The heat pump shall have an in-built facility to start /stop depending on
variation in demand at different periods(1w+1s) Each
12.3 Pumps :
Providing, fixing, testing & commissioning of Horizontal centrifugal
monoblock pump set with cast iron body, with SS impeller, stainless
steel shaft coupled with TEFC squirrel cage induction motor suitable for
operations on 415/440 volts, 3 phase, 50 Hz, AC supply mounted on
common M.S. channel base frame.
12.4.3 Providing, fixing, testing and commissioning lever operated gun metal
Ball Valve with SS ball.
a) 50 mm dia Each
b) 65 mm dia Each
12.4.6 Providing, fixing, testing and commissioning gun metal dial type
pressure gauge (150mm dia) of rating 0-10 kg./cm2 with gun metal
isolating cock pig and connecting pipe. Each
12.5.1 Providing, fixing, testing and commissioning of dust, damp and vermin
proof, free floor standing factory built sheet steel enclosed nondrawout
modular panel for water supply pumps, fabricated out of suitable sized
square tubular section and covered with 2.0mm thick CRCA sheet,
hinged doors of 2mm thick CRCA sheet, duly painted complete with
earth bus, necessary metering protections & indications and mounted
with the following including all inter connection etc. (Including earthing).
(Indoor type)
a) One No. 100 amps TP incoming MCB complete with the following:
i) 1 No. 0-500 volts 96x96 sq. mm ammeter with selector switch and
fuses. (1 set).
ii) 1 No. 0-100 amps 96x96sq.mm ammeter with 60/5 amps ratio CT's and
selector switch.
iii) Phase indicating lamps with toggle switches.
iv) Indication lamps for ON/OFF/TRIP status of motors.
b) Aluminium bus bar of 100 amps for three phase and neutral.
c) Out going feeders/Starters
i) 2 Nos. 63 amps TPN MCB each suitable for 10.3 KW Air cooled heat
pumps panel.
ii) 4 Nos. 10 amps DP MCB with Dol starter each suitable for 1 HP motor
for hot water circulation & hot water retun pumps.
iii) Spares TPN MCB's 32 amps 2 Nos.
Note :
a) All switch gear/panels shall be suitable for 25 KA rating.
b) All outgoing will have 96 sq. mm size ammeter and CT.
c) All starter units for pumps to be provided with 3 level liquid level
contractor.
d) All outgoing starter units to have "ON" red lamps.
e) All pumps to be provided with duty selector switch.
f) All pumps to be provided with sequence timer 220/440 V AC/DC and
alternate working of pumps between 6 to 8 hours or alternate use of
pumps after one service in sequence.
g) All pumps to be provided with over load relay.
h) Necessary cable alleys for space switches, level controller internal
wiring and copper earthing of all equipment shall also be included. All
switch gears/control gears shall be motor duty rating. Set
12.5.2 Providing, laying, jointing, testing, & commissioning the PVC insulated
& sheathed FRLS Armoured cables of 1.1 K.V. Aluminium Conductor
including supplying and making and termination with brass
compression glands:
80
10
80
10
2
6
2
5
2
4
1
40
50