01 - Wk10 APM Handout Part 1 of 4
01 - Wk10 APM Handout Part 1 of 4
Paul Lo
Senior Electrical Engineer
1
Ea
st H
all
West H
all
APM System
Runs between
East Hall and
West Hall
2
APM Trains
Maximum: 70 km/h
Acceleration: 0.98 m/s2 maximum
Deceleration: 1 m/s 2 maximum
Emergency deceleration: 1.5 m/s2 maximum
Route Length
11kV 3 Supply
11kV RMU
Traction
Transformer
Isolator (N/O)
Isolator (N/C)
ACB (N/O)
East Hall
Substation
Section Insulator
ACB (N/C)
Cable Section
Depot
Substation
Harmonic Filter
Stinger System
West Hall
Arrival
Platform
End of
Line
Power Rail
East Hall
Arrival
Platform
APM
Depot
Power Rail
West Hall
Departure
Platform
East Hall
Departure
Platform
Standards :
BS171, IEC60076
Vector Group :
Dyn11
Type of insulation :
Rated power :
2500 kVA
11 kV AC 3-phase
Rated frequency :
50Hz
28 kV / 75 kV peak
Impedance voltage :
6.5%
Thermal Class :
Type of cooling :
AN
LV Insulation Level :
3 kV
PDS Equipment
Photos
TR01
11KV / 600V
Traction Transformer Room
Photo area
TR02
Lifting Lugs
LV Terminal
PDS Equipment
Name Plate
Upper
Frame
HV Terminal
Transformer
Internal Layout
Interphase
Lead
No Voltage
Tap Changer
Lower
Frame
Anti-vibration
Rubber
Wheel
PDS Equipment
Transformer Construction
1 Lifting lugs
2 LV Terminals
3 HV Coil
4 LV Coil Termination
5 Core Bandage
6 LV Coil
7 Pulling Holes
8 Lower Frame
9 Core Yoke
10 Core Bolt Insulation
11 Core Pressing Bolts
12 Upper Frame
13 Coil Clamp Adjustor
14 Tap Link
15 Resin Support Block
15A Resilient Pad
16 Core Legs
17 Tie Bars
18 HV Terminal
19 HV Taps
20 Anti-Vibration Rubber
21 Trolley Frame
22 Bi-directional Wheel
23 HV Conductors
24 Air Duct for Cooling
25 LV Conductors
10
PDS Equipment
Photos
Traction Transformer
Photo 2 -
Photo area
Housing
600V side
Star Connection
Star Point
11
PDS Equipment
Photos
Insulator
Photo area
Incoming 11kV Cables
Traction Transformer
Photo 3 Transformer core inside
Housing
11kV side
Delta Connection
CastResin Core
Interphase lead
PDS Equipment
Photos
Traction Transformer
Photo 4
Photo area
Core Construction
Cable Trench
to APM Tunnel
Battery &
Charger
Cable Trench
Main Switchboard
Harmonic
Filter
Au
xil
iar
yP
lan
tro
om
RTU
14
Standards :
EN60439, IEC947
Rated voltage :
600V AC
2500 A
2500 A
2500 A
Breaking capacity :
50 kA
CB pole numbers :
50 kA 1 sec.
Type of insulation :
Air
Type of interruption :
ACB
15
Function
52S1
52S2
52F1
52F2
52F3
Depot Feeder
52FL1
52FL2
DS0
Isolator - Busbar
DS1
Isolator Feeder
DSF1
Isolator Arrival
DSF2
Isolator - Departure
16
DS1
DSF1
52FL1
DSF2
52F1
DS0
52F2
52F3
52S2
52S1
TR1
17
52FL2
TR2
52FL1
52F1
52S1
DS0
52S2
52F2
52FL2
52F3
18