Operation & Maintenance OF Generator and Exciter
Operation & Maintenance OF Generator and Exciter
OF
GENERATOR AND EXCITER
OPERATION OF GENERATOR
OPERATING AND SETTING VALUES
OPERATING AND SETTING VALUES FOR THE FOLLOWING PARAMETERS
SHOULD BE STRICTLY OBSERVED :
PARAMETER
OPERATING VALUE
SETTING VALUE
50 - 100 C
120 C
50 - 100 C
120 C
120 C
40 - 70 C
75 C
BEARING TEMP.
< 75 C
90 C ALARM
120 C m TRIP
SHAFT VIBRATIONS
< 85 m
160 m ALARM
240 m TRIP
BEARING TEMP
< 75 C
90 C ALARM
120 C m TRIP
80 KOHM (ALARM)
5 KOHM (TRIP)
CAPABILITY CURVE
PERIODICITY OF MAINTENANCE
FOR MACHINES WITH VPI INSULATION -
PERIODICITY OF MAINTENANCE
FOR MACHINES WITH NON-VPI INSULATION -
PERIODICITY OF MAINTENANCE
FOR MACHINES WITH NON-VPI INSULATION-
RECOMMENDED SPARES
ONE SET OF GENERATOR BEARINGS, EXCITER BEARINGS
1/3RD SET OF STATOR BARS FOR NON-VPI MACHINES
FEW WEDGES, INSULATION BELOW WEDGE ETC. FOR NON-VPI
MACHINES
ONE SET OF INSULATION OF BEARINGS
EARTHING BRUSHES
DIODES AND FUSES FOR EXCITERS
CLEANING AGENTS
WHITE PETROL, ACETONE, BENZENE (NO CTC)