HVAC Load Analysis


for

Juan Mahecha

Prepared By:
J&S

jueves, 17 de marzo de 2016

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Aire Acondicionado Salon 202 Cyt
Page 2

Building Summary Loads


Building peaks in August at 5pm.

Bldg Load
Descriptions
Roof
Wall
Glass
Floor Slab

Area
Quan

Sen
Loss

%Tot
Loss

Lat
Gain

Sen
Gain

Net
Gain

%Net
Gain

0
12
19
0

0
494
3.245
0

0,00
7,92
52,08
0,00

0
0
0
0

0
-111
4.750
0

0
-111
4.750
0

0,00
-1,55
66,47
0,00

3.738

60,01

4.639

4.639

64,92

0
0
0
0
0
0
0
0
1.108
0
0
0
0
0
0
865
519
0
0

0,00
0,00
0,00
0,00
0,00
0,00
0,00
0,00
17,78
0,00
0,00
0,00
0,00
0,00
0,00
13,88
8,34
0,00
0,00

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

158
525
0
1.024
0
0
0
-281
0
0
0
54
0
0
0
790
239
0
0

158
525
0
1.024
0
0
0
-281
0
0
0
54
0
0
0
790
239
0
0

2,20
7,35
0,00
14,33
0,00
0,00
0,00
-3,94
0,00
0,00
0,00
0,75
0,00
0,00
0,00
11,05
3,34
0,00
0,00

6.230

100,00

7.145

7.145

100,00

Skin Loads
Lighting
Equipment
Pool Latent
People
Partition
Cool. Pret.
Heat. Pret.
Cool. Vent.
Heat. Vent.
Cool. Infil.
Heat. Infil.
Draw-Thru Fan
Blow-Thru Fan
Reserve Cap.
Reheat Cap.
Supply Duct
Return Duct
Misc. Supply
Misc. Return

150
500
0
15
0
0
0
96
96
0
0
0
0
0
0
0
0
0
0

Building Totals

Building
Summary

Sen
Loss

%Tot
Loss

Lat
Gain

Sen
Gain

Net
Gain

%Net
Gain

Ventilation
Infiltration
Pretreated Air
Room Loads
Plenum Loads
Fan/Duct/Misc Loads

1.108
0
0
3.738
0
1.384

17,78
0,00
0,00
60,01
0,00
22,22

0
0
0
0
0
0

-281
0
0
6.345
0
1.082

-281
0
0
6.345
0
1.082

-3,94
0,00
0,00
88,80
0,00
15,14

Building Totals

6.230

100,00

7.145

7.145

100,00

Check Figures
Total Building Supply Air (based on a 15 TD):
Total Building Vent. Air (8,27% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

C:\Users\Jorge\Documents\jorge suarez.CH8

1.161 L/s
96 L/s
35
33,1763
4,8984
0,2041
178,00

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

6,23 kW
7,15 kW

17,2 Sq.m/Ton
0,0580 Tons/Sq.m

2,03 Tons

jueves, 17 de marzo de 2016, 03:45 p. m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Aire Acondicionado Salon 202 Cyt
Page 3

Air Handler #1 Summary Loads for Zones (Z)


Zn
No

Description
Zone Peak Time

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

Zone 0
5pm August

35
15
105

3.738
776
22,18

6.345
1.161
33,18

473
0
0

n/a
96
96

n/a
96
96

Zone Peak Totals:


Total Zones: 1

35
15
105

3.738
776
22,18

6.345
1.161
33,18

473
0
0

96
96

96
96

C:\Users\Jorge\Documents\jorge suarez.CH8

jueves, 17 de marzo de 2016, 03:45 p. m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Aire Acondicionado Salon 202 Cyt
Page 4

Air Handler #1 Summary Loads for Rooms (Z)


Rm
No

Description
Zone Peak Time

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

Z-01p2salon
5pm August

35
15
105

3.738
776
22,18

6.345
1.161
33,18

473
0
0

5/P, 0,6/m
96
96

5/P, 0,6/m
96
96

Room Peak Totals:


Total Rooms: 1

35
15
105

3.738
776
22,18

6.345
1.161
33,18

473
0
0

96
96

96
96

C:\Users\Jorge\Documents\jorge suarez.CH8

jueves, 17 de marzo de 2016, 03:45 p. m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Aire Acondicionado Salon 202 Cyt
Page 5

Air Handler #1 Total Load Summary (Z)


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

Constant Volume - Proportion


Draw-Thru with program estimated horsepower of 0,16 kW
0% motor and fan efficiency with 0 kPa across the fan
0,94
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

5pm in August.
Clg: 68 DB, 59 WB, 806,79 grams moisture per kg dry air, Htg: 46 DB
Clg: 75 DB, 50% RH, Htg: 75 DB

Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Room Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

3.738
0
1.108
865
519
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
96 L/s

6.230 Watts

Heating Supply Air: 4.603 / (,331 X 1,21 X 15) =


Winter Vent Outside Air (12,4% of supply) =
Room space sensible gain:
Infiltration sensible gain:
Draw-thru fan sensible gain:
Supply duct sensible gain:
Reserve sensible gain:
Total sensible gain on supply side of coil:

6.345
0
54
790
0

776 L/s
96 L/s
Watts
Watts
Watts
Watts
Watts
7.188 Watts

Cooling Supply Air: 7.188 / (,331 X 1,23 X 15) =


Summer Vent Outside Air (8,3% of supply) =

1.161 L/s
96 L/s

Return duct sensible gain:


239 Watts
Return plenum sensible gain:
0 Watts
Outside air sensible gain:
-281 Watts
Blow-thru fan sensible gain:
0 Watts
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Room space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

96 L/s
-43 Watts
7.145 Watts

473 Watts
0 Watts
-3.773 Watts
-3.300 Watts
3.845 Watts

Check Figures
Total Air Handler Supply Air (based on a 15 TD):
Total Air Handler Vent. Air (8,27% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

1.161 L/s
96 L/s
35
33,1763
4,8984
0,2041
178,00

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

6,23 kW
7,15 kW

17,2 Sq.m/Ton
0,0580 Tons/Sq.m

2,03 Tons

Note: Due to the system's negative latent gain, tonnage is based solely on sensible gain.

C:\Users\Jorge\Documents\jorge suarez.CH8

jueves, 17 de marzo de 2016, 03:45 p. m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Aire Acondicionado Salon 202 Cyt
Page 6

Zone Detailed Loads (At Zone Peak Times)


Load
Unit
-SCCLTD
U.Fac
Sen.
Lat.
Description
Quan
CFAC
SHGF
-CLFGain
Gain
Room 1-Z-01p2salon - Air Handler 1, Zone 0 peaks (sensible) in August at 5pm.
Wall-1-E-C-M
Wall-2-W-C-M
Gls-E-1-90-Tran
0%S-1-NS-Solar
Gls-W-1-90-Tran
0%S-0-NS-Solar
Lights-Prof=1
Equipment-Prof=3
People-Prof=2

9
3
6,0
6,0
12,5
12,5
150
500
15,0

Sub-total
Safety factors:
Total w/ safety factors:

C:\Users\Jorge\Documents\jorge suarez.CH8

0,83
0,83
1,000
0,880
1,000
0,880
1,000
1,000
1,000

-5,4
-10,4
-12
678
-12
678

1,420
1,420
4,600
0,220
4,600
0,640

-69
-37
-336
788
-701
4.773
150
500
975

0
450

6.043
+5%
--------6.345

450
+5%
--------473

Htg.
Mult.

Htg.
Loss

40,884
40,884
167,040

368
102
1.002

167,040

2.088

3.560
+5%
--------3.738

jueves, 17 de marzo de 2016, 03:45 p. m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Aire Acondicionado Salon 202 Cyt
Page 7

Room Detailed Loads (At Room Peak Times)


Load
Unit
-SCCLTD
U.Fac
Sen.
Lat.
Htg.
Htg.
Description
Quan
CFAC
SHGF
-CLFGain
Gain
Mult.
Loss
Room 1-Z-01p2salon peaks (sensible) in August at 5pm, Air Handler 1, Zone 0, 5,0 x 7,0, Construction
Type: 1 (Light)
Wall-1-E-C-M
Wall-2-W-C-M
Gls-E-1-90-Tran
0%S-1-NS-Solar
Gls-W-1-90-Tran
0%S-0-NS-Solar
Lights-Prof=1
Equipment-Prof=3
People-Prof=2

9
3
6,0
6,0
12,5
12,5
150
500
15,0

Sub-total
Safety factors:
Total w/ safety factors:

C:\Users\Jorge\Documents\jorge suarez.CH8

0,83
0,83
1,000
0,880
1,000
0,880
1,000
1,000
1,000

-5,4
-10,4
-12
678
-12
678

1,420
1,420
4,600
0,220
4,600
0,640

-69
-37
-336
788
-701
4.773
150
500
975

0
450

6.043
+5%
--------6.345

450
+5%
--------473

40,884
40,884
167,040

368
102
1.002

167,040

2.088

3.560
+5%
--------3.738

jueves, 17 de marzo de 2016, 03:45 p. m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Aire Acondicionado Salon 202 Cyt
Page 8

Building Profile Graphs


Building Net Load (Z)
8.000

6.000

August

Watts 4.000
2.000

01am

2am 3am 4am 5am 6am 7am 8am 9am 10am 11am 12pm 1pm 2pm 3pm 4pm 5pm 6pm 7pm 8pm 9pm 10pm 11pm 12am

Hours of Operation August

C:\Users\Jorge\Documents\jorge suarez.CH8

jueves, 17 de marzo de 2016, 03:45 p. m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Aire Acondicionado Salon 202 Cyt
Page 9

Air System #1 () Psychrometric Analysis (Z)


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Room Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

54
0
790
6.345
0

60,000
0,113
0,000
1,670
13,417
0,000

9
0
128
1.025
0

7.188
239
0
0
-281
0

75,200
0,550
0,000
0,000
-0,641
0,000

1.161

7.145

75,109

1.161

863,275

Room Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 96 L/s
Blow-Thru Fan
Entering Coil Condition

0,000

473

0,415

473

863,690

0
-3.773

0,000
-4,719

-3.300

858,971

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

SUM
GTH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010,387)


PR x
1,23 x L/s x (DB entering - DB leaving)
PR x
2,96 x L/s x (g/kg entering - g/kg leaving)
PR x
1,20 x L/s x (Enthalpy entering - Enthalpy leaving)
0,331
0,331

0,331

x
x

1,23
2,96

1,20

x
x

1.161
1.161

1.161

x(
x(

75,1
859,
0

x(

2.34
4,1

Total System Load

60,0
863,
3
2.31
6,1

)=
)=

7.145 Watts
-4.898 Watts

)=

---------2.247 Watts
12.947 Watts

3.845 Watts

=
=
=

0,0 L/s
0,0 L/s
6,42 kg./hr

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

12.947 / (
6.230 / (
6.230 /

0,00
0,00
970

x
x

4.179
4.179

)
)

Entering Cooling Coil Conditions

Entering Heating Coil Conditions

Dry bulb temperature:


Wet bulb temperature:
Relative humidity:
Enthalpy:

Dry bulb temperature:

75,11
59,64
50,22
2344,12 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

70,18

Leaving Heating Coil Conditions


60,00
59,53
97,81
2316,06 kJ/kg

C:\Users\Jorge\Documents\jorge suarez.CH8

Dry bulb temperature:

90,00

jueves, 17 de marzo de 2016, 03:45 p. m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Aire Acondicionado Salon 202 Cyt
Page 10

Air System #1 () Psychrometric Chart


RC
Room Condition
LC
Leaving Coil Condition
SD
Supply Duct Temperature Rise
DTF
Draw Through Fan Sensible Gain
RE
Reserve or Reheat Sensible Gain
SM
Supply Side Miscellaneous Sensible Gain
PRE
Pretreated Air Condition
MIX
Mixed Air Condition
One or more points or processes failed to be added to the chart:
Room point could not be added.

OC
EC
RD
BTF
PL
MR
HRV
RML

Outdoor Condition
Entering Coil Condition
Return Duct Temperature Rise
Blow Through Fan Sensible Gain
Return Air Plenum Sensible Gain
Return Side Miscellaneous Gain
Heat Recovery Ventilator Condition
Return Miscellaneous Latent Gain

Data out of range:


DB=167,36
RH=50
W=0,6272746

C:\Users\Jorge\Documents\jorge suarez.CH8

jueves, 17 de marzo de 2016, 03:45 p. m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Aire Acondicionado Salon 202 Cyt
Page 11

Building Pie Charts (Z)


Building peaks in August at 5pm.

Return Duct - 3,34%


Supply Duct - 11,05%
Draw-Thru Fan - 0,75%

People - 14,33%
Building
Net Gain
7.145 Watts

Equipment - 7,35%

Glass - 66,47%

Lighting - 2,20%

Wall - 7,92%

Return Duct - 8,34%

Supply Duct - 13,88%

Building
Loss 6.230
Watts
Heat. Vent. - 17,78%
Glass - 52,08%

C:\Users\Jorge\Documents\jorge suarez.CH8

jueves, 17 de marzo de 2016, 03:45 p. m.