch
Operating handle
Withdrawable equipment
compartment door
ON
Cable compartment door
OFF
Mechanical interlock
(door openable when E.S. ON)
Front
Figure 7-6 Section view of earthing switch
21
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
22
gas exhaust duct must be fitted onto the top of panel. The gas exhaust duct ensure that
in the event of an internal arc fault, any hot gases or vapours are channeled away from
personnel in the vicinity of the panel.
ITEM
CLASSIFICATION
The gas exhaust duct may extend to the open air. The straight and maximum two meters
Degree of protection
design, which is standard, is available. The part of extension duct to reach to the open
SPECIAL SPECIFICATIONS
STANDARD DESIGN
IP3X
AND/OR OPTIONS
IP31 IP32
IP4X IP42
air will be supplied by others. The design guideline for them will be shown for consumer
Padlocking facility
convenience.
Available
A FL , A F L R
25, 31.5, 40 kA
0.1, 0.5, 1.0 sec
Power
Bottom
Top
Control
Bottom
Top
Plating
Tin
Silver
Insulation
Bare
Epoxy coat
The gas exhaust duct is dismantled from the panels prior to shipping, and are
Position
re-attached on site.
Shutters
Enclosure
Available
With gas exhaust duct, the switchgear and controlgear are designed to protect persons
Accessibility type
in the event of an internal arc fault of up to 40 kA. Thus, in the event of internal arcing,
there is no ejection of parts, no expulsion of hot gases (except from the gas exhaust
duct) and the enclosure remains earthed. Minimum clearances of 600 mm, 100 mm
Cable entry
and 800 mm from the panel to the rooms ceiling, side walls and back wall, respectively,
are required.
Classification IAC
AFLR signifies that the switchgear and controlgear are designed for access from the
PVC
signifies that the switchgear and controlgear are designed for access from the
Plating
Tin
Size
6 25 mm
6 32, 6 40 mm
No segregation
With segregation
Cable lugs
Not supplied
Cable glands
Not supplied
Not supplied
Heat-shrinkable material
Busbars
Earthing busbar
5. GAS SCREEN
The gas screen can be selected instead of the gas exhaust duct on condition that
ceiling height from floor of electrical room is 4400 mm or over.
Busbar compartment
segregation between panels
Gas screen
Gas exhaust duct
Main circuit
Wire type
Please specify
Wire size
Please specify
other: 1.25 mm
Control circuit
Extension gas exhaust duct
Fr o
Fr o
nt
23
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
Colour
Yellow
Please specify
Terminals
Up to 5.5 mm2
Please specify
Terminal blocks
Screw type
Please specify
(e.g. clip-on)
nt
24
ITEM
CLASSIFICATION
STANDARD DESIGN
SPECIAL SPECIFICATIONS
AND/OR OPTIONS
Space heater
Not supplied
Thermostat
Not supplied
Not supplied
Available
Not supplied
Not supplied
Available
Earthing truck
Not supplied
Available
VT
Withdrawable (mid-mount)
Not supplied
Slow speed
High speed
(ATS)
Foundation bolts
Not supplied
Available
Channel base
Not supplied
Available
Secondary rating
5A
1A
Measuring
Class 1.0
Please specify
10P20
5P10
Accuracy
CT
Burden
Min. 5 VA
Please specify
Material
Acrylic plastic
Laminated plastic
Stainless steel
Nameplates
Measurement and
Protection
25
MEDIUM VOLTAGE
SWITCHGEAR AND CONTROLGEAR
Language
English
Please specify
Relay
MITSUBISHI MP or EMC
protection relays