Calculation
  Sheet  
(P-2 of
Cust.- HVPNL 4)  
1 st
  12.5/16 MVA 132/11 KV UNIT  
ORDER No. - HDP-1216/QDP-593/XEN.S.Stn(P) Dtd. 03.04.06
   
Total Mass of 80 strips (m) = kg 1.488  
% of hysteresis current loss for the thickness of 0.27 mm (h) = 50  
% of eddy current loss for the thickness of 0.27 mm (e) = 50  
Length of strips used (l) = m 0.305  
Maximum intrinsic flux density (Bi) = T 1.57  
Standard assumed density of the specimen (ρ) = Kg/m3 7650  
   
Formula Used For the Calculation of Flux Voltage = (38850 * Bi * m)/( ρ*l) 38.90  
Flux Voltage (Avg. Voltage) (Ef) = V 38.90  
Voltage Applied (Ef) = 39.00  
rms Voltage (E) = 38  
Wattmeter Reading = W 2.46  
Wattmeter Factor = 0.5  
Total Losses = Wattmeter Reading * Wattmeter Factor = W 1.23  
   
2
  Wc= W-(E /R) = 0.749  
Where = R is the resistance of the Wattmeter Used = 3000 ohms  
   
Observed PC = Wc/me = W/kg 0.653  
Where me = Active mass = (0.94 *m)/4*l 1.146  
   
Corrected PC = Observed PC * (100/(50+(Erms/Eavg)2*50)) = W/kg 0.670  
   
Ageing Test  
   
Wattmeter Reading = W 2.5  
Wattmeter Factor = 0.5  
Total Losses =
W 1.25  
   
WC = 0.769  
   
Obsrved PC 0.670  
=W/kg
   
Corrected PC = W/kg 0.688  
   
% Increased in Loss = ((0.688-0.670)/0.670) *100 = 2.68  
   