PRIMARY DISTRIBUTION REPORT

NETWORK_CODE:

S27F8B_CI

STUDY CODE:

STUDY DESCRIPTION:

Balanced_Loadflow

LOAD FLOW STUDY DETAILS


Power Source

NO DATA

Busloads

DT Capacity Demand

Load Allocation

DF

Load Modelling

CP: 1 CC: 0 CI: 0

Energy Loss

Load Loss Factor

PTR Tap control

Normal

DTR Tap control

Normal

MV FEEDER INPUT DATA

SLNO

FEEDER NAME

SUBSTATION NAME

RATED VOLTAGE

DF-KW

DF-KVAR

LF

PF

CHIRAA

SUNYANI

11.5

0.60

0.90

MV LOAD FLOW ANAYSIS

SL
LENGTH(K
FEEDER NAME
NO
M)

CHIRAA
TOTAL

TRANSFORMERS

NO

CAPACITY KVA

55.56

59

12565

55.56

59

12565

BUSBAR
VOLTAGE
KV

MAXIMUM-LOADING

11.50

VOLTAGE
DROP
(%age)

MINIMUM
VOLTAGE
(KV)

25.47

8.57

KW

KVAR

AMPS

6128.33

4485.00

381.00

32326.02

6128.33

4485.00

381.00

32326.02

PEAK - POWER - LOSS (KW)


Sl NO

ESTIMATE
ENERGY
INPUT
(MWH)

VALUE OF POWER
LOSS
(GHC*1000)

ENERGY LOSS (MWH)

FEEDER NAME

CHIRAA
TOTAL

LINE

IRON

COPER

TOTAL

(%age)

LINE

TRANS

TOTAL

(%age)

1014.46

32.96

63.34

1110.76

18.13

5332.01

621.63

5953.64

18.42

1014.46

32.96

63.34

1110.76

5332.01

621.63

5953.64

523.83
523.83

SUBSTATION LOAD FLOW ANALYSIS


LOADING
SNO

SUBSTATION NAME

SUNYANI
TOTAL

TOTAL

PTR CAPACITY MVA


KW

KVAR

KVA

%age

25.00

6128.33

4485.00

7594.19

30.38

25.00

6128.33

4485.00

7594.19

30.38