Apparatus Maintenance and Power Management for Energy Delivery

F6MCP Control Panel for MW/MVAR Meter/Transducer Testing


Kamin Dave Application Engineer (Protective Relaying)

DOBLE ENGINEERING COMPANY

F6MCP: CASE 1

MW/MVAR Transducer Testing with F6150

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: 3V X 3I

F6150 Configuration: 3V X 3I Meter/Transducer Configuration: 3V X 3I

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: 3V X 3I Connection diagram


63.5V@0o VA 63.5V@240o VB 63.5V@120o VC VA VB VC I1 I2 I3
Meter/ Transducer

F6150
I1 I2

1A@0o 1A@240o 1A@120o I3

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: 3V X 3I software view

Input: 191w

Output: based on Transducer output


Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: 3V X 3I Power Calculation


F6150 Configuration: 3V X 3I Meter/Transducer Configuration: 3V X 3I Power in secondary side: Vsec = 110V (L-L) & 63.5V (L-N) Isec = 1A Power factor = unity = 1 Psec = 1.3725*Vsec (L-L)*Isec*cos(0o) = 1.7325*110*1*1 = 190.52 watts
Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: CASE 1

Software display shows: Input: 190.52 watts based on F6150 input Output: 190.52 watts based on Transducer output

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: CASE 2

MW/MVAR Transducer Testing with F6150

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: 3V X 2I

F6150 Configuration: 3V X 3I Meter/Transducer Configuration: 3V X 2I Meter/Transducer calculating 3-phase Power output

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: 3V X 2I Connection diagram


63.5V@0o VA 63.5V@240o VB 63.5V@120o VC VA VB VC I1
Meter/ Transducer

F6150
I1 I2 I3

1A@0o 1A@240o 1A@120o

I3

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: 3V X 2I

Short link Red & Black terminals of Source I2 Magnitude of I2 = 1A@240o

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: 3V X 2I software view

Input: 191w

Output: based on Transducer output


Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: 3V X 2I Power Calculation


F6150 Configuration: 3V X 3I Meter/Transducer Configuration: 3V X 3I Power in secondary side: Vsec = 110V (L-L) & 63.5V (L-N) Isec = 1A Power factor = unity = 1 Psec = 1.3725*Vsec (L-L)*Isec*cos(0o) = 1.7325*110*1*1 = 190.52 watts
Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: CASE 2

Software display shows: Input: 190.52 watts based on F6150 input Output: 190.52 watts based on Transducer output

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: CASE 3

MW/MVAR Transducer Testing with F6150

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: 3V X 2I

F6150 Configuration: 3V X 2I Meter/Transducer Configuration: 3V X 2I Meter/Transducer calculating 3-phase Power output

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: 3V X 2I Connection diagram


63.5V@0o VA 63.5V@240o VB 63.5V@120o VC VA VB VC I1
Meter/ Transducer

F6150
I1 I2 I3

1A@0o 0A@240o 1A@120o

I3

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: 3V X 2I

Short link Red & Black terminals of Source I2 Magnitude of I2 = 0A@240o

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: 3V X 2I software view

Input: 127w

Output: based on Transducer output


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: 3V X 2I Power Calculation


F6150 Configuration: 3V X 2I Meter/Transducer Configuration: 3V X 3I Power in secondary side: Vsec = 110V (L-L) & 63.5V (L-N) Isec = 1A Power factor = unity = 1 Psec = (2/1.3725)*Vsec (L-L)*Isec*cos(0o) = (2/1.7325)*110*1*1 = 127 watts
Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: CASE 3
Software display shows: Input: 127 watts based on F6150 input Output: 190.52 watts based on Transducer output In this case Input & Output will not match because transducer calculating 3-ph power & software calculating 2-ph power based on F6150 source configurations
Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: CASE 3

How to set the values in Primary?

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: CASE 3

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: CASE 3

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: CASE 3

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6MCP: 3V X 2I Power Calculation


F6150 Configuration: 3V X 2I Meter/Transducer Configuration: 3V X 3I Power in secondary side: Vsec = 110V (L-L) & 63.5V (L-N) Isec = 1A VTR = 11500 / 110V = 104.54 CTR = 100 / 1 = 100 Power factor = unity = 1 PPri = (2/1.3725)*Vsec (L-L)*Isec*cos(0o)*CTR*VTR = (2/1.7325)*110*1*1*(104.54)*(100) = 1.327 Mwatts
Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

DOBLE ENGINEERING PVT. LTD 305, SAKAR, OLD PADRA ROAD, VADODARA. PH: (0265) 655 77 15 & Fax: (0265) 235 62 85 Cell: +91 94267 47545 E-MAIL: kdave@doble.com, infokamindave@yahoo.com Website: www.doble.com