Masonry Design Guide: Structural, Fire and Acoustics Victoria Book 1
Masonry Design Guide: Structural, Fire and Acoustics Victoria Book 1
www.boral.com.au/masonry
PAGE
PAGE
Victoria Book 1 A
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2
Products @ a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A4
A
B
Introduction
Structural Design
Robustness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2
Energy Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B7
Strength . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B5
Bending . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B5
Shear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B6
Durability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B6
Fire Design
Acoustic Design
The information presented herein is supplied in good faith and to the best of our knowledge was accurate at the time of preparation. No responsibility can be accepted by
Boral or its staff for any errors or omissions. Users are advised to make their own determination as to the suitability of this information in relation to their particular purpose
and specific circumstances. Since the information contained in this document may be applied under conditions beyond our control, no responsibility can be accepted by us
for any loss or damage caused by any person acting or refraining from action as a result of this information.
A2
Victoria Book 1 A
The quickest way to find a Boral Masonry Structural, Fire or Acoustic Wall Solution.
Simply follow the FAST FIND GUIDE on the right hand side of the table.
NLB = Non-loadbearing
LB = Loadbearing
W
al
l
Re
ta
in
in
g
Li
ni
ng
te
rb
o
N
o
Re
Pl
as
nd
er
ed
ar
d
ry
on
M
as
e
Fa
c
LL
W
A
BLOCK &
BRICK
PRODUCTS
FI
N
IS
H
BORAL
MASONRY
E4
E4
E4
E6
E6
E6
E6
E6
E6
E6
E6
E6
E6
E6
E6
E6
E6
E6
E6
Acousticell
E14
E14
Designer Block
E8
E8
E8
E8
E8
E8
Fast Find
a Boral
Solution
Select your application
criteria from the top of
the table
Go straight to the
section letter and page
number indicated at the
intersection of product
rows and application
columns (e.g. Section E,
Page E6 in this example)
E10
E10
E10
For technical support and sales office details please refer to the outside back cover
February 2009
A3
Victoria
Vi
V
icctttor
oriiaa BBook
ooook 1 A
Back-up Block
Ash Grey Concrete Block in 162mm height
(equivalent to 2 courses of standard brick).
Designed for cost effective construction of the
back-up leaf in face brick veneer walls.
A4
Victoria
V
Vic
icttor
oria
ia Book
BBoo
Bookk 1 A
Acousticell
Engineered block for premium sound absorption and
attenuation of industrial and commercial noise.
February 2009
A5
Victoria Book 1 A
Boral Masonry
Commercial Construction Solutions
Boral Masonry Victoria offers a comprehensive range of proven
products and systems including Masonry Blocks, Masonry
Bricks, Fire and Acoustic Wall Systems, Segmental Block
Retaining Walls and Segmental Paving Products.
A6
BORAL MASONRY
Victoria Book 1 B
tr
Robustness
B2
Cv,Ch =
kt
Lr
Victoria Book 1 B
Worked Examples
Isolated Piers
Aim:
H
tr
Cv
H 0.14 x 30
H 4.200m (maximum wall height)
Worked Examples
Aim:
Criteria:
H
Cv
kt x tr
H
Cv
February 2009
B3
Victoria Book 1 B
Worked Examples
Aim:
Criteria:
i.e. L tr x Ch
Where Ch is obtained from AS3700 Table 4.2. (Refer to
Page B5)
H
tr
L 0.11 x 12
L 1.320m
Example 2: If wall is restrained along both ends, then
Ch = 36
L 0.11 x 36
L 3.960m
NOTE: If the wall exceeds the permitted length, then a
thicker wall is required or formula 4.6.2 (4) governs and H
will be limited. (See below).
Worked Examples
Aim:
Criteria:
= no limit
H
tr
Cv +
Ch
Lr Chtr
( C + L C C t ) t
v
hr
H 5.9m
B4
Victoria Book 1 B
Vertically
unreinforced
Vertically reinforced
or prestressed
12 with
reinforcement
continuous into
support. Otherwise
6.
Free
SUPPORT
27
36
SUPPORT
Concrete Slab
Lateral
Support
36
48
SUPPORT
ISOLATED PIERS
Lateral
Support
13.5
30
SUPPORT
Ch
Horizontally
unreinforced
Horizontally
reinforced or
prestressed
12
24 with
reinforcement
continuous past
support.
Otherwise 16
SUPPORT
SUPPORT
SUPPORT
Edge restraints on
vertical sides of
wall panels
36
48
6
8
10
15
20 or more
Strength
Compressive strength is resistance to load, measured by the
amount of pressure to crush a masonry unit. The pressure, usually
measured in megapascals (MPa), is the force in kilonewtons (kN)
x 1000, divided by the loaded area in square mm.
Unconfined compressive strength is compressive strength,
multiplied by an aspect ratio, Ka (see AS4456.4, Table 1). The
unit height divided by its thickness is used to determine the
aspect ratio.
A solid brick will give a lower compressive strength if crushed
on its end rather than on its flat, as normally laid. In theory,
the aspect ratio will convert both tests to the same unconfined
compressive strength.
The strength of hollow blocks is calculated by dividing the force
by the face shells only. A 90mm hollow and 90mm solid block
are both 10MPa, but since the area of the face shells on the
hollow block is about half the area of the solid block, the hollow
will only carry half the load of the solid.
Characteristic Unconfined Compressive Strength of
masonry UNITS is uc.
uc is the average of crushing forces divided by loaded areas,
multiplied by the aspect ratio, minus the standard deviation x
1.65.
Characteristic Compressive Strength of a masonry
WALL is m.
m is the square root of uc, multiplied by Km (a mortar
strength factor), multiplied by Kh (a factor for the amount of
mortar joints) as per AS3700, 3.3.2.
The Km factor is 1.4 for M3 mortar on solid and cored units
and is 1.6 for the face shells of hollow units. For the richer M4
mortar it is 1.5 (Table 3.1).
The Kh factor is 1 for 76mm high units with 10mm mortar
beds and is 1.3 for 190mm units with 10mm mortar beds.
In other words, a wall of 190mm high units is 30% stronger
than a wall of 76mm high units of the same uc.
Bending
Characteristic Flexural Tensile Strength is mt.
Masonry is good in compression but poor in tension. Mortar
joint strength is generally zero or 0.2MPa for loads from wind,
earthquake etc. Higher bending forces may require masonry
to be partially reinforced.
t
Wall Leaf
Pier Width
Pier Spacing
February 2009
B5
Victoria Book 1 B
Shear
Characteristic Shear Strength is ms.
At damp course, it is zero unless tested. Elsewhere, mortar
joints have ms values of between 0.15 and 0.35MPa.
As with tension, high shear loads may require partially
reinforced masonry.
Durability
Masonry designed for Durability is deemed to satisfy when it
meets the requirements of AS3700 Section 5, which details
what areas require Exposure, General Purpose and Protected
grades. Assessment of these grades is defined in
AS/NZS4456.10 Resistance to Salt Attack.
AS3700 defines the usage of each of these grades as:
Protected Grade (PRO)
Elements above the damp-proof course in non-marine exterior
environments. Elements above the damp-proof course in other
exterior environments, with a waterproof coating, properly
flashed junctions with other building elements and a top covering
(roof or coping) protecting the masonry.
General Purpose Grade (GP)
Suitable for use in an external wall excluding severe marine
environment.
Exposure Grade (EXP)
Suitable for use in external walls exposed to severe marine
environments, i.e. up to 100m from a surf coast or up to 1km
from a non surf coast. The distances are specified from mean
high water mark.
Mortar mix requirements for durability are detailed in AS3700
Table 10.1. Mortar joints must be ironed.
Even if they are well away from the coast, they may be subjected
to acidic or alkaline soils. In any case, moisture in the ground
is absorbed into the masonry, creating an environment ideal
for bacteria, which feeds lichens and algae which can eventually
be detrimental.
AS/NZS4456.10 gives methods of testing and definitions for
durability (salt tests). An alternative to testing is a history of
survival in a marine environment. Concrete masonry has been
used for Surf Club construction around Australia for decades.
Movement
In general, concrete units contract as they cure while clay units
will expand. They both expand as they take up water and
contract as they dry. They both expand as they get hot and
contract as they cool.
The salt crystals then take up space, sometimes more than the
texture of the masonry will allow. The crystal then pops a piece
of the outer surface off to make room and salt attack begins.
B6
Victoria Book 1 B
Energy Efficiency
As of May 2005, the BCA requires energy efficiency
performance for houses and home units in Victoria to achieve
a 5 star rating for houses and an average of 5 stars for all
units in the building and a minimum of 3 stars for each
unit of a Class 2 building. For a Class 4 sole occupancy unit,
a minimum of 4 stars is required. The rating is assessed by
a person accredited in the use of NatHERS or FirstRate
software or complies with Practice Note: 2005-55 at
www.buildingcommission.com.au.
February 2009
B7
Victoria Book 1 B
NOTES
Vertical
Bars
Vc
Mc
Bars
Vc
Mc
N12
N16
5.1
6.3
2.6
2.6
N12
N16
12.5
13.7
9.3
16.0
Horizontal
Bars
N12
N16
100
Vc
5.1
6.3
Mc
2.0
2.9
Cut on-site
Horizontal
300
15.15
70
Bars
Vc
Mc
N12
N16
10.2
12.6
4.0
4.7
15.12
70
Moment and Shear Capacities for Series 200 Blocks (190mm leaf)
Vertical
Vertical
Bars
Vc
Mc
Bars
N12
N16
N20
7.9
10.2
13.1
3.6
3.6
3.6
N12
N16
N20
Vc
6.4
7.6
9.1
Mc
2.9
3.6
3.6
Horizontal
Horizontal
Bars
100
N12
N16
N20
20.12
Vc
8.2
9.3
10.6
Mc
4.0
6.9
9.9
Bars
100
N12
N16
N20
Mc
2.9
5.0
6.5
20.12
95
Vertical
Vertical
Bars
Vc
Mc
Bars
Vc
Mc
N12
N16
N20
17.9
20.2
23.1
18.0
30.2
32.2
N12
N16
N20
16.4
17.6
19.0
9.5
16.6
24.4
20.20 or
20.01 cut
on-site
20.20 or
20.01 cut
on-site
Horizontal
300
Horizontal
300
Bars
Vc
Mc
Bars
N12
N16
N20
16.4
18.6
21.3
8.0
13.4
17.2
N12
N16
N20
20.12
Vc
12.9
15.2
18.1
Mc
5.7
9.5
9.9
20.12
B8
Vc
6.4
7.6
9.1
95
Victoria Book 1 B
Boundary
Introduction
Backfill
Ground level
Base Type 1
Foundation
Boundary
Ground level
Base Type 2
Wall Types
Foundation
Design tables in this section are given for walls up to 3.4 metres
high and for two base types:
Loading Conditions
Construction
Recommendations
General
Since typical cases only are presented, these tables may not
provide an ideal solution for a particular application.
February 2009
B9
Victoria Book 1 B
Impermeable
layer sloping
to drain
Drain
The use of H blocks above the first course. These blocks are
easier to fill with grout which provides the required
continuous protection to the reinforcement. If rebated flushended blocks are used in lieu of H blocks, they should be
laid with alternate courses inverted to provide grout cover
to horizontal reinforcement, which should be supported
20mm clear of the webs of flush-ended blocks.
The forming of weepholes by leaving out mortar in the vertical
joints at the required locations. Where H blocks are used, and
weepholes are required, they may be provided by placing
25mm diameter PVC pipes through the vertical joint at the
required locations. Alternatively, flush-ended blocks may be
placed on either side of the required weephole location so a
mortar-free joint may be formed.
Backfill
Backfill Drainage
It is essential that steps be taken to prevent the backfill behind
the wall from becoming saturated. These steps should include:
Sealing Backfill Surface
To prevent saturation of backfill by surface run-off, the surface
of the backfill should be sealed by covering it with a compacted
layer of low permeability material. The surface should be sloped
towards an open drain.
B10
Continuous
agricultural pipe
drain surrounded
by free-draining
gravel or crushed
stone
To prevent clay or
silt infiltrating the
drainage system a
geofabric material
may be wrapped
around the gravel
and/or the pipe
Victoria Book 1 B
Backfill
Free draining
granular material
Locate the
continuous drain
at the bottom of
the base
Free-draining
gravel or stone
Weepholes
between
blocks
Drain
Water Penetration
Extra
agricultural
pipe drain
Weepholes
Weepholes should be provided above the finished ground
level. A drain should be provided in front of the wall to
prevent saturation of the ground.
The horizontal spacing of the weepholes depends on the
provisions made for directing water towards the holes.
The simplest, but most effective, method is to place one
or two buckets of free-draining gravel or crushed stone
around the intake end of each hole. In this case, the
horizontal spacing should not exceed 1.5 metres. If the
layers of draining material are continuous for the full
length of the wall, weephole spacing may be increased to
an extent depending on the quantity of water expected.
55mm cover to
wall reinforcement
30mm
Clean-out
course
February 2009
B11
Victoria Book 1 B
Sloping backfill
or surcharge
Optional
capping
Longitudinal
reinforcement: N12 in
alternate courses
commencing from top
course. Omit on top of
clean-out block
Sloping
backfill or
surcharge
190
Optional
capping
Longitudinal reinforcement:
N12 in alternate courses
commencing from top course.
Omit on top of clean-out block
Vertical reinforcement:
N12 @400 cts
190
450
min
lap
H = 2200
to 3400
N12 @400
cts
Optional
capping
H = 800
to 1200
Longitudinal
reinforcement:
N12 in
alternate
courses
commencing
from top
course. Omit
on top of
clean-out
block
Sloping
backfill or
surcharge
140
Height
of
190mm
blocks
K Bars
H = 1400
to 2000
290
N12 @400
cts
600
min
lap
V Bars
450
min
lap
Height of
290mm
blocks
V Bars
V Bars
X Bars
X Bars
X Bars
200
250
300
400
350
550
180
N16 @400
N12 @400
N16 @400
230
330
B
Fig B9 Construction Guidelines for Reinforced & Core Filled Retaining Walls with Base Type 1
Table B3 Design Guidelines for Reinforced & Core Filled Retaining Walls with Base Type 1
Wall Height
Total
Height
(mm)
H
800
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
3000
3200
3400
B12
150
Series
800
1000
1200
Height of Blockwork
200
Series
1400
1600
1800
2000
1400
1600
1600
1800
2000
2000
2000
Reinforcement
300
Series
800
800
1000
1000
1000
1200
1400
X-Bars
and
V-Bars
N12 at 400
N12 at 400
N12 at 400
N12 at 400
N16 at 400
N16 at 400
N16 at 200
N16 at 400
N16 at 400
N20 at 400
N20 at 400
N16 at 200
N20 at 200
N20 at 200
K-Bars
N16 at 400
N16 at 400
N20 at 400
N20 at 400
N16 at 200
N16 at 200
N16 at 200
Base Dimensions
Width, B (mm)
with following backfill conditions
Level
Max 1 in 4 Slope
800
1000
1000
1200
1100
1500
1300
1700
1400
2000
1600
2200
1700
2500
1900
2800
2000
3100
2200
3300
2400
3600
2600
3900
2800
4200
2900
4500
Victoria Book 1 B
Surcharge or
sloping backfill
(1 in 4 max.)
Surcharge or
sloping backfill
(1 in 4 max.)
Optional
capping
N16 in top course only
190
Height of
190mm
blocks
Optional
capping
Longitudinal
reinforcement
N12@400cts.
commencing from
top course. Omit on
top of clean-out
course
N12@400 cts
Longitudinal reinforcement:
N12@400
N16 in top
course only
190
Surcharge or
sloping backfill
(1 in 4 max.)
140
Longitudinal
reinforcement
N12@400 cts.
Omit on top of
clean-out course
Optional
capping
600
min.
lap
H = 2200
to 3400
Longitudinal reinforcement
2 x N12@400cts. Omit on
top of clean-out course
N12@400 cts
H = 1400
to 2000
290
N12@400 cts
H = 800
to 1200
K Bars
V Bars
Height of
290mm
blocks
V Bars
V Bars
600
min.
lap
450
min.
lap
SL72 Fabric
SL72 Fabric
250
250
D
SL72 Fabric
300
D
N16@400
N16@400
N16@400
N12@400
N12@400
W
W
B
Fig B10 Construction Guidelines for Reinforced & Core Filled Walls with Base Type 2
Table B4 Design Guidelines for Reinforced & Core Filled Walls with Base Type 2
Wall Height
Total
Height
(mm)
H
800
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
3000
3200
3400
Reinforcement
Height of Blockwork
150
200
300
Series
Series
Series
800
1000
1200
1400
1600
1800
2000
1400
800
1600
800
1600
1000
1800
1000
2000
1000
2000
1200
2000
1400
V-Bars
N12 at 400
N12 at 400
N12 at 400
N16 at 400
N16 at 400
N16 at 400
N16 at 200
N16 at 400
N16 at 400
N20 at 400
N20 at 400
N16 at 200
N20 at 200
N20 at 200
February 2009
K-Bars
N16 at 400
N16 at 400
N20 at 400
N20 at 400
N16 at 200
N16 at 200
N16 at 200
Base Dimensions
Max. 1 in 4
Level Backfill
Sloping Backfill
Heel Width Base Width Heel Depth Base Width Heel Depth
(mm)
(mm)
(mm)
(mm)
(mm)
W
B
D
B
D
450
600
500
800
500
450
800
500
1000
500
450
1000
500
1200
600
450
1200
500
1400
600
450
1400
600
1600
700
450
1600
700
1800
800
600
1800
700
2000
800
600
2000
800
2200
900
600
2200
900
2400
1000
900
2400
900
2600
1000
900
2600
900
2800
1100
900
2800
1000
3000
1200
900
3000
1100
3200
1300
900
3200
1200
3400
1500
B13
Victoria Book 1 B
190
One-course bond
beam with N12 bar
Series 200
blocks
2700 max.
Horizontal
reinforcement,
N12 at 400 cts
Note:
Wall blocks and
reinforcement as
for 'Typical Details'
Vertical
reinforcement:
N16 @400 cts,
central
False wall
Floor slab
reinforcement
Drained cavity
200
55mm
cover
Ag. drain
200
Ag. drain
1000
B14
Victoria Book 1 B
290
190
140
190
Timber floor
Timber floor
One-course
bond beam using
20.20 knock-out block
with 1xN12 bar
65mm cover to
back face
Vertical reinforcement
N16 at 400 cts, central
2700 max.
Natural
soil
Note:
Reinforcement as
for Typical Details
Series 200
blocks
Tanking to
back face
of wall
Horizontal reinforcement,
N12 at 400 cts
65mm cover
to back face
Series 300
blocks
1200
290
False wall
Clean-out
course
Natural
soil
Floor slab
reinforcement
Drained cavity
300
1500
55mm cover
300
Ag. drain
Ag. drain
February 2009
B15
Victoria Book 1 B
Note:
Retaining wall shall be propped prior to
backfilling and remain in place for a
minimum of 7 days after placing floor slab
190
Knock-out block
saw-cut at floor
soffit level
Horizontal
reinforcement,
N12 at 400 cts
Free-draining gravel
Vertical
reinforcement:
N12 at spacing 'S',
centrally placed
Use Double-U or H
blocks for
sub-floor wall
section
Bars
450 lap
Clean-out course
Starter bars,
N12 @ spacing 'S',
centrally placed
450 min.
600 min.
Note:
Footing size and
reinforcement to suit
site conditions
B16
Height H(mm)
Spacing S(mm)
1500
600
400
BORAL MASONRY
Victoria Book 1 C
avf = 0.75 if the member is laterally supported along its top edge.
Structural Adequacy
This governs the wall height, length, thickness and restraints.
Masonry unit suppliers do not control the wall height, length
or restraints, therefore do not control Structural Adequacy.
However, information that is useful in the design of masonry
walls is the maximum Slenderness ratio (Srf). Boral Masonry
provides Srf information for all of its masonry units, and its use
is discussed in more detail later.
Integrity
This is the resistance to the passage of flame or gas. To provide
integrity, masonry walls must be structurally adequate because
cracks that form when it bows can allow flame through the
wall. Since the masonry unit supplier does not control Structural
Adequacy, they cannot control integrity either.
Insulation
This is resistance to the passage of heat. Insulation is governed
by the type and thickness of the material used to produce the
masonry unit. This is controlled by the masonry unit manufacturer.
In relation to FRL, masonry must always provide Insulation to
an equal or better level than is required for Integrity.
C2
Victoria Book 1 C
avf H
t
Srf =
Srf =
0.7
t
avf H ah L
For cavity walls, two thirds of the total thickness can be used
for t, provided that BOTH leaves are restrained in the same
positions (eg: external leaf stops at slab also). If the external
leaf is a veneer to the slab edge, the internal leaf must provide
the Structural Adequacy FRL on its own.
For reinforced masonry, the Srf of 36, from Table 6.1 may be
used. Reinforcement can be horizontal, as bond beams when
spanning between columns. Reinforcement can be vertical, as
filled cores when spanning between slabs. In either case,
reinforcement can be spaced up to 2m apart, depending on
span. This reinforcement stiffens the masonry and resists
bowing. Reinforced walls with Srf < 36 have a 240 minute FRL
for Structural Adequacy.
All calculations should be checked by an engineer. Other loads
may supersede Structural Adequacy requirements.
Srf = ah
L
t
H =
Srf x t
Avf
Avf x H
Srf
February 2009
C3
Victoria Book 1 C
For hollow units (cores > 30%), the material thickness is the
net volume divided by the face area.
For cavity walls, t = the sum of material thicknesses in both
leaves. (not two thirds as for the Structural Adequacy FRL).
C4
Victoria Book 1 C
Step 1
Tables and graphs assume all walls are built on concrete slabs
or broad footings and have adequate restraints. Piers, cavity
walls, freestanding walls, earthquake, wind and other loads are
not addressed in this guide. All fire rated walls should be
designed by a suitably qualified engineer.
Example
eg: 120/60/60
NOTE: For masonry wall design, the FRL for any given wall
must comply with:
Insulation
Integrity
Structural Adequacy
Worked Example
A 6m high, 6m long fire rated, non-loadbearing wall in a 3
storey warehouse. BCA specifies Class 7, Type b Construction.
BCA Section C1.1, Table 4 specifies an FRL 240/240/240.
February 2009
C5
Victoria Book 1 C
Step 2
Worked Example
From Table C1, the following units all achieve 240 minutes
FRL for Insulation:
30
60
240
Material
Product Code/Type*
Yes
Scoria Blend (SB)
Yes
Scoria Blend (SB)
Yes
Scoria Blend (SB)
Yes
Scoria Blend (SB)
Yes
FireLight (FL)
d.t.s..
+render
Ash Grey (AG) & Designer Block
d.t.s..
Ash Grey (AG) & Designer Block
d.t.s..
Ash Grey (AG) & Designer Block
d.t.s..
+render
Ash Grey (AG) & Designer Block
d.t.s..
+render
Grout Filled Masonry 140mm
d.t.s.
Grout Filled Masonry 190mm
d.t.s.
Grout Filled Masonry 290mm
d.t.s. deemed to satisfy. +render = 10mm render both faces
* Product Codes listed are for the Full Size Unit. Fractional size blocks in the same range have the same FRL rating.
15.01SC
15.301; 10.331; 10.383
12.401; 15.401; 15.483; 20.401
Scoria Quick Brick
FireLight Quick Brick
10.01; 10.201
15.01; 15.201
20.01;
Brick B1, Quick Brick Solid or Cored
15.01; 15.42; 15.48
20.01; 20.42; 20.48
30.48
Offers excellent Insulation and Structural Adequacy FRLs for NONLOADBEARING fire rated walls. 10% lighter than Standard Ash
Grey units. Scoria Blend is hard, durable and suitable for paint or
render. Acoustic performance with plasterboard linings is excellent.
Acoustic performance with render is medium range.
C6
Victoria Book 1 C
Step 3
Worked Example
The calculated Srf value for your wall design MUST NOT
EXCEED the value from the accompanying table.
February 2009
Material
Scoria Blend (SB)
Scoria Quick Brick
FireLight
Standard Ash Grey (AG) and Basalt Quick Brick
Designer Block
Reinforced & Grout Filled Masonry
Condition of use
Non loadbearing ONLY
Non loadbearing ONLY
Non loadbearing ONLY
Any
Any
Any
C7
Victoria Book 1 C
IMPORTANT
The following selection graphs are based on Specific
Products manufactured at Victorian Boral Plants.
Should these units be sourced from other plants, the
specification should be checked with the respective
supply plant.
Worked Example
1. Select the appropriate page and graph for the
chosen masonry unit material.
Laterally supported
both ends and top
SUPPORT
SUPPORT
SUPPORT
Structural Adequacy
180 minutes FRL
SUPPORT
Leaf
Thickness
7
6
190mm
5
4
140mm
110mm
90mm
2
1
0
0
Page
60 120
180
240
90
120
60
90
60
90
60 240
60 240
C9
C10
C11
C12
C13
C14
C15
C16
C17
C18
C18
C8
Victoria Book 1 C
Srf = 22.6
SUPPORT
Laterally supported
both ends, top free
190mm
5
140mm
110mm
3
90mm
2
1
0
1
SUPPORT
Laterally supported
one end and top
5
4
3
1
0
0
SUPPORT
6
190mm
5
140mm
110mm
90mm
2
1
0
6
SUPPORT
Leaf
Thickness
6
5
4
3
2
190mm
140mm
110mm
90mm
1
0
0
Laterally supported
one end top free
SUPPORT
Structural Adequacy
60 120 minutes FRL
Leaf
Thickness
190mm
140mm
110mm
90mm
Leaf
Thickness
Structural Adequacy
60 120 minutes FRL
SUPPORT
Leaf
Thickness
SUPPORT
Structural Adequacy
60 120 minutes FRL
SUPPORT
Laterally supported
both ends and top
SUPPORT
SUPPORT
SUPPORT
Structural Adequacy
60 120 minutes FRL
SUPPORT
February 2009
C9
Victoria Book 1 C
Srf = 21.5
SUPPORT
Laterally supported
both ends, top free
6
190mm
5
4
140mm
110mm
90mm
2
1
0
1
SUPPORT
Laterally supported
one end and top
5
4
3
190mm
2
0
0
SUPPORT
6
190mm
5
4
140mm
110mm
90mm
2
1
0
6
C10
SUPPORT
Laterally supported
one end top free
SUPPORT
Structural Adequacy
180 minutes FRL
Leaf
Thickness
140mm
110mm
90mm
Leaf
Thickness
Structural Adequacy
180 minutes FRL
SUPPORT
Leaf
Thickness
SUPPORT
Structural Adequacy
180 minutes FRL
SUPPORT
Laterally supported
both ends and top
SUPPORT
SUPPORT
SUPPORT
Structural Adequacy
180 minutes FRL
SUPPORT
Leaf
Thickness
6
5
4
3
2
190mm
140mm
110mm
90mm
1
0
0
Victoria Book 1 C
Srf = 19.7
SUPPORT
Laterally supported
both ends, top free
190mm
140mm
110mm
90mm
2
1
0
1
SUPPORT
Laterally supported
one end and top
4
3
190mm
2
0
0
SUPPORT
190mm
5
4
140mm
110mm
90mm
2
1
0
6
SUPPORT
Leaf
Thickness
5
4
3
2
190mm
140mm
110mm
90mm
1
0
0
Laterally supported
one end top free
SUPPORT
Structural Adequacy
240 minutes FRL
Leaf
Thickness
140mm
110mm
90mm
Leaf
Thickness
Structural Adequacy
240 minutes FRL
SUPPORT
Leaf
Thickness
SUPPORT
Structural Adequacy
240 minutes FRL
SUPPORT
Laterally supported
both ends and top
SUPPORT
SUPPORT
SUPPORT
Structural Adequacy
240 minutes FRL
SUPPORT
February 2009
C11
Victoria Book 1 C
Srf = 26.9
SUPPORT
Laterally supported
both ends, top free
140mm
110mm
100mm
90mm
3
2
1
0
1
5
4
3
190mm
140mm
110mm
100mm
90mm
1
0
0
SUPPORT
Laterally supported
one end and top
SUPPORT
6
190mm
5
4
140mm
110mm
100mm
90mm
2
1
0
4
C12
SUPPORT
Laterally supported
one end, top free
SUPPORT
Leaf
Thickness
Structural Adequacy
90 minutes FRL
Structural Adequacy
90 minutes FRL
Leaf
Thickness
SUPPORT
Leaf
Thickness
190mm
SUPPORT
Structural Adequacy
90 minutes FRL
SUPPORT
Laterally supported
both ends and top
SUPPORT
SUPPORT
SUPPORT
Structural Adequacy
90 minutes FRL
SUPPORT
Leaf
Thickness
6
5
4
3
2
190mm
140mm
110mm
90/100mm
1
0
0
Victoria Book 1 C
Srf = 24.9
Structural Adequacy
120 minutes FRL
SUPPORT
Laterally supported
both ends, top free
Leaf
Thickness
190mm
6
5
140mm
110mm
100mm
90mm
3
2
1
0
1
6
5
4
3
190mm
2
1
0
0
SUPPORT
Laterally supported
one end and top
SUPPORT
6
190mm
5
4
140mm
110mm
100mm
90mm
2
1
0
4
February 2009
SUPPORT
Laterally supported
one end top free
SUPPORT
Leaf
Thickness
Structural Adequacy
120 minutes FRL
Structural Adequacy
120 minutes FRL
140mm
110mm
100mm
90mm
SUPPORT
SUPPORT
Leaf
Thickness
SUPPORT
Laterally supported
both ends and top
SUPPORT
SUPPORT
SUPPORT
Structural Adequacy
120 minutes FRL
SUPPORT
Leaf
Thickness
6
5
4
3
2
190mm
140mm
110mm
90/100mm
1
0
0
C13
Victoria Book 1 C
(Basalt 45%)
Srf = 22.5
SUPPORT
Laterally supported
both ends, top free
190mm
5
140mm
110mm
90mm
2
1
0
1
SUPPORT
Laterally supported
one end and top
5
4
3
1
0
0
SUPPORT
6
190mm
5
4
140mm
110mm
90mm
2
1
0
6
C14
SUPPORT
Laterally supported
one end, top free
SUPPORT
Structural Adequacy
60 minutes FRL
Leaf
Thickness
190mm
140mm
110mm
90mm
Leaf
Thickness
Structural Adequacy
60 minutes FRL
SUPPORT
Leaf
Thickness
SUPPORT
Structural Adequacy
60 minutes FRL
SUPPORT
Laterally supported
both ends and top
SUPPORT
SUPPORT
SUPPORT
Structural Adequacy
60 minutes FRL
SUPPORT
Leaf
Thickness
6
5
4
3
2
190mm
140mm
110mm
90mm
1
0
0
Victoria Book 1 C
(Basalt 45%)
Srf = 21.0
SUPPORT
Laterally supported
both ends, top free
190mm
5
4
140mm
110mm
90mm
2
1
0
1
SUPPORT
Laterally supported
one end and top
4
3
1
0
0
SUPPORT
190mm
5
4
140mm
110mm
90mm
2
1
0
6
SUPPORT
Leaf
Thickness
5
4
3
2
190mm
140mm
110mm
90mm
1
0
0
Laterally supported
one end, top free
SUPPORT
Structural Adequacy
90 minutes FRL
Leaf
Thickness
190mm
140mm
110mm
90mm
Leaf
Thickness
Structural Adequacy
90 minutes FRL
SUPPORT
Leaf
Thickness
SUPPORT
Structural Adequacy
90 minutes FRL
SUPPORT
Laterally supported
both ends and top
SUPPORT
SUPPORT
SUPPORT
Structural Adequacy
90 minutes FRL
SUPPORT
February 2009
C15
Victoria Book 1 C
Designer Block
Srf = 18.0
SUPPORT
Laterally supported
both ends, top free
5
190mm
4
140mm
3
110mm
90mm
2
1
0
1
SUPPORT
Laterally supported
one end and top
4
3
2
0
0
SUPPORT
5
190mm
4
140mm
3
110mm
90mm
2
1
0
6
C16
SUPPORT
Laterally supported
one end, top free
SUPPORT
Structural Adequacy
60 minutes FRL
Leaf
Thickness
190mm
140mm
110mm
90mm
Leaf
Thickness
Structural Adequacy
60 minutes FRL
SUPPORT
Leaf
Thickness
SUPPORT
Structural Adequacy
60 minutes FRL
SUPPORT
Laterally supported
both ends and top
SUPPORT
SUPPORT
SUPPORT
Structural Adequacy
60 minutes FRL
SUPPORT
Leaf
Thickness
5
4
3
2
190mm
140mm
110mm
90mm
1
0
0
Victoria Book 1 C
Designer Block
Srf = 17.0
SUPPORT
Laterally supported
both ends, top free
5
190mm
4
3
140mm
110mm
90mm
1
0
1
SUPPORT
Laterally supported
one end and top
4
3
2
0
0
SUPPORT
5
190mm
4
3
140mm
110mm
90mm
1
0
6
SUPPORT
Leaf
Thickness
5
4
3
2
190mm
140mm
110mm
90mm
1
0
0
Laterally supported
one end, top free
SUPPORT
Structural Adequacy
90 minutes FRL
Leaf
Thickness
190mm
140mm
110mm
90mm
Leaf
Thickness
Structural Adequacy
90 minutes FRL
SUPPORT
Leaf
Thickness
SUPPORT
Structural Adequacy
90 minutes FRL
SUPPORT
Laterally supported
both ends and top
SUPPORT
SUPPORT
SUPPORT
Structural Adequacy
90 minutes FRL
SUPPORT
February 2009
C17
Victoria Book 1 C
SUPPORT
Walls without restraint to the ends, but with lateral restraint along their top have
maximum heights irrespective of their length as detailed in the following table. (Most
doorways and windows create free ends).
SUPPORT
Material
Thickness
60
Designer Block
240
90mm
2.430
2.430
2.430
2.430
2.364
110mm
2.970
2.970
2.970
2.970
2.889
140mm
3.780
3.780
3.780
3.780
3.677
190mm
5.130
5.130
5.130
5.130
4.991
110mm
2.970
2.970
2.970
2.970
2.970
90mm
2.430
2.430
2.400
2.160
2.040
110mm
2.970
2.970
2.933
2.640
2.493
140mm
3.780
3.780
3.733
3.360
3.173
190mm
5.130
5.130
5.067
4.560
4.307
90mm
2.160
2.040
1.920
1.860
1.800
140mm
3.360
3.173
2.987
2.893
2.800
190mm
4.560
4.307
4.053
3.927
3.800
140mm
5.040
5.040
5.040
5.040
5.040
190mm
6.840
6.840
6.840
6.840
6.840
*Governed by Robustness. Can be higher if supporting a slab. These heights can be exceeded when one or both ends are restrained as well as the top.
Structural Adequacy
60 240 minutes FRL
Structural Adequacy
60 240 minutes FRL
Maximum
Wall Height
(metres)
SUPPORT
Steel
Core Fill
Spacing (metres)
Leaf
Thickness
(mm)
4.000
N12
5.040
N16
4.800
Maximum
Wall Length
(metres)
140
N12
6.400
6.840
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Steel
Bond Beam
Spacing (metres)
Leaf
Thickness
(mm)
4.000
N12
140
140
5.040
N16
140
190
4.800
N12
190
N16
190
6.400
N16
190
N16
190
6.840
N16
190
C18
BORAL MASONRY
Victoria Book 1 D
D2
Victoria Book 1 D
Sound Insulation
Any wall system that separates one dwelling from another,
or that separates one room from another, should be selected
to provide a sufficient level of insulation against noise.
There are two types of noise transfer through partitions,
airborne transfer, and structure-borne transfer. Both may need
to be considered in order to achieve the desired result.
Noise sources, such as voices, televisions and musical
instruments, generate noise in the air in one room, and this
noise passes through the partition and into the room on the
other side. This is known as airborne noise.
As we know, some partitions are better than others at
isolating airborne noise. In order to simply compare the
isolating performance of partitions Rw rating was developed.
A partition with a high Rw rating isolates sound better than a
partition with a low Rw rating. If we compare two partitions,
and one has an Rw which is 10 rating points higher, then
the noise passing through the wall with the higher Rw will
be about half the loudness when compared with the noise
passing through the wall with the lower Rw.
The Rw ratings are obtained from tests carried out in
certified laboratories, under controlled conditions. When
identical partitions are part of buildings and tested insitu, it is often found that the actual Rw rating obtained,
usually called the Weighted Standardised Level Difference
February 2009
D3
Victoria Book 1 D
Rw 50
Unit to unit
Rw + Ctr 50
The larger the value of the WIIC the better the impact insulation.
D4
Installation
Victoria Book 1 D
Noise Flanking
Through ventilation
and service ducts
Through
ceilings and the
above ceiling
cavity
Through
perimeter joints
between the wall
and floor, or the
wall and ceiling
(or underside of
the floor slab) or
wall junctions
Through back to
back cupboards
Through light
switches, or GPO's,
located in the wall,
poor sealing at
penetrations
Through floors
and the below
floor crawl
space
Through shared building elements such as floor boards, floor
joists, continuous plasterboard walls, continuous plasterboard
ceilings, and even continuous concrete walls and floors
February 2009
D5
Victoria Book 1 D
Doors
Hollow, cored and even solid doors generally provide
unsatisfactory sound insulation between rooms. Doors can
also provide direct air leaks between rooms thus having a
bad effect on the overall sound insulation of the partition
in which they are inserted. The higher the insulation of the
partition, the worse is the effect of doors.
Where sound insulation is important, specialised
heavyweight doors or, preferably, two doors separated by
an absorbent lined airspace or lobby should be used.
Noise paths
through vents
or lightweight
decorative panels
Appliances
In cases where sound insulation is important, noise
producing fixtures or appliances such as water closets,
cisterns, water storage tanks, sluices, dishwashers, washing
machines and pumps should be repositioned or isolated from
the structure with resilient mountings and flexible service
leads and connections.
Where fittings are duplicated on opposite sides of partitions,
they should be offset.
Noise paths
through lightweight
panel doors
Noise paths
through vents
Noise paths
through gaps
D6
BORAL MASONRY
Victoria Book 1 E
Product Introduction
and Application
Information
Product Specific
Acoustic Test Results
and Wall Lining System
Information
Product Identification
Victoria Book 1 E
E12
FireLight Quick Brick (FL)
162
162
110
110
INTRODUCTION
INTRODUCTION
Boral
Boral Masonry
Masonry Victoria
Victoria is
is constantly
constantly
developing
developing new
new and
and innovative
innovative
products.
FireLight
Quick
Brick
products. FireLight
Quick
Brick
(FL)
(FL)
utilises
a unique
low-density
utilises
a unique
low-density
blended
blended
which
concrete concrete
material material
which provides
provides
high
fire
rated
performance
high fire rated performance together
together
with minimum
with minimum
weight. weight.
230
230
FireLight
FireLight Quick
Quick Brick
Brick (FL)
(FL)
FireLight
FireLight Quick
Quick Brick
Brick is
is ideal
ideal for
for
non-loadbearing
non-loadbearing applications
applications such
such
as
as walls
walls in
in concrete
concrete framed
framed office
office
buildings
and
high-rise
buildings and
high-rise
home home
units.
units.
FireLight Quick Brick is 230mm long
FireLight
Brick
230mm
by 162mm Quick
high, equal
to 2iscourses
of
long
by 162mm
high,
equal
to 2
standard
brick with
mortar,
making
courses
of standard
brick
them a highly
efficient
and with
costmortar,
making them
a highly
effective construction
component.
efficient and cost-effective
construction component.
FIRE
FIRE DESIGN
DESIGN
CONSIDERATIONS
CONSIDERATIONS
FireLight
Quick Brick
Brick is
is aa fire
FireLight Quick
fire tested
tested
lightweight
lightweight concrete
concrete which
which is
is unique
unique
to
to Boral,
Boral, and
and provides
provides excellent
excellent fire
fire
rating
characteristics.
rating characteristics.
ACOUSTIC
ACOUSTIC DESIGN
DESIGN
CONSIDERATIONS
CONSIDERATIONS
FireLight
is not
FireLight Quick
Quick Brick
Brick is
not
recommended
for cement
recommended for
cement rendered
rendered
acoustic
acoustic walls,
walls, but
but gives
gives excellent
excellent
sound
sound resistance
resistance with
with aa wide
wide variety
variety
of
tested board-lining
board-liningsystems.
systems.
of tested
The
The 1st
1st test
test on
on page
page E13
E13 qualifies
qualifies
for
vent shafts
shafts in
in aa
for walls
walls enclosing
enclosing vent
40.
habitable
room:RRww++CCtrtr40.
habitable room:
The
The 3rd
3rd test
test qualifies
qualifies for
for unit-tounit-to50.
corridor
walls:RRw50.
corridor walls:
w
The
The 4th,
4th, 5th
5th and
and 6th
6th tests
tests qualify
qualify
for
f o r unit-to-unit
u n i t - t o - u n i t walls
w a l l s where
where
+C
50 and impact ratings
R
Rw
w + Ctr
tr 50 and impact ratings
are
are required
required and
and can
can also
also be
be used
used
in
dry-to-dry,wet-to-dry
wet-to-dryand
and
wetin dry-to-dry,
wet-toto-wet
areas.
wet areas.
Availability
information
for your
region/state
PAGE
BOOK
PAGE
BOOK
Victoria Book 1 E
E13
WALL LINING
LINING
WALL
Boral Test
Test N
N
Boral
45
45
(-1, -5)
-5)
(-1,
T621-05s33
T621-05s33
47
47
(-1, -6)
-6)
(-1,
T621-05s32
T621-05s32
51
51
(-2, -8)
-8)
(-2,
T621-05s31
T621-05s31
60
60
(-3, -9)
(-3, -9)
T621-05s30
T621-05s30
IIC
IIC
62
62
13mm Boral
Boral Plasterboard
Plasterboard daub
daub fixed
fixed
11 xx 13mm
at 500mm
500mm centres.
centres.
at
Suits vents
vents in
in habitable
habitable rooms.
rooms.
Suits
Rw ++ ctr
ctr == 40
40
Rw
WALL LINING
LINING
WALL
126mm
126mm
13mm Boral
Boral Plasterboard
Plasterboard daub
daub fixed
fixed
11 xx 13mm
at 500mm
500mm centres
centres
at
13mmBoral
BoralPlasterboard
Plasterboarddaub
daubfixed
fixed
11xx13mm
at500mm
500mmcentres
centres
at
142mm
142mm
13mm Boral
Boral Plasterboard
Plasterboard daub
daub fixed
fixed
11 xx 13mm
at 500mm
500mm centres
centres
at
13mmBoral
BoralPlasterboard
Plasterboardscrew
screwfixed
fixed
11xx13mm
28mmfurring
furringchannel
channelatat600mm
600mmcentres
centres
28mm
Standard Clips
Wall Cross
section Icon
and Overall
System
Thickness
(-4, -12)
(-4, -12)
Option based
Option based
on Test T621on Test T62105s25
05s25
IIC
IIC
63
63
(-4, -11)
(-4, -11)
T621-05s29
T621-05s29
IIC
IIC
110mm
110mm
LIGHTWEIGHT
LIGHTWEIGHT
QUICK BRICK
BRICK (FL)
(FL)
QUICK
250mm
250mm
Availability
Availability
Specifications
Specifications
Rw (Estimate or *Tested)
Maximum Slenderness Ratio (Srf)
Rw (Estimate or *Tested)
Maximum Slenderness Ratio (Srf)
With Lining System
N
N
Insulation (minutes)
With Lining System
N
N
Insulation (minutes)
FRL (minutes)
per
per
FRL (minutes)
per
per
m22 Pallet 60
90
120 180 240
IIC
m Pallet 60
90
120 180 240
IIC
24.2 250
29
26.9 24.9 22.2 20.3
47
54
58
56
60
24.2 250
29
26.9 24.9 22.2 20.3
47
54
58
56
60
120
120
Refer
to Lining Systems on Page E3. IIC = Complies with BCA requirement for Impact Sound Resistance.
Refer to Lining Systems on Page E3. IIC = Complies with BCA requirement for Impact Sound Resistance.
= Quantity may vary from plant to plant.
= Quantity may vary from plant to plant.
Product
Product
Code
TxLxH (mm)
Code
TxLxH (mm)
FireLight 110x230x162
FireLight 110x230x162
Quick Brick (FL)
Quick Brick (FL)
E12
uc
uc
MPa
MPa
3
3
Unit
Unit
Wt
Wt
kg
kg
4.5
4.5
Fire Performance
Data
Acoustic
Performance
Data
IMPACT SOUND RESISTANCE IIC = Systems comply with BCA requirements for IMPACT SOUND RESISTANCE.
IMPACT SOUND RESISTANCE IIC = Systems comply with BCA requirements for IMPACT SOUND RESISTANCE.
February 2009
Acoustic Test
Result (Rw) and
Impact Isolation
Information (IIC)
E13
Product
Specifications
E2
Victoria Book 1 E
WALL LINING
Refer to
product pages
BORAL MASONRY
BRICK OR BLOCK
WALL LINING
13mm Render
Masonry
Thickness
+26mm
Masonry
Thickness
+32mm
Masonry
Thickness
+71mm
Masonry
Thickness
+84mm
or
+77mm
13mm Render
Masonry
Thickness
+98mm
Masonry
Thickness
Acousti
+127mm
c Estim
ate
s with
these L
ining
System
PAGE
BOOK
Victoria Book 1 E
E4
Fire Rated
Rated Block
Block -- Scoria
Scoria Blend
Blend (SB)
(SB)
Fire
Series 100,
100, 120,
120, 150
150 &
& 200
200
Series
INTRODUCTION
INTRODUCTION
Fire Rated
Rated Block
Block (SB)
(SB) is
is manufactured
manufactured
Fire
from aa scoria-blend
scoria-blend material
material which
which
from
reduces the
the block
block weight
weight and
and increases
increases
reduces
the fire
fire performance
performance characteristics.
characteristics.
the
Fire Rated
Rated Block
Block (SB)
(SB) is
is ideal
ideal for
for nonnonFire
loadbearing walls
walls of
of commercial,
commercial,
loadbearing
industrial and
and high-rise
high-rise buildings
buildings
industrial
with concrete
concrete and
and portal
portal framed
framed
with
structures.
structures.
Fire Rated
Rated Block
Block (SB)
(SB) is
is also
also suitable
suitable
Fire
for loadbearing
loadbearing walls,
walls, however
however the
the S
Srf
rf
for
values from
from Designer
Designer Block
Block masonry
masonry
values
units apply.
apply. Refer
Refer to
to Section
Section C
C of
of this
this
units
guide for
for more
more information.
information.
guide
Fire Rated
Rated Block
Block (SB)
(SB) is
is manufactured
manufactured
Fire
in 90,
90, 110,
110, 140
140 and
and 190mm
190mm thicknesses
thicknesses
in
to suit
suit most
most types
types of
of fire
fire and/or
and/or acoustic
acoustic
to
wall construction.
construction.
wall
FIRE DESIGN
DESIGN CONSIDERATIONS
CONSIDERATIONS
FIRE
Fire Rated
Rated Block
Block (SB)
(SB) utilises
utilises aa
Fire
unique scoria-blend
scoria-blend material,
material, which
which
unique
has been
been shown
shown through
through fire
fire testing
testing
has
to provide
provide excellent
excellent fire
fire insulation
insulation
to
characteristics.
characteristics.
Please refer
refer to
to the
the fire
fire performance
performance
Please
characteristics in
in the
the specifications
specifications
characteristics
table.
table.
Availability
Availability
ACOUSTIC DESIGN
DESIGN
ACOUSTIC
CONSIDERATIONS
CONSIDERATIONS
Fire Rated
Rated Block
Block (SB)
(SB) provides
provides excellent
excellent
Fire
sound resistance
resistance with
with aa wide
wide variety
variety of
of
sound
board-lining systems.
systems.
board-lining
Please refer
refer to
to the
the acoustic
acoustic performance
performance
Please
characteristics in
in the
the specifications
specifications
characteristics
table.
table.
FRACTIONAL SIZE
SIZE BLOCKS
BLOCKS
FRACTIONAL
Boral Masonry
Masonry Victoria
Victoria manufactures
manufactures
Boral
an extensive
extensive range
range of
of special
special purpose
purpose
an
blocks and
and fractional
fractional size
size blocks
blocks to
to
blocks
complement the
the products
products detailed
detailed on
on
complement
this
page.
Please
refer
to the
the Boral
Boral
this page. Please refer to
Block &
& Brick
Brick Guide
Guide (MDG
(MDG Book
Book 2)
2) for
for
Block
additional information.
information.
additional
Specifications
Specifications
Product
Product
Code
Code
uc
uc
MPa
MPa
8
8
Unit
Unit
Wt
Wt
kg
kg
N
N
per
per
m22
m
13.1
13.1
25
25
Rw (Estimate
(Estimate or
or *Tested)
*Tested)
Maximum Slenderness
Slenderness Ratio
Ratio (S
(Srf))
Maximum
R
w
rf
With Lining
Lining System
System
Insulation (minutes)
(minutes)
N
With
Insulation
N
FRL (minutes)
(minutes)
per
FRL
per
Pallet 60
60
90
120 180
180 240
240
IIC
Pallet
90
120
IIC
139 22.6
22.6 22.6
22.6 22.6
22.6 21.5
21.5 19.7
19.7 46
46 48
48 53
53 58
58 56
56 59
59
139
180
180
10.331
10.331
Type
Type
Full Solid
Solid
Full
10.383
10.383
Half Height
Height
Half
12.401
12.401
Full Cored
Cored
Full
8
8
12.5
12.5
12.5
12.5
120
120
22.6
22.6
21.5
21.5
19.7
19.7
45
45
46
46
50
50
55
55
53
53
56
56
15.01SC
15.01SC
Full Hollow
Hollow
Full
8
8
11.1
11.1
12.5
12.5
120
120
22.6
22.6
22.6
22.6
120
120
22.6
22.6
21.5
21.5
19.7
19.7
46
46
47
47
52
52
57
57
55
55
58
58
15.301
15.301
Full Hollow
Hollow
Full
8
8
12.6
12.6
12.5
12.5
120
120
22.6
22.6
22.6 22.6
22.6
22.6
180
180
21.5
21.5
19.7
19.7
48
48
49
49
54
54
59
59
57
57
60
60
15.401
15.401
Full Hollow
Hollow
Full
8
8
14.3
14.3
12.5
12.5
120
120
21.5
21.5
19.7
19.7
15.483
15.483
Half Height
Height
Half
8
8
9.3
9.3
25
25
192
192
22.6
22.6
22.6
22.6
22.6
22.6
21.5
21.5
19.7
19.7
48
48
49
49
54
54
59
59
57
57
60
60
20.401
20.401
Full Hollow
Hollow
Full
8
8
15.3
15.3
12.5
12.5
90
90
22.6
22.6
22.6
22.6
240
240
22.6
22.6
240
240
21.5
21.5
19.7
19.7
48
48
49
49
54
54
59
59
57
57
60
60
8
8
6.0
6.0
12.5
12.5
234
234
22.6
22.6
22.6
22.6
22.6
22.6
22.6
22.6
180
180
22.6 22.6
22.6
22.6
240
240
22.6
22.6
22.6
22.6
240
240
21.5
21.5
19.7
19.7
46
46
48
48
48
48
49
49
53
53
54
54
58
58
59
59
56
56
57
57
59
59
Read off
Acoustic
Performance
(Rw) from
intersection
of product
row and
lining system
column
60
60
Refer to
to Lining
Lining Systems
Systems on
on Page
Page E3.
E3.
Refer
IIC == Complies
Complies with
with BCA
BCA requirement
requirement for
for Impact
Impact Sound
Sound Resistance.
Resistance.
IIC
== Quantity
Quantity may
may vary
vary from
from plant
plant to
to plant.
plant.
E4
February 2009
E3
Victoria Book 1 E
Availability
ACOUSTIC DESIGN
CONSIDERATIONS
Fire Rated Block (SB) provides excellent
sound resistance with a wide variety of
board-lining systems.
Please refer to the acoustic performance
characteristics in the specifications
table.
FRACTIONAL SIZE BLOCKS
Boral Masonry Victoria manufactures
an extensive range of special purpose
blocks and fractional size blocks to
complement the products detailed on
this page. Please refer to the Boral
Block & Brick Guide (MDG Book 2) for
additional information.
Specifications
Maximum Slenderness Ratio (Srf)
Insulation (minutes)
N
FRL (minutes)
per
Pallet 60
90
120 180 240
uc
MPa
Unit
Wt
kg
N
per
m2
Full Solid
13.1
25
139
22.6
22.6
Half Height
6.0
12.5
234
22.6
22.6
Product
Code
Type
10.331
10.383
22.6
Rw (Estimate or *Tested)
With Lining System
IIC
21.5
19.7
46
48
53
58
56
59
21.5
19.7
46
48
53
58
56
59
21.5
19.7
45
46
50
55
53
56
22.6
21.5
19.7
46
47
52
57
55
58
22.6
21.5
19.7
48
49
54
59
57
60
21.5
19.7
48
49
54
59
57
60
21.5
19.7
48
49
54
59
57
60
21.5
19.7
48
49
54
59
57
60
180
22.6
180
12.401
Full Cored
12.5
12.5
120
22.6
22.6
22.6
240
15.01SC
Full Hollow
11.1
12.5
120
22.6
22.6
15.301
Full Hollow
12.6
12.5
120
22.6
22.6
15.401
Full Hollow
14.3
12.5
120
22.6
22.6
120
180
22.6
240
15.483
Half Height
9.3
25
192
22.6
22.6
22.6
240
20.401
Full Hollow
15.3
12.5
90
22.6
22.6
22.6
240
E4
Victoria Book 1 E
Series 120
Half Height Solid
Full Height
190
190
90
90
390
390
90
12.401
Full
(1 in every 5 blocks is
universal solid)
10.383
Half Height
10.331
Full Solid
390
110
Series 150
Full Height
Full Height
Thick Wall
190
140
390
190
190
390
140
15.01SC
Full
140
15.401
Full
15.301
Full
390
90
140
390
15.483
Half Height
Series 200
Full Height
190
190
390
20.401
Full
February 2009
E5
Victoria Book 1 E
Availability
Please refer to the Boral Masonry Blocks & Bricks
Guide (MDG Book 2) for detailed availability
information on these products.
ACOUSTIC DESIGN
CONSIDERATIONS
Standard Ash Grey (AG) being of a
relatively dense material provide
inherent sound resistance. This
performance may be sufficient for many
applications without enhancement.
Where higher performance is required,
the addition of render is effective while
board-lining systems using furring
systems and Boral Impact Clips or
plasterboard on light-weight studs
and polyester insulation materials
can provide high acoustic insulation.
Please refer to acoustic test/ estimate
data for appropriate systems.
FRACTIONAL SIZE BLOCKS
Boral Masonry Victoria manufactures
an extensive range of special purpose
blocks and fractional size blocks to
complement the products detailed on
this page.
Specifications
uc
MPa
Unit
Wt
kg
N
per
m2
Product
Code
Type
10.01
10.201
10.31
Full Hollow
Full Hollow
Solid
10
10
10
11.6
10.1
14.3
12.5
14.5
12.5
149
172
139
22.5
21
60
60
12.01
Full Hollow
10
14.0
12.5
120
22.5
21
20
21
20
18
17
Rw (Estimate or *Tested)
With Lining System
IIC
46
46
52
57
55
58
47
47
53
58
56
59
18
17
46
46
52
57
55
58
20
18
17
47
47
53
58
56
59
21
20
18
17
48
48
54
59
57
60
36.0
53
51
58
63
61
64
90
15.01
15.201
Full Hollow
Full Hollow
10
10
13.0
11.0
12.5
14.5
120
120
22.5
20.01
Full Hollow
10
15.9
12.5
90
22.5
15.48
Core Filled
& reinforced
15
13.9
12.5
120
36.0
36.0
36.0
36.0
20.48
Core Filled
& reinforced
15
14.7
12.5
90
36.0
120
36.0
36.0
36.0
36.0
56
55
62
67
65
68
Core Filled
& reinforced
15
36.0
240
36.0
36.0
36.0
59
59
66
71
69
72
60
90
30.48
18.3
12.5
60
36.0
240
Refer to Lining Systems on Page E3. IIC = Complies with BCA requirement for Impact Sound Resistance.
Additional Insulation with Lining System (13mm render both sides). = Quantity may vary from plant to plant.
E6
Victoria Book 1 E
Series 120
Back-up
190
190
162
390
390
Full Height
90
390
90
90
10.01
Full
10.201
Full
10.31
Full Solid
Back-up
190
110
390
12.01
Full
(1 in every 5 blocks is universal
solid)
Series 150
Full Height
190
190
162
140
390
390
140
15.01
Full
140
15.201
Full
390
15.48
H Block
Series 200
Full Height
190
190
390
190
390
190
20.01
Full
20.48
H Block
Series 300
Core Fill Block
190
290
390
30.48
H Block
February 2009
E7
Victoria Book 1 E
BORAL CONCRETE-BASALT
QUICK BRICK
Quick Brick (Victoria only) is 230mm
long by 162mm high, equal to 2 courses
of standard brick with mortar, making
them a highly efficient and costeffective construction component.
FIRE DESIGN CONSIDERATIONS
These products are manufactured from
a Concrete-Basalt blend which provides
good fire performance characteristics
in loadbearing conditions.
Please refer to the fire performance
characteristics in the specifications
table.
ACOUSTIC DESIGN
CONSIDERATIONS
The mass of the Concrete-Basalt
material is 7% heavier than Clay
therefore walls from Concrete-Basalt
products perform slightly better.
Its texture is coarser and its porosity is
higher than Clay, so it performs better
with plasterboard, particularly when
daub-fixed.
Please refer to acoustic test/estimate
data in this guide for appropriate
systems.
Availability
No minimum order quantities apply.
Lead time 0-2 weeks.
Specifications
Unit
Wt
kg
N
per
m2
Product
Code
TxLxH (mm)
uc
MPa
B1 Brick
110x230x76
12
3.8
48.4
450
22.5
12
7.9
24.2
250
22.5
12
8.9
24.2
200
22.5
21.0
20.0
21.0
20.0
21.0
20.0
Rw (Estimate or *Tested)
With Lining System
IIC
18.0
17.0
48
46
51
59
57
60
18.0
17.0
48
46
51*
59
57
60
18.0
17.0
48
46
51
59
57
60
90
90
90
Additional Insulation with Lining System (13mm render both sides).
Refer to Lining Systems on Page E3. IIC = Complies with BCA requirement for Impact Sound Resistance.
E8
Victoria Book 1 E
162
76
230
110
110
Brick (B1)
230
110
230
WALL LINING
Boral Test N
110mm
QUICK BRICK (B)
(CORED)
WALL LINING
46
1 x 13mm Boral Plasterboard daub fixed
48
13mm Render
13mm Render
Opinion
136mm
49
(-2, -8)
RMIT
1211/705
51
(-3, -9)
RMIT
1211/706
52
(-5, -12)
RMIT
1211/708
57
(-4, -11)
RMIT
1211/707
220mm
IMPACT SOUND RESISTANCE IIC = Systems comply with BCA requirements for IMPACT SOUND RESISTANCE.
February 2009
E9
Victoria Book 1 E
162
110
INTRODUCTION
Boral Masonry Victoria is constantly
developing new and innovative
products. Scoria Quick Brick (SB)
utilises a unique low-density
blended concrete material which
provides high fire rated performance
together with minimum weight.
230
FIRE DESIGN
CONSIDERATIONS
Scoria Quick Brick is a fire
tested lightweight concrete
which is unique to Boral, and
provides excellent fire rating
characteristics.
ACOUSTIC DESIGN
CONSIDERATIONS
Scoria Quick Brick is not
recommended for cement rendered
acoustic walls, but gives excellent
sound resistance with a wide variety
of tested board-lining systems.
The 2nd test on page E11 qualifies
for walls enclosing vent shafts in a
habitable room: Rw + Ctr 40.
The 3rd test qualifies for unit-tocorridor walls: Rw 50.
The 4th and 5th tests qualify for unitto-unit walls where Rw + Ctr 50
and impact ratings are required.
Availability
No minimum order quantities apply.
Lead time 0-2 weeks.
Specifications
Product
Code
TxLxH (mm)
Scoria
110x230x162
Quick Brick (SB)
uc
MPa
Unit
Wt
kg
N
per
m2
5.9
24.2
22.6
22.6
22.6
21.5
19.7
Rw (Estimate or *Tested)
With Lining System
IIC
47
48*
56
59
57
60
240
IIC = Complies with BCA requirement for Impact Sound Resistance.
E10
Victoria Book 1 E
WALL LINING
48
110mm
QUICK BRICK (SB)
(-1, -6)
T621-05S22
WALL LINING
47
(-1, -6)
T621-05S21
55
(-4, -10)
T621-05S20
169mm
61
(-4, -11)
T621-05S19
IIC
62
(-4, -10)
T621-05S17
IIC
IMPACT SOUND RESISTANCE IIC = Systems comply with BCA requirements for IMPACT SOUND RESISTANCE.
February 2009
E11
Victoria Book 1 E
162
110
230
INTRODUCTION
Boral Masonry Victoria is constantly
developing new and innovative
products. FireLight Quick Brick (FL)
utilises a unique low-density blended
concrete material which provides
high fire rated performance together
with minimum weight.
FIRE DESIGN
CONSIDERATIONS
ACOUSTIC DESIGN
CONSIDERATIONS
Availability
No minimum order quantities apply.
Lead time 0-2 weeks.
Specifications
Product
Code
TxLxH (mm)
FireLight 110x230x162
Quick Brick (FL)
uc
MPa
Unit
Wt
kg
N
per
m2
4.5
24.2
250
29
26.9
24.9
22.2
20.3
Rw (Estimate or *Tested)
With Lining System
IIC
47
54
58
56
60
120
IIC = Complies with BCA requirement for Impact Sound Resistance.
E12
Victoria Book 1 E
WALL LINING
Boral Test N
45
(-1, -5)
T621-05s33
47
(-1, -6)
T621-05s32
51
(-2, -8)
T621-05s31
110mm
LIGHTWEIGHT
QUICK BRICK (FL)
126mm
169mm
60
(-3, -9)
T621-05s30
IIC
62
(-4, -12)
Option based
on Test T62105s25
IIC
63
(-4, -11)
T621-05s29
IIC
WALL LINING
229mm
250mm
244mm
IMPACT SOUND RESISTANCE IIC = Systems comply with BCA requirements for IMPACT SOUND RESISTANCE.
February 2009
E13
Victoria Book 1 E
Acousticell
190
INTRODUCTION
Boral Acousticell is a purpose
designed block which combines
excellent acoustic absorption
and sound transmission loss
characteristics.
Boral Acousticell has been
successfully integrated into a wide
variety of industrial and commercial
acoustic applications, providing
both acoustic performance and
unique and attractive aesthetic
qualities.
390
140
Acousticell
Full
Availability
Essential Colours
Alabaster
Almond
Pearl Grey
Charcoal
Natural Grey
SOUND ABSORPTION
Boral Acousticell blocks combine
the high transmission loss
characteristics generally associated
with a dense, non-porous material
(concrete block) with efficient
absorption of sound, resulting in
a very low radiated sound level
and effective control of both high
frequencies and troublesome low
frequency noise. Boral Acousticell
blocks provide maximum absorption
in the frequency range of 80Hz to
500Hz, peaking at 1.0 at 200Hz
and providing absorption of 0.6 at
100Hz.
Where high frequency noise is to be
absorbed, fibreglass insulation pads
can be inserted into the Helm-Holtz
cells. In this case, absorption of low
frequency noise drops slightly, but
absorption of other frequencies
improves. (Note: Fibreglass is not
suitable for external use. Carbon
fibre pads are more suitable in
external situations).
Refer to accompanying absorption
graph for application results.
COLOURS
Boral Acousticell Block is Madeto-Order and can therefore be
manufactured in any of the Boral
Designerblock colours. Minimum
order quantities apply to all
colours.
Accent Colours
Sandune
Rust
E14
Paperbark
Wilderness
Terrain
Midway
Specifications
Code
Product Description
150mm
Acousticell Full
MPa
Wt kg
N /Pallet
10
14.0
120
Victoria Book 1 E
50
40
70
20
60
10
0
125
250
1K
500
2K
5K
60
50
40
30
20
10
4
2K
4K
8K 16K 32K
Sound Absorption
0.9
0.7
0.6
0.5
0.4
0.3
0.2
0.1
4
0.8
16
31.5
63
125
250
500
1K
2K
4K
8K
February 2009
E15
Technical Enquires
Specifier Line
Internet
ACT
South Australia
Queensland
Cairns
Townsville
Mackay
North Queensland:
Acousticell, Designer Block and FireLight are registered trademarks of Boral Masonry.
Keystone and Gardenwall are each registered trademarks of Keystone Retaining Wall Systems, Inc.
under licence by Boral Masonry Limited. ABN 13 000 223 718
Boral Masonry - all rights reserved 2004.