Professional Documents
Culture Documents
A Technical Report on
___________________________________________________________________
Prepared by:
Institute of Integrated Electrical
Engineers, Inc. (IIEE) Standards Committee 2011
Prepared by:
IIEE Standards Committee
March 19, 2011
Disclaimer
It is not the intention of this paper to endorse over another the compared short-circuit
calculations and standards.
All discussions in this report are based on the featured system one line diagram only. The
same parameters were considered for the American National Standards Institute/Institute of
Electrical and Electronics Engineers (ANSI/IEEE) and the International Electro-technical
Commission (IEC) calculations for result comparison. The values of these parameters,
however, may vary from every project in terms of available utility short circuit levels, power
system configuration, wiring method and all applicable factors to consider.
IIEE and this Committee will not be responsible for any disputes that may arise out of
referencing from this paper.
ii
Preface
This technical report focuses on two of the most widely used short circuit calculation
methods and standards/guidelines namely: American National Standards Institute/Institute of
Electrical and Electronics Engineers (ANSI/C37/IEEE std 551) and the International Electrotechnical Commission (IEC 60909). To fully understand the analytical techniques of short
circuit current analysis in industrial and commercial power system using both methods, a
representative network model was exemplified and a comprehensive comparison between the
two calculation methods was presented. For expediency, a short circuit calculating software
was employed and the results were presented and evaluated at the end of the analysis.
This technical report provides information and inculcates awareness to electrical practitioners
in the country on the difference in the procedure of short circuit calculations and its
implication between the standards cited. It is not intended to show the detailed short circuit
current calculation for both methods. The reader is still recommended to consult technical
books for reference on a complete and accurate calculation procedure.
This paper starts off with a brief introduction on the current scenario in the Philippines and
the importance of short circuit calculation in Chapter I and expounds on its basic principle in
Chapter II. The equivalent short circuit schematic diagram is also available for analysis in
simple calculation.
Chapter III discusses the asymmetry current application focusing on the importance of
determining the total available short circuit current in the design of electrical equipment such
as circuit breakers, switches, transformers and fuses that are subjected to fault current.
Chapter IV shows the different components in determining the short circuit calculation based
on the two standard/guidelines, the ANSI/IEEE and the IEC. This is followed by Chapter V
presenting the comparative matrix on both standards Calculation Method and Multiplying
Factors with reference to the X/R ratio.
Chapter VI clearly tabulates a comparison between the standards parameters particularly the
device type, device capability and the calculated short circuit duty.
In Chapter VII, an illustration of a sample network was configured consisting of two power
transformers connected to a 13.2 kV bus wherein two different results from the ANSI/IEEE
and IEC calculations were generated with the aid of short circuit calculating software.
Chapter VIII presents the protective devices selection and evaluation focusing on the X/R
ratio for breaker evaluation and on the short circuit test parameters while Chapter IX
discusses the findings and results of the ETAP Total Bus Fault Short Circuit Study. The
tables on the short circuit calculation clearly show the difference in values for the same
parameters between ANSI/IEEE and IEC.
This technical report was developed through the initiative of the IIEE Standards Committee.
Any concern or contention as to its applicability, accuracy and completeness shall be
addressed to the Institute of Integrated Electrical Engineers of the Philippines, Inc. for further
validation and interpretation.
iii
Participants
The following are the working group members of the Institute of Integrated Electrical Engineers of the
Philippines, Inc. (IIEE) under the Standards Committee:
Chairman:
Gem J. Tan
Fuji-Haya Audit Inspection and Maintenance Corporation
Members:
Arjun G. Ansay
Technological University of the Philippines Manila
Jesus C. Santos
JC Santos and Associates
Arturo M. Zabala
AC-DC-KV and Associates
Marites R. Pangilinan
LJ Industrial Fabrication, Inc.
Edwin V. Pangilinan
Total Power Box Solution, Inc.
Roderick T. Khu
Airnergy and Renewables, Inc.
Frumencio T. Tan
Safety Consultant
Samson D. Paden
Department of Trade and IndustryBureau of Product Standards
Genesis A. Ramos
Department of Energy
Vincent E. Jimenez
Delta Power Engineering and Consulting
Gideon S. Tan
Yu Eng Kao Electrical Supply and Hardware, Inc.
Wilson T. Yu
Standards Committee Member
Jaime S. Jimenez
Meralco
Advisers:
Arthur A. Lopez
Private Consultant
IIEE former president - year 2000
Willington K.K.C. Tan
Columbia Wire and Cable Corporation
IIEE former president - year 1990
Approved by the members of the IIEE Board of Governors on March 19, 2011:
Armando R. Diaz, President
iv
Table of Contents
Chapter
Title
Page
I.
Introduction
II.
1
1
2
III.
IV.
V.
Calculation Comparison
Table 1 : Comparison Matrix of ANSI/IEEE and IEC
3
4
VI.
5
5
5
5
VII.
6
6
7
16
23
VIII.
26
26
27
IX.
27
27
27
X.
28
XI.
References
29
Appendix
ABB MCB S200 Technical Features
30
I.
Introduction
In the emerging world market place, Electrical Engineers should be familiar with the basic differences between the
American National Standards Institute (ANSI) and the International Electro-technical Commission (IEC) with
regards to short circuit current calculation procedures. Both the ANSI and the IEC Standards developed these
procedures to provide rating for electrical equipment. These two standards are currently being applied by the
electrical practitioners in the Philippines and it is important to determine the differences between these standards
so that a more logical evaluation and breaker rating selection can be appropriated. IEC procedure requires
significantly more detailed modeling of the power system short circuit contribution than ANSI.
A short circuit calculation is an important task undertaken by a professional in power systems planning and
operation. Circuit breaker and switchgear selection, protection settings and coordination require a comprehensive,
detailed and accurate short-circuit calculation. The report focuses on the guidelines found in the following shortcircuit standards: the North American ANSI/IEEE standard and its European counterpart, IEC.
II.
To come up with a precise short circuit calculation requires a very complex computation. What is important is that
whatever the short circuit calculation method used, it should be compared with the assigned (tested) fault current
rating of the protective devices.
The final equivalent short circuit schematic diagram is shown below.
R
i(t)
2 Esin(t + )
I
where:
E
Z
The duration and magnitude of the asymmetrical current depends on the following parameters:
a) The X/R ratio of the faulted circuit
b) The phase angle of the voltage waveform at the time the short circuit occur
1
The asymmetrical fault current decay time is longer when X/R ratio is greater at the fault point. For specific X/R
ratio, the angle of the applied voltage at the time of short-circuits initiation determines the degree of fault current
asymmetry that will exist for that X/R ratio. The maximum asymmetrical short-circuit current occurs at the fault
inception when the voltage sine wave is at zero point and not necessarily at the highest dc component.
V.
Calculation Comparison
Table 1 presents a brief comparison of the ANSI/IEEE and IEC with regards to short circuit current calculation
method and multiplying factors.
ANSI/IEEE
North America
IEC
Europe Predominant
machine Zk
Multiplying Factors
1. MF(m) Momentary
multiplying factor I mom.
rms asym = I mom. rms sym *
MF(m)
2. MF(p) Peak multiplying factor
I mom. peak = I mom. rms.
Sym * MF(p)
4
ANSI/IEEE Parameter
DEVICE TYPE
HV BUS BRACING
LV BUS BRACING
HVCB
LVCB
Table 3:
Asymm. KA rms
Symm. KA rms
Symm. KA rms
Asymm. KA rms
C and L Capability KA rms
C and L Capability KA Crest
Interrupting KA
Rated Interrupting KA
Adjusted KA
DEVICE CAPABILITY
IEC Parameter
DEVICE TYPE
CALCULATED
SHORT-CIRCUIT
DUTY (Momentary
Duty)
ip
DEVICE CAPABILITY
Making
MVCB
AC Breaking
Ib ,symm
Making
LVCB
Fuse
ip
Breaking
Ib ,symm
Breaking
Ib ,symm
Table 4:
The ANSI/IEEE vs. IEC
DEVICE TYPE
DEVICE CAPABILITY
ANSI
IEC
HVCB
MVCB
ANSI
IEC
Making (ip)
n/a
Interrupting KA
AC breaking (Isc)
Ib asymm
CALCULATED SHORT
CIRCUIT DUTY
ANSI
IEC
Asymm. KA
ip
rms
Asymm. KA
rest
Adjusted KA
Ib symm
Ib asymm
Idc
LVCB
LVCB
Rated interrupting KA
Iohm
Ish
Ib symm
ip
Ib asymm
Ib asymm
Ish
Ish
or Ik
ETAP
6.0.0C
Project:
Page:
Date:
10-19-2010
Contract:
SN:
FUJIHAYAPH
Engineer:
Revision: Base
Location:
Study Case: SC
Filename: sample
Config.: Normal
Number of Buses:
Number of
Branches:
Swing
1
V-Control
0
Load
7
Total
8
XFMR2
2
XFMR3
0
Reactor
0
Line/Cable
0
Synchronous
Generator
Number of
Machines:
Impedance
0
Tie PD
5
Lumped
Load
Total
System Frequency: 60 Hz
Unit System:
English
Project Filename:
sample
Output Filename:
Total
7
Adjustments
Apply
Adjustment
Individual
/Global
Transformer Impedance:
Yes
Individual
Reactor Impedance:
Yes
Individual
No
No
Cable Length:
No
Tolerance
Percent
Apply
Adjustment
Individual
/Global
Degree C
Transformer Resistance:
Yes
Global
20
Cable Resistance:
Yes
Global
20
Temperature Correction
Initial Voltage
ID
Type
Nom. kV
Base kV
Sub-sys
%Mag.
Ang.
B1
Load
0.240
0.240
100.00
0.00
B2
Load
2.300
2.300
100.00
0.00
Bus4
Load
0.240
0.240
100.00
0.00
Bus5
Load
2.300
2.300
100.00
0.00
Bus6
Load
2.300
2.300
100.00
0.00
Bus7
Load
2.300
2.300
100.00
0.00
Bus8
Load
2.300
2.300
100.00
0.00
UB
SWNG
13.200
13.200
100.00
0.00
8 Buses Total
All voltages reported by ETAP are in % of bus Nominal kV.
Base kV values of buses are calculated and used internally by ETAP
Rating
Z Variation
% Tap Setting
Adjusted
Phase Shift
ID
MVA
Prim.
kV
T1
1.500
13.200
0.240
5.75
7.10
5.7500
0.0
T2
5.000
13.200
2.300
7.15
12.14
7.1500
0.0
Sec. kV
%Z
X/R
+5%
-5%
%Tol.
Prim.
Sec.
%Z
Type
Angle
Branch Connections
CKT/Branch
Connected Bus ID
ID
Type
From Bus
To Bus
T1
2W XFMR
UB
B1
51.58
366.13
369.74
T2
2W XFMR
UB
B2
11.76
142.82
143.31
CB6
Tie Breaker
B1
Bus4
CB7
Tie Breaker
B2
Bus5
CB8
Tie Breaker
B2
Bus6
CB9
Tie Breaker
B2
Bus7
CB10
Tie Breaker
B2
Bus8
Connected Bus
ID
ID
MVAsc
kV
U1
UB
720.000
13.200
% Impedance 100
MVA Base
X"
R/X
0.00014
13.88889
0.00
Rating
Connected Bus
% Impedance
(Motor Base)
Rating
ID
mFact.
Type
Qty
HP/kW
kVA
kV
Amp
PF
X"
R/X"
MW/PP
M2
Motor
Bus5
500.00
440.28
2.300
110.52
90.82
2.96
15.41
0.19
0.19
M3
Motor
Bus6
500.00
440.28
2.300
110.52
90.82
2.96
15.41
0.19
0.19
M4
Motor
Bus7
500.00
440.28
2.300
110.52
90.82
2.96
15.41
0.19
0.19
M5
Motor
Bus8
500.00
440.28
2.300
110.52
90.82
2.96
15.41
0.19
0.19
M1
Motor
Bus4
125.00
110.12
0.240
264.91
91.51
4.62
16.01
0.29
0.05
Connected Bus
Motor Loads
Rating
ID
ID
kVA
kV
L1
B1
1000.0
0.240
% Load
Amp
% PF
MTR
2405.63
85.00
60
10
% Impedance
Machine Base
Loading
STAT
40
m Fact.
kW
kvar
X"
R/X"
MW/PP
510.0
316.1
6.46
15.37
0.42
0.51
=
=
=
=
0.240
1.10
181.348
68.754
(Maximum If)
kA Method A
kA rms
Contribution
From Bus
To Bus
ID
ID
B1
Total
%V
From
Bus
0.00
UB
B1
Imaginary
Ratio
Magnitude
13.406
-78.631
5.9
79.766
96.12
9.232
-68.170
7.4
68.792
L1
B1
100.00
3.690
-8.782
2.4
9.526
M1
Bus4
100.00
0.485
-1.680
3.5
1.748
Bus4
B1
0.00
0.485
-1.680
3.5
1.748
Ib sym
Ib asym
Idc
0.01
78.916
101.347
63.588
0.02
78.315
86.941
37.756
0.03
77.529
80.547
21.843
0.04
76.761
77.794
12.637
0.05
76.017
76.406
7.704
0.06
75.656
75.79
4.504
0.07
75.301
75.347
2.633
0.08
74.952
74.968
1.539
0.09
74.610
74.616
0.939
0.10
74.275
74.277
0.551
0.15
73.582
73.582
0.039
0.20
72.918
72.918
0.003
0.25
72.285
72.285
0.000
0.30
72.260
72.260
0.000
11
B2
Nomimal kV
= 2.300
Voltage c Factor
= 1.10
(Maximum If)
Peak Value
= 51.136
kA Method A
Steady State
= 17.417
kA rms
Contribution
From Bus
ID
To Bus
ID
%V
From Bus
kA
Real
kA
Imaginary
X/R
Ratio
kA
Magnitude
B2
Total
0.00
1.882
-20.420
10.9
20.506
UB
B2
90.44
1.297
-17.377
13.4
17.425
M5
Bus8
100.00
0.146
-0.761
5.2
0.775
M4
Bus7
100.00
0.146
-0.761
5.2
0.775
M3
Bus6
100.00
0.146
-0.761
5.2
0.775
M2
Bus5
100.00
0.146
-0.761
5.2
0.775
Bus5
B2
0.00
0.146
-0.761
5.2
0.775
Bus6
B2
0.00
0.146
-0.761
5.2
0.775
Bus7
B2
0.00
0.146
-0.761
5.2
0.775
Bus8
B2
0.00
0.146
-0.761
5.2
0.775
Ib sym
Ib asym
Idc
0.01
20.014
28.877
20.816
0.02
19.722
25.04
15.429
0.03
19.441
22.464
11.254
0.04
19.174
20.857
8.208
0.05
18.921
19.955
6.342
0.06
18.799
19.373
4.679
0.07
18.681
18.997
3.453
0.08
18.566
18.74
2.548
0.09
18.456
18.564
2.001
0.10
18.349
18.409
1.486
0.15
18.145
18.148
0.336
0.20
17.954
17.954
0.076
0.25
17.775
17.775
0.017
0.30
17.769
17.769
0.004
12
Bus4
Nomimal kV
= 0.240
Voltage c Factor
= 1.10
(Maximum If)
Peak Value
= 181.348
kA Method A
Steady State
= 68.754
kA rms
Contribution
From Bus
ID
To Bus
ID
%V
From Bus
kA
Real
kA
Imaginary
X/R
Ratio
kA
Magnitude
Bus4
Total
0.00
13.406
-78.631
5.9
79.766
M1
Bus4
100.00
0.485
-1.680
3.5
1.748
UB
B1
96.12
9.232
-68.170
7.4
68.792
L1
B1
100.00
3.690
-8.782
2.4
9.526
B1
Bus4
0.00
12.921
-76.952
6.0
78.029
Ib sym
Ib asym
0.01
78.916
101.347
63.588
0.02
78.315
86.941
37.756
0.03
77.529
80.547
21.843
0.04
76.761
77.794
12.637
0.05
76.017
76.406
7.704
0.06
75.656
75.790
4.504
0.07
75.301
75.347
2.633
0.08
74.952
74.968
1.539
0.09
74.61
74.616
0.939
0.10
74.275
74.277
0.551
0.15
73.582
73.582
0.039
0.20
72.918
72.918
0.003
0.25
72.285
72.285
0.000
0.30
72.26
72.260
0.000
13
Idc
UB
Nomimal kV
= 13.200
Voltage c Factor
= 1.10
(Maximum If)
Peak Value
= 90.256
kA Method A
Steady State
= 31.492
kA rms
Contribution
From Bus
ID
To Bus
ID
%V
From Bus
kA
Real
kA
Imaginary
X/R
Ratio
kA
Magnitude
UB
Total
0.00
0.142
-32.117
226.5
32.117
B1
UB
13.64
0.060
-0.167
2.8
0.178
B2
UB
13.86
0.081
-0.458
5.7
0.465
U1
UB
100.00
0.000
-31.492
99999.0
31.492
Ib sym
Ib asym
Idc
0.01
32.048
55.226
44.977
0.02
32.004
55.166
44.934
0.03
31.959
54.943
44.692
0.04
31.915
54.723
44.452
0.05
31.874
54.998
44.82
0.06
31.853
54.889
44.701
0.07
31.833
54.781
44.583
0.08
31.814
54.674
44.464
0.09
31.795
55.076
44.971
0.10
31.777
55.024
44.921
0.15
31.74
54.801
44.674
0.20
31.706
54.581
44.427
0.25
31.673
54.362
44.182
0.30
31.672
54.164
43.939
14
Bus
ID
B1
Device
kV
ID
Type
Ib sym
Ib asym
Idc
I"k
ip
79.766
181.348
Ib sym
Ib asym
Idc
Ik
0.240
B1
Bus
0.240
CB2
CB
220.000
100.000
102.111
79.766
181.348
77.920
83.044
28.718
0.240
CB6
CB
176.000
80.000
80.426
79.766
181.348*
77.219
77.219
17.549
B2
2.300
B2
Bus
20.506
51.136
17.417
Bus4
0.240
Bus4
Bus
79.766
181.348
68.754
0.240
CB6
CB
79.766
181.348*
UB
13.200
UB
Bus
32.117
90.256
176.000
80.000
80.426
68.754
77.219
79.188
31.492
Device Capacity
3-Phase
Short-Circuit
Current
Bus ID
Device ID
1thr (kA)
Tkr (sec.)
Ith (kA)
B1
CB2
100.000
1.00
75.613
B1
CB6
65.000
1.00
75.613*
Bus4
CB6
65.000
1.00
75.613*
15
17.549
FIGURE 5:
ETAP
Page:
Date:
10-19-2010
Contract:
SN:
FUJIHAYAPH
Engineer:
6.0.0C
Location:
Study Case: SC
Filename: sample
Config.: Normal
Swing
Number of Buses:
Number of
Branches:
XFMR2
2
V-Control
0
Load
7
XFMR3
Reactor
0
Total
8
Line/Cable Impedance
0
0
Tie PD
Total
Lumped
Load
Total
System Frequency:
60 Hz
Unit System:
English
Project Filename:
sample
Output Filename:
17
Adjustments
Apply
Adjustment
Individual
/Global
Transformer Impedance:
Yes
Individual
Reactor Impedance:
Yes
Individual
No
No
Cable Length:
No
Tolerance
Percent
Apply
Adjustment
Individual
/Global
Degree C
Transformer Resistance:
Yes
Global
20
Cable Resistance:
Yes
Global
20
Temperature Correction
Initial Voltage
ID
Type
Nom. kV
Base kV
Sub-sys
%Mag.
Ang.
B1
Load
0.240
0.240
100.00
0.00
B2
Load
2.300
2.300
100.00
0.00
Bus4
Load
0.240
0.240
100.00
0.00
Bus5
Load
2.300
2.300
100.00
0.00
Bus6
Load
2.300
2.300
100.00
0.00
Bus7
Load
2.300
2.300
100.00
0.00
Bus8
Load
2.300
2.300
100.00
0.00
UB
SWNG
13.200
13.200
100.00
0.00
8 Buses Total
All voltages reported by ETAP are in % of bus Nominal kV.
Base kV values of buses are calculated and used internally by ETAP
Rating
Z Variation
% Tap Setting
Adjusted
Phase Shift
ID
MVA
Prim.
kV
T1
1.500
13.200
0.240
5.75
7.10
5.7500
0.0
T2
5.000
13.200
2.300
7.15
12.14
7.1500
0.0
Sec. kV
%Z
X/R
+5%
-5%
%Tol.
Prim.
Sec.
%Z
18
Type
Angle
Branch Connections
CKT/Branch
Connected Bus ID
ID
Type
From Bus
To Bus
T1
2W XFMR
UB
B1
53.48
379.58
383.33
T2
2W XFMR
UB
B2
11.74
142.52
143.00
CB6
Tie Breaker
B1
Bus4
CB7
Tie Breaker
B2
Bus5
CB8
Tie Breaker
B2
Bus6
CB9
Tie Breaker
B2
Bus7
CB10
Tie Breaker
B2
Bus8
Power Grid
Connected Bus
Rating
ID
ID
MVASC
kV
X/R
U1
UB
720.000
13.200
99999
0.00014
13.88889
Connected Bus
Rating
% Impedance
(Motor Base)
X/R Ratio
Qty
ID
HP/kW
kVA
kV
RPM
M2
Bus5
500.00
440.28
2.300
1800
M3
Bus6
500.00
440.28
2.300
M4
Bus7
500.00
440.28
M5
Bus8
500.00
M1
Bus4
125.00
X"/R
X'/R
X"
X'
10.89
10.89
2.21
24.05
36.08
1800
10.89
10.89
2.21
24.05
36.08
2.300
1800
10.89
10.89
2.21
24.05
36.08
440.28
2.300
1800
10.89
10.89
2.21
24.05
36.08
110.12
0.240
1800
8.71
8.71
2.30
20.00
50.00
Motors
Motor Loads
Rating
% Load
Loading
X/R Ratio
Static Loads
Loading
ID
ID
kVA
kV
MTR
STAT
kW
kvar
X"/R
X'/R
X"
X'
kW
kvar
L1
B1
1000.0
0.240
60
40
510.00
316.1
2.38
2.38
8.403
20.00
50.00
340.00
210.71
19
B1
Contribution
1/2 Cycle
From Bus
To Bus
%V
kA
kA
Imag.
ID
ID
From
Bus
kA
Symm.
Real
Imaginary
/Real
Magnitude
B1
Total
0.00
10.893
-67.489
6.2
68.362
UB
B1
96.57
8.165
-60.047
7.4
60.600
L1
B1
100.00
2.577
-6.134
2.4
6.653
M1
Bus4
100.00
0.150
-1.307
8.7
1.316
*Bus4
B1
0.00
0.150
-1.307
8.7
1316
B2
=
=
Contribution
From Bus
To Bus
ID
ID
B2
Total
1/2 Cycle
%V
1.5 to 4 Cycle
kA
kA
Imag.
kA
Symm.
From
Bus
0.00
Real
Imaginary
/Real
Magnitude
1.368
-17.787
13.0
17.840
kA
kA
Imag.
kA
Symm.
Real
Imaginary
/Real
Magnitude
0.00
1.311
-17.177
13.1
17.227
%V
From Bus
UB
B2
91.20
1.201
-15.965
13.3
16.010
91.19
1.199
-15.962
13.3
16.007
M5
Bus8
100.00
0.042
-0.456
10.9
0.458
100.00
0.028
-0.304
10.9
0.305
M4
Bus7
100.00
0.042
-0.456
10.9
0.458
100.00
0.028
-0.304
10.9
0.305
M3
Bus6
100.00
0.042
-0.456
10.9
0.458
100.00
0.028
-0.304
10.9
0.305
M2
Bus5
100.00
0.042
-0.456
10.9
0.458
100.00
0.028
-0.304
10.9
0.305
* Bus5
B2
0.00
0.042
-0.456
10.9
0.458
0.00
0.028
-0.304
10.9
0.305
* Bus6
B2
0.00
0.042
-0.456
10.9
0.458
0.00
0.028
-0.304
10.9
0.305
* Bus7
B2
0.00
0.042
-0.456
10.9
0.458
0.00
0.028
-0.304
10.9
0.305
* Bus8
B2
0.00
0.042
-0.456
10.9
0.458
0.00
0.028
-0.304
10.9
0.305
20
B4
=
=
From Bus
ID
Bus4
Contribution
To Bus
ID
Total
%V
From Bus
0.00
kA
Real
10.893
1/2 Cycle
kA
Imaginary
-67.489
Imag.
/Real
6.2
kA Symm.
Magnitude
68.362
M1
UB
L1
Bus4
B1
B1
100.00
96.57
100.00
0.150
8.165
2.577
-1.307
-60.047
-6.134
8.7
7.4
2.4
1.316
60.6
6.653
*B1
Bus4
0.00
10.743
-66.181
6.2
67.048
UB
=
=
Contribution
From
Bus
To
Bus
ID
1.5 to 4 Cycle
kA
kA
Imag.
kA
Symm.
Real
Imaginary
/Real
Magnitude
0.00
0.037
-31.742
863.6
31.742
0.128
4.81
0.018
-0.052
2.8
0.055
0.289
6.50
0.018
-0.198
11.0
0.199
31.492
100.00
0.000
-31.492
99999.0
31.492
%V
kA
kA
Imag.
kA Symm.
ID
From
Bus
Real
Imaginary
/Real
Magnitude
UB
Total
0.00
0.068
-31.901
470.9
31.901
B1
UB
11.24
0.041
-0.121
2.9
B2
UB
9.44
0.026
-0.288
11.0
U1
UB
100.00
0.000
-31.492
99999.0
%V
From Bus
21
Bus
Device
Momentary Duty
Device Capability
ID
kV
ID
Type
Symm.
kA rms
X/R
Ratio
M.F.
Asymm
kA rms
Asymm.
kA Crest
B1
0.240
B1
Bus
68.362
6.9
1.342
91.741
157.859
B2
2.300
B2
Bus
17.840
13.1
1.496
26.68
45.067
Bus4
0.240
Bus4
Bus
68.362
6.9
1.342
91.741
157.859
UB
13.200
UB
Bus
31.901
999.9
1.728
55.139
90.088
Symm
kA
rms
Asymm.
kA rms
Bus
Device
Interrupting Duty
CPT
ID
kV
B1
0.240
B2
2.300
Bus4
0.240
UB
13.200
ID
CB6
CB6
Type
Molded
Case
Molded
Case
Test
Rated
Adjusted
Ratio
M.F.
kA rms
kV
PF
Int.
Int.
68.362
6.9
1.070
73.118
0.240
20.00
85.000
85.000
17.227
13.1
68.362
6.9
1.070
73.118
0.240
20.00
85.000
85.000
(Cy)
31.742
X/R
Device Capability
Adj. Sym.
99184.7
22
Asymm
kA
Crest
XU
RT2
RT1
XT1
RM1
XM1
where:
B2
B1
XT2
RM3
RM2
RL
XL
XM2
XM3
HP(0.746)
(Eff)(pf)(100)
500(0.746)
(1000)(0.9325)(0.9082)
MOTOR (MVA) =
RM4
RM5
XM4
XM5
M2 =
M2 = 0.440 MVA
1. X U
2. R T1
3. X T1
4. R T2
5. X T2
6. R M1
7. X M1
8. R L
9. X L
10. X M2M5
11. R M2M5
100
j 0.13889
720
100
0.575costan 7.1
0.53463
1.5
100
0.575sin tan 7.1
j 3.79587
1.5
100
0.0715costan 12.14 0.11739
5
100
0.0715sin tan 12.14 j1.42157
5
100
0.2costan 8.707 20.74547
0.11
100
0.2sin tan 8.707
j180.63078
0.11
100
0.2costan 2.38 12.91214
1.00.6
100
0.2sin tan 2.38 j30.73089
1.00.6
100
0.24051sin tan 10.888 j54.43227
0.44
100
0.24051sin tan 10.888 12.91214
0.44
j
23
T2
Z M2 Z M3 Z M4 Z M5 Z U Z T1 Z M1 Z L
0.56271
I T3 B
j3.44496
3.49062 80.72
B2
Z M2 Z M3 Z M4 Z M5
0.10787
I T3 B 2
100 x 10 6
68.9 kA
3 240 3.49062
B1
M1
Z L Z T1 Z U Z T2
100 x 10 6
17.85 kA
3 2300 1.40655
1. XUK
j0.13889
2. RT1K
K
K
0.534630.965
0.51592
0.965 as per60909IECformula
Cmax
0.965
; ZK ZT K
1 0.6XT
4. RT2K 0.117391.0
0.11739
5. XT2
j1.42517
j1.425171.0
6. RM1K 20.745470.8
7. XM1K j180.630780.8
8. RLK
9. XLK
12.912140.77
j30.730890.77
16.596
j144.505
9.942
j23.66
3.199
T2K
B1
0.54641
I"K B
I"K B
j3.22821
100 x 10 6 1.1
3 240 3.27412
, I "K
B2
3.27412 80.39
80 kA
, I "K
0.10307
1.32948 85.6
j1.32547
M1K
Z LK Z T1K Z UK Z T2K
100 x 10 6 1.1
17.85 kA
3 2300 1.32948
* It is therefore the basic inclusion of factors C m and k that increases the calculated short-circuit of IEC
method when being compared to the result of the ANSI method.
25
VIII.
ANSI / IEEE
2 I ac rms 1 e X / R
IEC 60909
Lagging
Power
factor
0.7
0.5
0.3
0.25
0.2
X/R
1.02
1.73
3.18
3.87
4.9
Ratio between Short-circuit making capacity and Short-circuit breaking capacity and related power factor or X/R
ratio (for ac circuit breaker).
26
Based on NEMA AB1/UL489, the circuit breakers interrupting capacity, lagging power factor should be in
accordance with Table 6.
Table 6: Circuit Breakers Interrupting Capacity
kA
I 10
10 < I 20
20 < I
All
All
lagging pf
0.45 0.5
0.25 0.30
0.15 0.20
0.15
0.20
X/R
1.98 1.73
3.87 3.17
6.59 4.90
6.59
4.90
Device
B1
CB2
80
80.426
ip
Ib sym
Ib asym
79.8
181.348*
77.219
79.188
From the data in Table 7, the calculated short circuit current level of 79.8kA (Ik) is within the circuit breaker
capacity of 80 kA (Ib sym), however, other parameters such as peak short circuit current ( ip) is 181.348 kA
exceeded the circuit breaker rating equivalent to 176 kA (making peak) only. Therefore, the selected IEC rated
circuit breaker is not suitable for this particular application.
The reason for this difference is that the calculated X/R ratio at 3-phase fault at point B1 is 5.9, which is greater
than the device capacity X/R ratio of only 4.9 (see ETAP IEC method result above) applied during the testing of
circuit breaker interrupting capacity or the Icu rating of the circuit breaker.
Table 8: ANSI Short Circuit Calculation
Bus
ID
Device
B1
CB2
Adj. Int
85.0
85.0
From the data in Table 8, the calculated symmetrical rms current of 68.362 kA needs to be adjusted by the
multiplying factor (MF) of 1.070 (see computation below) resulting to 73.118 kA. This is because the calculated
X/R ratio 6.9 is greater than the X/R ratio used in testing the circuit breaker interrupting capacity which is only 4.9
(Table 6). Comparing the adjusted symmetrical rms value of 73.118 kA against the selected NEMA rated device
interrupting capacity of 85kA, the selected circuit breaker is suitable for the particular application.
27
MF
1 e
1 e
R
X C
R
X T
1 e
1 e
6 .9 C
1
4 .9 T
1.07
Where:
R
X C
MF - Multiplying factor
X.
From the above short circuit calculation examples, IEC method shows a higher value of short circuit current as
compared to ANSI/IEEE calculation method. This is due to the differences in the consideration as mentioned
above. Both methods are being used and internationally acceptable.
In any electrical system, it is important to know the short circuit level of each of the protective equipment.
However, we should not forget to verify the X/R ratio of the faulted bus against the circuit breaker test power
factor or X/R ratio based on their product standard (e.g. UL/NEMA/ANSI or IEC). The example above
illustrates clearly the importance of X/R ratio in evaluating or selecting the circuit breaker. Understanding the
relationship between the product standards and electrical codes is of utmost importance.
It is up to the engineers/designers to decide which method of short circuit calculation they are more comfortable
with provided they have to take note of the different considerations in the selection of the protective equipment.
28
XI. References
1 IEEE Std 551-2006, IEEE Recommended Practice for Calculating Short-Circuit currents in
Industrial and Commercial Power System.
2 IEEE Papers, Simplifying IEEE/ANSI and IEC Fault Point X/R Ratio for Breaker Evaluation
by Ketut Dartawan and Conrad St. Pierre
3 IEC 60497-1:2009, Low-voltage switchgear and control gear - Part 1: General rules
4 IEC 60497-2:2009, Low-voltage switchgear and control gear - Part 2: Circuit-breakers
5 ANSI C37.5-1989, Calculation of Fault Currents for Application of Power Circuit Breakers
Rated on a Total Current Basis
6 UL 489-1986, Molded Case Circuit Breaker and Circuit Breakers Enclosure
7 IEC 60909-0, Corrigendum 1 - Short-circuit currents in three-phase A.C. systems - Part 0:
Calculation of currents
8 Electrical Transient Analyzer Program (ETAP) Software version 6.0
29
Appendix
proM Compact
Technical features
S 200
Series
Characteristics
Rated current
[A]
Breaking capacity
[kA]
Reference standard
IEC 23-3/EN 60898
IEC/EN 60947 - 2
Alternating current
Nr.
Poles
lcs
lcu
1, 1P +
N
2,3,4
2,3,4
lcs
1, 1P +
N
B,C,D
K,Z
S 200 P
B,C,D
K,Z
B,C,D
K,Z
0.5 ln 63
0.2 ln 25
32 ln 40
50 ln 63
80 LN 100
10
25
15
15
133
230
230
400
500
690
20
10
20
10
25
15
25
15
40
25
40
25
25
15
25
15
25
15
25
15
15
6
10
6
133
15
18.7
20
18.7
18.7
15
Ue [V]
230 / 400
S 200
B,C,D
K,Z
S 200 M
B,C,D
K,Z
0.5 ln 63
30
S 280
B,C
(continued )
2,3,4
2,3,4
IEC/EN 60497 - 2
Direct current
T= lR 5ms for all
series
except S280 UC and
S800S-UC
where T = lR <15ms
lcu
1, 1P +
N
3,4
lcs
1, 1P +
N
3,4
230
230
400
500
690
7.5
15
7.5
11.2
18.7
11.2
12.5
20
12.5
11.2
18.7
11.2
7.5
18.7
7.5
6
10
6
24
60
125
250
48
125
250
500
600
800
375
500
750
1000
1200
20
10
10
15
10
10
10
20
10
10
15
10
10
10
24
60
125
250
48
125
250
500
600
800
375
20
10
10
15
10
10
10
20
10
10
15
10
10
10
31
(continued )
500
750
1000
1200
UL 1077 / C22.2
No 235
Alternating current
lnt.
cap.
1, 1P +
N
2,3,4
UL 1077 / C22.2
No 235
Direct current
UL 489/ C22.2
No 5
Alternating current
lnt.
cap.
IEC / EN 60947 - 3
lcw
lnt.
cap.
1, 1P +
N
2,3,4
1
2,3,4
2
3,4
120
277
240
480Y /
277
10
6
10
10
10
10
10
10
10
10
10
10
10
10
10
60
125
10
10
240
277
240
480y /
277
800
1200
<50 A
32