01 WATER & FIRE TANK CONNECTIONS
Supply, install connect and test water and fire tank connections and accessories
complete, including but not limited to covers, stainless steel ladders, sleeves,
galvanized black seamless steel buddle flange sch.40, access doors (two for each tank
compartment, filling mechanical float valves, electrically actuated butterfly valves,
isolating valves, water level control system, water leak alarm system (Ultrasonic level
indicator), dismantling joint and all other required pipe connections, fittings, bolts,
nuts, gaskets, supports, paint, cleaning, tags, labels, flow indicator, color code finishing
and all accessories as specified and as shown on drawings
01.1 Water and fire tanks piping connections for main water tank. L.S 1 1
02 DOMESTIC WATER PIPING AND FITTING MATERIALS
02.1 Supply, install, connect, test and commission all steel domestic water piping system
within pump room complete including pipes, strainer for bosser pumps, fittings,
flanges, galvanized seamless black steel sch.40, valves, hangers, over flow, bolts, nuts,
gaskets, supports, paint, cleaning, tags, labels, flow indicator, color code finishing and
all accessories as specified and as shown on drawings and specification.
L.S 1 1
03 FIRE FIGHTING PIPING AND FITTING MATERIALS
03.1 Supplying, installing, connecting ,commission and testing all galvanized seamless
black steel piping sch.40 works for fire protection system within the pump room
including fire and jockey pumps suction and delivery piping system, fire pump test
line back to the tank, test line flow meter, relief line, connecting relief valves to pump
room, drain points, water level connection systems, all OS&Y valves with tamper
switches, fire alarm control modules, hangers, bolts, nuts, gaskets, supports, paint,
cleaning, tags, labels, flow indicator, color code finishing and all accessories as
specified and as shown on drawings and NFPA requirements.
L.S 1 1
04 MAIN WATER METER
Supply, install, connect and test turbine type water meter complete and conforming
to the requiremments of AWWA standard C702 and to local governing authorities
requirement. Water meter to be installed on water
main supply system line at pump room and to be connected to B.M.S system
06 WATER TREATMENT BOOSTER PUMP
Supply, install, test, commissoning and startup an automatic factory packaged,
prefabricated, tested certifed and guaranteed constant speed constant pressure water
booster pumping system at 2900 rpm complete with all , cabel 20 m length, controls,
motors, valves, galvanized suction and discharge pipe manifold with all
interconnecting piping flanche and wiring, as well as, copper tubing with shutoff
cocks for gauges, pressure switches, galvanized base, vibration-isolating mounts and
control panels.. etc., all
mounted on a common galvanized structural steel base prior to shipment.
06.1 doublex Water Treatment Booster Pumps 65 gpm flow rate 70 ft.head each
(1 working , 1 stand by) set 1 1
07 WATER SUPPLY SAND FILTER
Supply, install commissoning and test rapid sand filter complete with all accessories,
valves, pressure gage, vent, drain and relive valve with media charge and Material
fiber glass, working at 2 bar as specified and as shown
on drawings, maximum surface filteration rate should not exceed
07.1 High rate press sand filter of multilayer capacity 65 GPM filtration rate, 900 mm
diameter . No. 2 2
08 WATER TREATMENT FILTRATION SYSTEM
Supply, install, connect, test and commission an automatic factory packaged
perfabricated tested, certifed guaranteed compete multimedia filtration system 10
bar working pressure to produce a maximum of 5 NTU complete with filter, tank, inlet
distributors, drains, gravel supporting beds, filtration media, filter exterior valving,
filter piping & system accessories
and controls, including spare parts all as per specifications and as shown
08.1 Complete packaged water filtration system, for general water supply facilaities with
65 gpm capacities. No. 2 2
09 ELECTRICAL FIRE FIGHTING PUMP
Supplying, installing, connecting, testing and commissioning an automatic, factory
assembled wired and tested electric driven fire pump system consisting of the pump,
motor, control panel and controller, (pump & motor) to be 1000 GPM at a design head
of 360 feet TDH & 145 H.P when operating at 3500 RPM. The pump complete package
shall be UL listed and FM approved including all accessories and fittings all as
specified and as
09.1 Electric Fire pump 1000 gpm flow rate 330 ft.head . SET 0 1
09.1 Electric Fire pump 1000 gpm flow rate 360 ft.head . SET 1 0
10 DIESEL FIRE FIGHTING PUMP
Supplying, installing, connecting, testing and commissioning an automatic, factory
assembled wired and tested deisel driven fire pump system consisting of the pump,
motor, control panel and controller, (pump & motor) to be 750 GPM at a design head
of 360 feet TDH when operating at 3500 RPM. The pump complete package shall be
UL listed and FM
approved including all accessories and fittings all as specified and as
10.1 Diesel Fire pump 1000 gpm flow rate 330 ft.head . SET 1 0
10.1 Diesel Fire pump 1000 gpm flow rate 360 ft.head . SET 0 1
11 JOCKEY FIRE FIGHTING PUMP
Supplying, installing, connecting, testing and commissioning an automatic packaged
vertical multi-stage jockey pump having a design cap. of 25 GPM at a design head of
385 feet TDH, & 4 H.P complete including the UL listed controller, electric control
panel and all other accessories as specified and
as shown on drawings.
11.1 Jockey Fire pump 25 gpm flow rate 350 ft.head No. 0 1
11.1 Jockey Fire pump 25 gpm flow rate 385 ft.head No. 1 0
12 MAIN FIRE ALARM CHECK VALVE
Supplying, installing, connecting, testing and commissioning an main alarm check
valve complete with all accessoires including the UL&FM listed, gain, retardant
champers, hangers, bolts, nuts, gaskets, paint, cleaning, tags,
labels, flow indicator, color code finishing as specified and as shown on
13.1 Submersible Pump 45 gpm at 70 ft head for pump room.(1 working + 1stand-by) SET. 1 0
13.1 Submersible Pump 45 gpm at 50 ft head for pump room. (1 working + 1stand-by) SET. 0 1
14 SUMP PIT
Form sump pit for submersible pumps including additional excavation, backfilling,
removing surplus excavated material, concrete, formwork, reinforcement, water
proofing, with heavy duty ductile iron cover and
frame to EN 124, and frames as Specification and drawings.
WATER TANK AND PUMP ROOM WORKS LE
TOTAL
عورشم: ناكسالو هحصال ةرازو – جاهوس ةظفاحم – ىزكرمال انيلبال ىفشتسم ءاشنا
Page No. 01
Page No. 02
Page No. 03
WATER TANK AND PUMP ROOM WORKS LE
TOTAL