REACTOR PROTECTION

PREPARED BY GOPALA KRISHNA PALEPU ADE/MRT(PROTECTION)


gk_aptransco@yahoo.co.in, Mobile:9440336984

MAIN-1 & MAIN-2 PROTECTION FOR SHUNT REACTOR ADOPTED IN ONE AND HALF CIRCUIT BREAKER SCHEME
PREPARED BY GOPALA KRISHNA PALEPU ADE/MRT(PROTECTION)

BASICS OF SHUNT REACTOR


1. TYPES OF REACTORS : A. BASED ON REACTOR CONNECTION i. SHUNT REACTOR. ii. SERIES REACTOR. B. BASED ON REACTOR LOCATION i. BUS REACTOR ii. LINE REACTOR C. BASED ON CONTROL i. 3-PH OIL IMMERSED REACTOR WITH GAPPED IRON CORE. ii. THYRISTOR CONTROLLED REACTOR (STATIC VAR COMPENSATOR) (APTRANSCO UTILISING SHUNT REACTORS FOR BUS & LINE IN 400KV NETWORK) 2. NEED OF SHUNT REACTOR: A. LINE REACTOR
SHUNT REACTORS ARE USED IN ORDER TO COMPENSATE FOR THE CAPACITIVE SHUNT REACTANCE OF TRANSMISSION LINES. THE REACTOR IS CONNECTED PARALLEL TO THE LINE. THE LOCATION OF REACTOR IS OUT GOING SIDE OF LINE i.e AFTER CIRCUIT BREAKER. LENGTH OF LINE IS MORE THERE MAY BE VOLTAGE IS RAISING DUE TO FARANTI EFFECT(CAPACITANCE) DURING CHARGING. IN CASE OF ZONE-2 (OPEN JUMPER) FAULT, THE FAULT CLEARED BY REMOTE END IS FAST, BUT THIS END IT WILL TAKE TIME DELAY DUE TO ZONE-2. DURING THIS TIME, VOLTAGE MAY RAISING. SO, LINE REACTOR IS USED FOR CONTROLLING THE SWITCHING OVER VOLTAGES AND SAFEGUARD THE OPERATING EQUIPMENT. NORMALLY IT IS ALWAYS IN SERVICE. NORMALLY BOTH ENDS LINE REACTORS ARE PROVIDED. THE ELECTRICAL INTERLOCK IS PROVIDED THAT IF REACTOR ISOLATOR CLOSSED POSITION ONLY WILL GIVE PERMIT TO CLOSE THE LINE ISOLATOR. SIMILARLY FOR OPENING REACTOR ISOLATOR THE LINE ISOLATOR SHOULD BE IN OPEN POSITION. NEUTRAL REACTOR CONNECTED BETWEEN THE STAR POINT OF EHV SHUNT REACTOR AND THE GROUND, LIMITS THE SECONDARY ARC CURRENT TO A LOW VALUE OF AROUND 10 AMPS TYPICALLY FOR 400KV SYSTEM TO ENSURE COMPLETE DE-IONISATION OF ARC PATH WHEN EHV SYSTEM DEVELOPS A SINGLE LINE TO GROUND FAULT. ARC EXTINCTION DURING LINE SINGLEPHASE AUTORECLOSE DEAD TIME IS ASSISTED BY THIS NEUTRAL REACTOR.

3.

4.

B. BUS REACTOR THE REACTOR IS CONNECTED PARALLEL TO THE BUS i.e LIKE A FEEDER/LINE. DURING LIGHTLY LOADED CONDITIONS THERE MAY BE POSSIBULITY OF RAISING BUS VOLTAGES. FOR SAFEGUARD THE OPERATING EQUIPMENT BUS REACTORS ARE UTILISING. NORMALLY IT IS NOT IN SERVICE. WHENEVER THE VOLTAGE RAISES TO 4%TO 5% MORE THAN THE RATED VOLTAGE THIS MAY BE KEPT IN SERVICE AND 2% TO 3% LESS THAN THE RATED VOLTAGE THIS MAY BE KEPT OUT OF SERVICE. SELECTION OF REACTOR A. LINE REACTOR NORMALLY LINE REACTORS ARE PROVIDED IF THE LINE IS MORE OR EQUAL TO 250KM. IN APTRANSCO NETWORK MAXIMUM LENTH OF LINE IS 350KM. AS PER SYSTEM STUDIES RECOMANDATIONS IF LINE LENGTH IS 250KM TO 300KM 50MVAR REACTOR IS TO BE USED. IF MORE THAN 300KM 63MVAR REACTOR IS TO BE USED. B. BUS REACTOR NORMALLY BUS REACTORS ARE PROVIDED IF THE SUBSTATION BUS VOLTAGE IS RAISING 5% MORE THAN THE RATED VOLTAGE DURING LIGHTLY LOADED CONDITION. BASED ON THE SYSTEM STUDIES RECOMANDATIONS BUS REACTORS ARE TO BE PROVIDED. CALCULATIONS ARE REQUIRED FOR PROVIDING BUS REACTOR. IN THIS THERE IS NO STANDARDISATION. LOCATION OF REACTORS WITH CAPACITY IN APTRANSCO A. LINE REACTOR 1. 400KV KALAPAKA-KHAMMAM 1 AT BOTH ENDS 63MVAR 2. 400KV KALAPAKA-KHAMMAM 2 AT BOTH ENDS 63MVAR B. BUS REACTOR 1. 400KV KALAPAKA SS 2 X 50 MVAR 2. 400KV NUNNA SS(PGCIL BAYS) 1 x 63 MVAR

5.

6.

7.

8.

9.

PURPOSE OF SHUNT REACTOR PROTECTION THE PURPOSE OF THE PROTECTION RELAYING IS TO DISCONNECT THE REACTOR AND LIMIT DAMAGE IN CASE OF INTERNAL SHORT CIRCUITS, EARTH FAULTS, INTERTURN FAULTS AND OVER VOLTAGE OR OVER LOAD.THE REACTOR FORMS CERTAIN IMPEDENCE FOR RATED FREQUENCY, AND AS IT IS SHUNT CONNECTED, AS OVER LOAD MAY BE CAUSED BY OVER VOLTAGE OR HARMONICS IN VOLTAGE AND CURRENT. PROTECTION DEVICES INBUILT OR MOUNTED ON REACTOR A. OIL IMMERSED REACTOR USUALLY HAVE A GAS DETECTOR AND OIL SURGE. DETECTOR (BUCHHOLZ ALARAM & TRIP DEVICES), WHICH ARE EXCELLENT FOR DETECTING INTERNAL FAULTS. B. TEMPARATURE MONITORS FOR OIL & WINDING PROVIDE GOOD OVER LOAD PROTECTION. C. PRESSURE RELIEF DEVICE IS PROVIDED TO SAFE GUARD THE REACTOR FROM HIGH PRESURES. REACTOR DIFFERENTIAL PROTECTION IT IS WIDELY USED AS INSTANTANEOUS PROTECTION FOR SHORT CIRCUIT FAULTS WITH IN THE DIFFERENTIAL ZONE. THIS IS TREATED AS MAIN-1 PROT FOR REACTOR. IT CAN BE OF HIGH IMPEDENCE TYPE OR OF A SENSITIVE CURRENT STABILISED TYPE. HIGH IMPEDENCE DIFFERENTIAL PROTECTION RELAYS REQUIRE AN EQUAL CT TURNS RATIO ON THE PHASE AND NEUTRAL SIDE. SENSITIVITY IS 5% OF NOMINAL REACTOR CT CURRENT. BACK-UP PROTECTION A VARIETY OF RELAYS ARE AVAILABLE. A. OVER CURRENT & EARTH FAULT PROTECTION. ( 50, 50N, 51, 51N, 67, 67N - ANY COMBINATION OF THESE) B. UNDER IMPEDENCE / DISTANCE ( Z<)(21R). C. NEUTRAL DISPLACEMENT PROTECTION (Un>). RESTRICTED EARTH FAULT PROTECTION IF, FOR SOME REASON, A SENSITIVE DIFFERENTIAL PROTECTION NOT CHOOSEN A RESTRICTED EARTH FAULT PROTECTION CAN BE UTILISED.

SHUNT REACTOR (BUS & LINE)


(ONE AND HALF CIRCUIT BREAKER SYSTEM )
BUS-1
IL INTER LOCK FACILITY: WHEN 1-89R CLOSES ONLY PERMIT TO CLOSE 1-89L AND 1-89L OPENS ONLY PERMIT TO OPEN 1-89R.

BUS-2 3-89

1-89

1-52CB 1-CT 1-89A 1-89R


IL P2

3-52CB

P2

P1

P1

3 3-CT
3-89A

.
2-89A

2-CT
P1

P2

LINE SHUNT REACTOR


1-PH NEUTRAL GROUNDING REACTOR

2-52CB

2-89B 3-89R

U UU

1-89L

U UU

LINE 1

UU UU

BUS SHUNT REACTOR

REACTOR BUSHING CT INFORMATION


CAPACITY OF 400KV REACTORS : 50, 63, 80, 125 MVAR
Sr NO 1

SHUNT REACTOR ITEM


RATIO
400KV / LINE SIDE
CORE-1 CORE -2 CORE-3 CORE-4 CORE-5 CORE-1

STAR / NEUTRAL SIDE


CORE-2 CORE -3 CORE-4

LINE SIDE EARTH SIDE

NGR

CORE-1

CORE-2

2000- 2000200/1 200/1 200/1 1000- 1000- 200/1 WTI 200/1 200/1 500/1 500/1 NEUTRAN BUSHING CT : CORE-1 : BEFORE STAR FORMATION IN RYB PHASES 200V 200V 1000500250V 1000500250V
Parameters of WTI CT for each winding shall be provided by the contractor

200/1

200/1

VKNEE FOR PS 2 & VA FOR 200V MET 3 RCT IN OHMS 1 OHM 4 5


CLASS OF ACURACY

1 OHM PS 64 R REF1

1.0 CL AND 10 5 10 5 BURDEN 2.5 10 VA 1 OHM 2.5

200V

200V

200V

200V

OHM PS

OHM PS

1 OHM PS 87 R DIFF

1 OHM PS 64 R REF1

1 OHM PS 64 R REF2

1 OHM PS 64 R REF1/2

PS 87 R DIFF

PS

PURPOSE

FOR 21L2 FOR 21L1 21 R /TEED-1 / /TEED-2 / MET IMP BBM BBC

SHUNT REACTOR PROTECTION


CORES 400KV SIDE CORE-1 CORE-2 CORE-3 CORE-4 CORE-5 87R 3Ph, 2Wdg REACTOR DIFFERENTIAL RELAY EITHER LOW or HIGH IMPEDANCE TYPE. 64R - REACTOR RESTRICTED EARTH FAULT PROTECTION OF1-POLE HIGH IMPEDANCE TYPE.(REF1) 21R 3Ph, REACTOR BACKUP IMPEDANCE RELAY OF SUITABLY SHAPED CHARECRESTICS EITHER SINGLE / DOUBLE ZONE TYPE. 21L2
(M_CT+T_CTR_CT)

ONE & HALF BREAKER SYSTEM LINE BUS

DOUBLE BUS & TRANSFER BUS SYSTEM LINE BUS

87 TEED-2
(M_CT, T_CT, R_CT)

21L2
(M_CT+T_CT R_CT)

87 BBC/BB-2 87 BBM/BB-1

21L1
(M_CT+T_CTR_CT)

87 TEED-1
(M_CT, T_CT, R_CT)

21L1
(M_CT+T_CT R_CT)

M_CT: Main CT, T_CT: Tie CT, R_CT: Reactor CT

SHUNT REACTOR PROTECTION


CORES ONE & HALF BREAKER SYSTEM LINE STAR / NEUTRAL SIDE CORE-1 CORE-2 CORE-3 CORE-4 METERING OF REACTOR WINDING TEMPARETURE OF REACTOR 87R 3Ph, 2Wdg REACTOR DIFFERENTIAL RELAY EITHER LOW / HIGH IMPEDANCE TYPE. 64R - REACTOR RESTRICTED EARTH FAULT PROTECTION OF1-POLE HIGH IMPEDANCE TYPE .(REF1) 64 REF1 64 REF1 --64 REF2 64 REF 1 / 2 --BUS DOUBLE BUS & TRANSFER BUS SYSTEM LINE BUS

NEUTRAL GROUNDING REACTOR SIDE CORE-1 CORE-2

REACTOR BUSHING CT INFORMATION

1-PH NEUTRAL GROUNDING REACTOR

U UU 3
CORE -2

3 3 3

LINE SHUNT REACTOR

U UU

U UU

U UU
CORE -1 CORE -2 CORE -3 CORE -4 CORE -1

3 3 3 3 3

3 3 3 3 3

3 3 3 3 3 3

CORE -1 CORE -2 CORE -3 CORE -4 CORE -5

REACTOR BUSHING CT INFORMATION

3 3 3

BUS SHUNT REACTOR

U UU

U UU

U UU
CORE -1 CORE -2 CORE -3 CORE -4

3 3 3 3 3

3 3 3 3 3

3 3 3 3 3 3

CORE -1 CORE -2 CORE -3 CORE -4 CORE -5

ONE & HALF BREAKER LINE & BUS SHUNT REACTOR PROTECTION SCHEME
87BB1 BUSBAR-1 79 CVT VBB1 VBB1 VL1 / VL2 OR VBB2 25 BF 87L 21M2 VL1 CVT VL1 FEEDER1 / LINE1 79 VL1 / VBB1 VL2 / VBB2 25 87R 21M1 VL1

VL1/VBB1/VBB2

BF

64R 21R

87R

TEED-1 BF VBB2 VL2 / VL1 OR VBB1 CVT VBB2 VBB1/VBB2 79 25 TEED-2

64R

PROTECTION OF BUS REACTOR 21R BUSBAR-2 FOR REACTOR PROTECTION & METERING VOLTAGE SELECTION RELAYS FOR BUS-1, BUS-2& LINE ARE PROVIDED .

87BB2

U UU
OR

U UU

U UU

LINE/BUS REACTOR DIFFERENTIAL PROTECTION


(LOW IMPEDANCE DIFFERENTIAL PROTECTION)
CT MB

P2 P2 P2 R-CT CORE-1
CTR: 200/1A

CT MB

RET 670

3S1 3S2

3 3 3
3S2 3S2

3S1

3S1

CLASS: PS

IN CASE OF REACTOR BUSHING CT P2 IS AWAY FROM REACTOR & P1 IS TOWARDS REACTOR

3 3 3
1S2 1S2 1S1 1S1

HV BUSHING

1S2 1S1

ACTIVE

START

TRIP

P2 P2 P2 R-CT

DISPLAY C

STAR BUSHING CORE-3


CTR: 200/1A

CLASS: PS

NORMALLY LOW / HIGH IMPEDENCE DIFFERENTIAL RELAY IS USED FOR BUS / LINE REACTOR DIFFERENTIAL PROTECTION

LINE/BUS REACTOR DIFFERENTIAL PROTECTION


(HIGH IMPEDANCE DIFFERENTIAL PROTECTION)
P2 P2 P2 R-CT HV CORE-1
CTR: 200/1A

CLASS: PS P1 P1 P1

R-CT STAR CORE-3


CTR: 200/1A

CLASS: PS

3 3 3

BUSHING CT

3 3 3

BUSHING CT

RET 670
1S2 1S2 1S2 ACTIVE START TRIP 1S1 1S1 1S1

DISPLAY C E
NORMALLY LOW / HIGH IMPEDENCE DIFFERENTIAL RELAY IS USED FOR BUS / LINE REACTOR DIFFERENTIAL PROTECTION
IN CASE OF REACTOR BUSHING CT P2 IS AWAY FROM REACTOR & P1 IS TOWARDS REACTOR

P1 P1 P1

3S1 3S1 3S1

3S2 3S2 3S2

P2 P2 P2

LINE/BUS REACTOR REF PROTECTION


(NGR IS NOT AVAIALBLE)
P2 P2 P2 R-CT HV CORE-2
CTR: 200/1A

CLASS: PS P1 P1 P1

R-CT STAR CORE-4


CTR: 200/1A

CLASS: PS IN CASE OF REACTOR BUSHING CT P2 IS AWAY FROM REACTOR & P1 IS TOWARDS REACTOR

3 3 3

BUSHING CT

3 3 3

BUSHING CT

RET 670
2S2 2S2 2S2 ACTIVE START TRIP 2S1 2S1 2S1

DISPLAY C E

P1 P1 P1

NORMALLY HIGH IMPEDENCE VOLTAGE/CURRENT OPERATED SINGLE POLE RELAY IS USED FOR BUS / LINE REACTOR RESTRICTED EARTH FAULT PROTECTION. PRESENTLY NUMERICAL DIFFERENTIAL RELAYS HAVING IN BUILT FUNCTION OF 2 REF OR 2 SEF PROTECTIONS.

4S1 4S1 4S1 4S2 4S2 4S2

P2 P2 P2

LINE REACTOR REF PROTECTION


(NGR IS AVAIALBLE)
P2 P2 P2 R-CT HV CORE-2
CTR: 200/1A

CLASS: PS P1 P1 P1

NGR-CT EARTH CORE-2


CTR: 200/1A

CLASS: PS IN CASE OF REACTOR BUSHING CT P2 IS AWAY FROM REACTOR & P1 IS TOWARDS REACTOR

3 3 3

BUSHING CT

3 3 3

BUSHING CT

RET 670
2S2 2S2 2S2 ACTIVE START TRIP 2S1 2S1 2S1

DISPLAY C E

P1 P1 P1

NORMALLY HIGH IMPEDENCE VOLTAGE/CURRENT OPERATED SINGLE POLE RELAY IS USED FOR BUS / LINE REACTOR RESTRICTED EARTH FAULT PROTECTION. PRESENTLY NUMERICAL DIFFERENTIAL RELAYS HAVING IN BUILT FUNCTION OF 2 REF OR 2 SEF PROTECTIONS.

2S1 2S1 2S1 2S2 2S2 2S2

P2 P2 P2

LINE REACTOR 2 NOs REF PROTECTIONS


(NGR IS AVAIALBLE)
P2 P2 P2 CT MB R-CT HV CORE-2
CTR: 200/1A

P2 P2 P2

CLASS: PS P1 P1 P1

R-CT STAR CORE-4


CTR: 200/1A

CLASS: PS

3 3 3

BUSHING CT

3 3 3

BUSHING CT

RET 670
2S2 2S2 2S2 ACTIVE START TRIP 2S1 2S1 2S1
1S2 1S1

3 3 3
1S1 1S1

1S2

1S2

DISPLAY C E
NORMALLY HIGH IMPEDENCE VOLTAGE/CURRENT OPERATED SINGLE POLE RELAY IS USED FOR BUS / LINE REACTOR RESTRICTED EARTH FAULT PROTECTION. PRESENTLY NUMERICAL DIFFERENTIAL RELAYS HAVING IN BUILT FUNCTION OF 2 REF OR 2 SEF PROTECTIONS. P1 P1 P1 NGR-CT BUSHING CT CORE - 1 & 2
CTR: 200/1A

CLASS: PS

CT MB

P1 P1 P1

P1 P1 P1

4S1 4S1 4S1 4S2 4S2 4S2

2S1 2S2

3 3 3
2S2 2S2

2S1

2S1

P2 P2 P2

P2 P2 P2

LINE/BUS REACTOR B/U IMPEDANCE PROTECTION

P2 P2 P2 R-CT HV CORE-3
CTR: 200/1A

CT MB IR3 / A311 IY3 / A331 IB3 / A351 VR11 / E111 VY11 / E131 VB11 / E151 VN11 / E171 CVT SELECTION BUS-1 CVT / BUS-2 CVT / LINE CVT CORE-1
VA : 200

CLASS: PS

3 3 3
3S2 3S2 3S1 3S1

BUSHING CT

REL 670
ACTIVE START TRIP

3S2 3S1

IN3 / A371

DISPLAY C E

CLASS: 3P

LINE REACTOR PROTECTION FOR LINE


(MAIN-1 PROTECTION)
P2 P2 P2 1-CT
CTR: 2000-1000-500/1A

CT MB IR5 / A511 IY5 / A531 IB5 / A551 VR11 / E111 VY11 / E131 VB11 / E151 VN11 / E171 1-CVT

CLASS: PS

2-BCT
CTR: 2000-1000-500/1A

CLASS: PS

LR-CT 400KV
CTR: 2000-1000-500/1A

CLASS: PS P1 P1 P1

3 3 3

CORE-5

3 3 3

CORE-5

3 3 3
5S4 5S4 5S2 5S2 5S2 5S2 5S4 5S4 5S4 5S4 5S2 5S2

CORE-5

REL 521
ACTIVE START TRIP

5S4 5S2

IN5 / A571

DISPLAY C
5S2 5S4

CORE 1 200VA CLASS: 3P

P2 P2 P2

5S4 5S2

LINE REACTOR PROTECTION FOR LINE


(MAIN-2 PROTECTION)
P2 P2 P2 1-CT
CTR: 2000-1000-500/1A

CT MB IR4 / A411 IY4 / A431 IB4 / A451 VR21 / E211 VY21 / E231 VB21 / E251 VN21 / E271 1-CVT

CLASS: PS

2-BCT
CTR: 2000-1000-500/1A

CLASS: PS

LR-CT 400KV
CTR: 2000-1000-500/1A

CLASS: PS P1 P1 P1

3 3 3

CORE-4

3 3 3

CORE-4

3 3 3
4S4 4S4 4S2 4S2 4S2 4S2 4S4 4S4 4S4 4S4 4S2 4S2

CORE-4

REL 316
ACTIVE START TRIP

4S4 4S2

IN4 / A471

DISPLAY C
4S2 4S4

CORE 2 200VA CLASS: 3P

P2 P2 P2

4S4 4S2

BUS REACTOR TEED-1 PROTECTION


P2 P2 P2 3-CT
CTR: 2000-1000-500/1A

{BAY3&2} IR5 IY5 IB5

CLASS: PS P1 P1 P1 P2 P2 P2 2-CT
CTR: 2000-1000-500/1A

CLASS: PS

BR-LCT
CTR: 2000-1000-500/1A

CLASS: PS

3 3 3

CORE-5

3 3 3

CORE-1

3 3 3
5S4 5S4 5S2 5S2 1S4 1S4 1S2 1S2 4S4 4S4 4S2 4S2

CORE-5

5S4 5S2

IN5

RET 670
IR5 IY5 IB5 IN5
P1 P1 P1 P2 P2 P2
ACTIVE START TRIP

1S4 1S2

DISPLAY C E

IN1
4S4 4S2

IB1 IY1 IR1


P1 P1 P1

IT WORKS ON CIRCULATING CURRENT PRINCIPLE AND IT IS HIGH IMPEDENCE DIFFERENTIAL RELAY. TEED-1 PROTECTION FOR BAY 2&3 AND THE FOLLOWING CTs & CORES ARE USED 3-CT(CORE-5), 2-CT(CORE-1) & BR-CT (CORE-5) ARE STARRED AND CONNECTED TO TEED-1 PROTECTION

BUS REACTOR TEED-2 PROTECTION


{BAY3&2} RAICA LBB/BFR
P2 P2 P2 3-CT
CTR: 2000-1000-500/1A

CT MB

CT MB

P2 P2 P2

CLASS: PS

BR-CT
CTR: 2000-1000-500/1A

CLASS: PS

3 3 3

CORE-4

3 3 3
4S4 4S4 4S2 4S2 4S4 4S4 4S2 4S2

CORE-4

4S4 4S2

RAICA LBB/BFR

RET 670
ACTIVE START TRIP

2S4 2S2

3 3 3
2S2 2S2

2S4

2S4

2-CT

DISPLAY
P2 P2 P2 CT MB

CORE-2
CTR: 2000-1000-500/1A

CLASS: PS

C
4S4 4S2

IT WORKS ON KIRCHOFFS CURRENT PRINCIPLE & IT IS PERCENTAGE BIASED LOW IMPEDENCE DIFFERENTIAL RELAY. TEED-2 PROTECTION FOR BAY 2&3 IS THE FOLLOWING CTs & CORES ARE USED. 3-CT(CORE-4), 2-CT(CORE-2) & BR-CT (CORE-4) ARE CONNECTED TO TEED-2 PROTECTION.

OVER EXCITATION/FLUX RELAY


{FOR LINE & BUS REACTORS}
VOLTAGE SELECTION BUS-1 PT / BUS-2 PT CORE-1
VA : 200

RATUB V/F RELAY LINE

CLASS: 3P

CVT SELECTION BUS-1 CVT / BUS-2 CVT / LINE CVT CORE-1


VA : 200

RATUB V/F RELAY BUS

CLASS: 3P

REACTOR MULTI FUNCTION PANEL METERING


P2 P2 P2 R-CT STAR CORE-2
CTR: 200/1A

CT MB IR2 / D211 IY2 / D231 IB2 / D251

CLASS: 0.2

3 3 3
2S2 2S2 2S1 2S1

BUSHING CT

2S2 2S1

IN2 / D271

VR31 / E311 VY31 / E331 VB31 / E351 VN31 / E371 BASED ON SELECTION LINE CVT / BUS-1 CVT / BUS-2 CVT CORE 3 100VA CLASS: 0.2

CARRIER INTERTRIPPING OF LINE SHUNT REACTOR


LINE SHUNT REACTOR PROTECTION TRIPPINGS WILL BE USED AS DIRECT TRIPPINGS OF LINE IN ADDITION TO OTHER TRIPPINGS. BUS SHUNT REACTOR NEED NOT REQUIRE CARRIER INTER TRIPPING FACILITY.
87R REACTOR DIFFERENTIAL RELAY RET 670 21R REACTOR IMPEDENCE RELAY REL 670
64R RESTRICTED EARTH FAULT RELAY

ABB NSD 50
DC +VE FROM PANEL

LINE PROTECTION COUPLER PANEL-1

RET 670 REACTORS INTERNAL FAULTS GROUP-1/A TRIPPINGS

G4AD V9LC 2 G4AD V9LC 1


DC VE FROM PANEL

87R REACTOR DIFFERENTIAL RELAY RET 670 21R REACTOR IMPEDENCE RELAY REL 670
64R RESTRICTED EARTH FAULT RELAY

ABB NSD 50
DC +VE FROM PANEL

LINE PROTECTION COUPLER PANEL-2

RET 670 REACTORS INTERNAL FAULTS GROUP-2/B TRIPPINGS

G4AD V9LC 2 G4AD V9LC 1


DC VE FROM PANEL