Unit Qty Rate Amount
SL Rs. SL Rs.
1.00 The Bidder is requested to refer the Bill of Quantities,
General Note, Pricing Preambles, drawing, specification,
conditions of contract, special conditions of contract and
other relevant documents prior to pricing of items in this
trade
Note
2.00 Rates shall include for supply, installation, commissioning
and maintaining of the following items according to
drawings, specifications and complete to working order
with all connections to the approval of the consultant,
Fire Department and other relevant authorities.
Note
3.00 It is the contractor's responsibility to obtain approval from
relevant fire authorities whenever necessary, before and
after installation of items in this trade
Note
4.00 The bidder shall submit the following information on the
items/equipment quoted for together with the bid
1. Make
2. Model
3. Technical data
4. Country of manufacture
5. Delivery period
6. Lead time for manufacturing
7. Port of shipping
8. CIF value of each item in foreign currency
9. Schedule I, II & III attached
10. Schedule of equipment & materials
5.00 The rates shall include for providing insurance during
handling, rehandling, transport, storage until ready
installation, delivery of equipment up to the point of
installation and until handling over
Note
6.00 All equipment shall be guaranteed for a period of 12
months from the date of commissioning
Note
7.00 The bidder shall provide all dimension, technical
information of all necessary builders work to the
consultant in advance in relation with the programme of
work Note
8.00 All pipes pipe shall be heavy grade galvanized steel Note
9.00 Contractor shall be provided the list of items to be
supplied under BOI facilities along with the bid Note
10.00 Rates for all pipes shall include for all pipe supports,
hangers, saddles, brackets, screws, nails, tees, bends,
sockets, reducers and the like and fixing material, cutting
holes and chases in concrete brick/block work, etc, any
builders work require and making good in all trades unless
otherwise measured separately
Note
11.00 All valves and fittings approved quality European or
Japanese make only Note
Part - A - External Fire Protection System
Fire Protection System of Proposed Building Complex for .
No Description
12.00 All fixed pipes in and out to the building shall have
flexible connection to accommodate moment due to any
structural settlements to avoid any cracks
Note
13.00 Rate of pipe shall include fire barriers, sleeves, Hume
pipes & other material as specified when passing through
wall or met with an other services
Note
14.00 Water connection to water /fire sump has been measured
in separate contract Note
Fire Pumps
15.00 All pumps installation should be according to relevant
NFPA, ENBS Note
16.00 Installation of Horizontal Centrifugal (multistage type)
end suction type electrical driven fire pump capacity 1900
L/min, pump head 11.0 bar fire pump 400V/3ph/50hz
"Grundfos" or equivalent approved make including pump
bed, hardware tools and fixing materials and complete
with electrical connection to panel to working order as
per details drawing & specification (Pump control panels
measured separately)
Nr. 2.00
Fire J ockey (Booster) Pump
17.00 Installation of Centrifugal, vertical multi stage type
electrically operated fire jockey pump "Grundfos" or
equivalent approved make with a capacity not less than a
flow rate of 70Ltr/min. against pump head of 11.0 bar,
power supply 400v/3ph/50Hz including pump bed,
hardware tools and fixing materials and compete with
electrical connection to working order as per detail
drawing ( pump control panels measured separately)
Nr. 1.00
18.00 Supply and installation of pressure vessel 750 litter
necessary isolation valve, non return valve, accessories
and pipes as per detail drawing & specification Item 1.00
Valves
19.00 150mm dia Non return valve as per detail drawing &
specification Nr. 2.00
20.00 50mm dia. Non return valve as per detail drawing &
specification
Nr. 1.00
21.00 150mm dia gate valve as per detail drawing &
specification Nr. 4.00
22.00 50mm dia. Gate valve as per detail drawing &
specification Nr. 4.00
23.00 150mm dia. Flexible coupling - do- Nr 4.00
24.00 65 mm PRV (water relies type) Nr 1.00
25.00 150mm dia. Isolating gate valve with under ground valve
chamber as per detail drawing & specification in under
ground ring main system
Nr. 5.00
26.00 150mm dia. Strainer comprising with gate type below
down valve and hose adaptor coupling with cap as per
detail drawing & specification
Nr. 2.00
27.00 150mm dia. Vertex Inhibiter in raw water sump as per
detail drawing & specification Nr. 2.00
28.00 100 dial size pressure gauge with gauge cock Nr. 2.00
29.00 pressure Switch with gauge cock Nr. 3.00
30.00 Allow for approved 150mm suction manifold for complete
to working order as per detail drawing & specification
(fittings and other accessories)
item 1.00
31.00 Allow for approved 150mm discharge manifolds for
complete to working order as per detail drawing &
specification (fitting and other accessories)
item 1.00
Fire Pump Control Panels
32.00 Electrical supply cable to pump control panel has been
measured under electrical installation Note
33.00 Installation of Fire pump control panel complete with
approved quality electrical switch gears, volt, meters,
ammeters, alarm, level control, low level float switch
wiring system and alarm indicator, change over switches
and starter in single metal enclosure complete with push
button starter switches and auto manual selector's
switches, pressure control switches etc.. to proper
working order including al electrical connections to alarm
control panel, remote on/off and indicators as per detail
drawing & specification and necessary earthling.
item 1.00
External Fire Hydrant
Ring Main
34.00 All pipes & fitting shall comply with relevant specification
as specified in drawing & specification Note
35.00 Rates for all pipes shall include for all pipe fittings, fixing,
and hanging to the approval and finish with one coat of
zinc rich primer and minimum two coats of Red color anti
corrosive enamel paint as per specification where ever
applicable
Note
36.00
All underground pipes shall be heavy grade galvanized
steel (seamless) and galvanized thickness to be minimum
100-120 microns as per detail drawing & specification (mill
or other certificate need to submit and approved) Note
37.00 All pipe connection to be welded flange connection and
connected nut & bolt to be hot dip galvanized. (50mm dia
above)
Note
38.00 All flange pipe connection to be at least provided in every
two length of pipe Note
39.00 Air release valve to be provided at the highest level and
drain valves at lowest level on the fire hydrant piping
system.
Note
40.00 Rate to include under ground pipes wrapped with tow
layers of "DENSO" bituflex or equivalent type of tape prior
to installation in oder to prevent the pipe from corrosion
Note
41.00 The gaskets used in-between matching flange shall be
suitable for underground application with water resistance
type and durable construction.
Note
42.00 Rate to include all necessary excavation, concrete work,
form work, sand filling & back filling, compaction,
concrete thrust block, concrete hard stand and etc. for all
underground pipes & above ground pipe rate shall include
to concrete footing, all pipes supports, clips and etc. as
per the drawings and specifications
Note
43.00 Excavation bed rock with breaking depth not exceeding
0.5m M2 1.00
44.00 Excavation hard rock with chemical blasting depth not
exceeding 0.5m M2 1.00
45.00 Excavation hard rock with control blasting depth not
exceeding 0.5m M2 1.00
46.00 150mm dia. Above ground Heavy duty seam Galvanized
pipe as per drawing and specification. Rate shall include
to all necessary accessories
M 30.00
47.00 150mm dia. Under ground heavy duty seamless Galvanized
fire hydrant line as per the drawings and specifications
M 450.00
48.00 100mm dia. Under ground heavy duty seamless finish GI
pipe connecting to pillar hydrants, HR & LV as per
drawings and specification.
M 200.00
49.00 100mm dia. Above ground heavy duty seam finish GI pipe
connecting to pillar hydrants, HR & LV as per drawings and
specification.
M 200.00
50.00 50mm dia. Under ground heavy duty seamless finish G I
pipe connecting as per drawings and specification m 50.00
51.00 65mm dia. Above ground heavy duty seam finish G I pipe
connecting as per drawings and specification m 50.00
52.00 50mm dia. Above ground Heavy duty seam finish G I pipes
connecting as per drawings and specification m 200.00
53.00 25mm dia above ground Heavy duty seam finish G I pipes
connecting as per drawings and specification
m 50.00
54.00 150 dia - 4 way fire service breaching inlet point as per
detail drawing and specification. Rate shall include
breaching inlet box, swing check valve, copper tape, earth
road clamp, earthing rod and etc. as per detail drawing
and specification
nr 1.00
Fire Hoses in Exposed Fire Cabinets
55.00 Nozzle not measured separately but to be included with
fire hose. note
56.00 Two way pillar type fire hydrant having 02x65mm outlets
as per drawings and specification
nr 7.00
57.00 Approved quality 2 No 65mm dia 15m long fire hose
complete with instantaneous coupling one/jet/spray/shut
off and branch pipe etc. Fire hose to comply BS 3169 all
housed in weather proof type fire cabinet shall marked
with " Fire Hydrant & Fire Hose" in white lettering Red
background. Fire cabinet to be installed closer to the
pillar hydrant as per details drawing & specification. rate
to include necessary concrete plinth as per detail drawing
set 7.00
Testing and Commissioning
57.00 Allow for testing and commissioning of the total fire
protection and fighting system to the entire satisfaction
of the consultant and local fire authority and submission
of commissioning report in triplicate
item 1.00
Shop drawings
59.00 Allow for submission of 3 sets of shop drawings for
approval prior to ordering of materials and
commencement of construction of work for the approval
of the Consultants/engineer
item 1.00
As Built Drawings
60.00 Allow for submission of 3 sets of as built drawings at the
commission of the system for the approval of the
Consultants including manuals
item 1.00
Builder's work in connection with
61.00 Allow for providing all necessary builder's work in connection with including following items
a Making opening in floor slab, walls
b Bases for equipment
c Masonry work in relation for fixing
d Conducting
e all other builders work not stated above for fire
protection, detection and fighting system item 1.00
Any other item
62.00 Allow for any other item necessary for the satisfactory
completion of the system but not included above(submit
details with the tender)
item 1.00
Total for External Fire Protection System carried
forward to summary sheet 0.00