0 HOT WATER HEAT PUMP SYSTEM 38 KW HEAT PUMPS

12.1 AIR COOLED HEAT PUMP FOR GENERATING HOT WATER


Providing, fixing, testing and commissioning of Micro Processor
Controlled air cooled Heat pump delivering actual capacity as per the
following parameters .
Heat pumps shall be rated at 10.3 KW of input power and 38 KW of
output power. Refrigerant used should be environment friendly R-
410a. Heat pump should heat water upto 55⁰C on heat pump mode. It
shall have silent operation and the sound level should not exceed 65
dB.
Refrigerent
R-410a/6.2 kg ( Refrigerant)
Heat Pump as described above
Nominal Input Power - 10.3 KW
Output Heating capacity - 38 kW
Heat pump shall have LCD display control panel with built in diagnostic
and troubleshooting information
Heat pump should have an inbuilt cycle for defrosting in case icing
occurs on evaporator.
with inbuilt tube in tube type heat exchanger.
All other mounting ,fitting and controls
Suitable for electric supply of 380 +/- 10 % volts & 3N~ 50 hz
All interconnecing wiring/cabling between heat pump and electric panel

The heat pump shall have an in-built facility to start /stop depending on
variation in demand at different periods(1w+1s) Each

Note: Contractor to revalidate design of Pumps based on selected heat


pump capacity.

Cost of shifting of Heat Pump at desired level shall be included in this


item.

12.2 Hot Water Storage Tank

Providing, fixing testing & commissioning of SS 304 horizontal hot


water storage tank (Capacity 6000 Ltrs) suitable for minimum 6 Kg
/Sqm working pressure. Tank shall be provided with water flow meter
at inlet (approved by department of weights and measures), inlet /
outlet, overflow / drain connection with MH cover 6 mm thick SS tank,
pressure relief valves, pressure gauge at inlet / outlet with isolation
cock, thermometer at inlet / outlet. All the valves & accessories shall
be suitable for an operating pressure of 6 Kg/sq.cm.
Tank shall be insulated with glass wool insulation including 24 gauge
aluminium cladding. Tank shall provided with 15 mm dia testing spout
with valve (inlet temperature to hot water storage tank 60-65 deg.C).
The flanges shall be machined from SS304 sheets with dimensions
confirming to ANSI, B 16.5 No. 150. The nozzles shall be SS pipes.
(Tank shall be fabricated as per unfired pressure vessel code IS 2825-
1969, IS 226 / IS 2062).

Tank shall be complete with insulation, MS supporting structure with


access ladder duly painted with red oxide with following connections.
Set
1 no. Cold Water inlet 50 mm dia PN10 Ball Valve.
1 no. Cold Water inlet line 50 mm dia Check Valve.
1 no. 20 mm dia Safety Valve.
1 no. 50 mm dia PN10 Ball Valve.
1 no. Hot water return inlet 50 mm dia Ball Valve Valve PN 10
1 no. Tank Drain connection 50 mm PN 10 Ball valve.
1 no. 80 mm Hot Water Outlet.
1 no. 80 mm dia PN10 Ball Valve.

12.3 Pumps :
Providing, fixing, testing & commissioning of Horizontal centrifugal
monoblock pump set with cast iron body, with SS impeller, stainless
steel shaft coupled with TEFC squirrel cage induction motor suitable for
operations on 415/440 volts, 3 phase, 50 Hz, AC supply mounted on
common M.S. channel base frame.

a) Hot water circulation pumps


Discharge : 6000 LPH
Head : 20m Each
(1W+1S) 1 set of 2 nos. for one set of heat pump system

b) Hot water return pumps


Discharge : 12000 LPH
Head : 15m Each
(1W+1S) 1 set of 2 nos. for one set of heat pump system

12.4 Piping, valves & accessories:

12.4.1 Providing, fixing, testing and commissioning of Chlorinated Polyvinyl


Chloride (CPVC) pipes, for Hot water circulation & return pumps
suction & delivery piping including all CPVC plain & brass threaded
fittings. This includes jointing of pipes & fittings with one step CPVC
solvent cement, testing of joints complete as per direction of Engineer
in Charge.

a) 50 mm NB (SDR-11 ASTM D-2846) Metre


b) 65 mm NB (SCH-40 ASTM F-441) Metre
12.4.2 Providing, fixing, testing and commissioning of closed cells class O
insulation 32 mm thick & wrapping with 24 gauge aluminium sheet
cladding giving proper overlaps & sealing the joints with suitable
adhesive compound.
a) 50 mm mm Metre

12.4.3 Providing, fixing, testing and commissioning lever operated gun metal
Ball Valve with SS ball.
a) 50 mm dia Each
b) 65 mm dia Each

12.4.4 Providing, fixing, testing and commissioning gunmetal horizontal Non-


Return Valve with flanged ends tested to 20 kg/cm2. ( 1 no. at inlet of
hydropneumatic system plus 1 no. each at hot water pump)
a) 50 mm dia Each
b) 65 mm dia Each

12.4.5 Providing, fixing, testing and commissioningof CI Y-strainer (Screwed


ends).
a) 50 mm dia Each
b) 65 mm dia Each

12.4.6 Providing, fixing, testing and commissioning gun metal dial type
pressure gauge (150mm dia) of rating 0-10 kg./cm2 with gun metal
isolating cock pig and connecting pipe. Each

12.4.7 Providing, fixing, testing and commissioning of Temperature Gauges of


an approved make. Each

12.4.8 Providing, fixing, testing and commissioning of Air release valves


screwed ends with ball valve of approved brand of manufacture, with
accessories etc., complete.
25mm dia Each

12.5 Electrical control panel & cables:

12.5.1 Providing, fixing, testing and commissioning of dust, damp and vermin
proof, free floor standing factory built sheet steel enclosed nondrawout
modular panel for water supply pumps, fabricated out of suitable sized
square tubular section and covered with 2.0mm thick CRCA sheet,
hinged doors of 2mm thick CRCA sheet, duly painted complete with
earth bus, necessary metering protections & indications and mounted
with the following including all inter connection etc. (Including earthing).
(Indoor type)

a) One No. 100 amps TP incoming MCB complete with the following:
i) 1 No. 0-500 volts 96x96 sq. mm ammeter with selector switch and
fuses. (1 set).
ii) 1 No. 0-100 amps 96x96sq.mm ammeter with 60/5 amps ratio CT's and
selector switch.
iii) Phase indicating lamps with toggle switches.
iv) Indication lamps for ON/OFF/TRIP status of motors.
b) Aluminium bus bar of 100 amps for three phase and neutral.
c) Out going feeders/Starters
i) 2 Nos. 63 amps TPN MCB each suitable for 10.3 KW Air cooled heat
pumps panel.
ii) 4 Nos. 10 amps DP MCB with Dol starter each suitable for 1 HP motor
for hot water circulation & hot water retun pumps.
iii) Spares TPN MCB's 32 amps 2 Nos.

Note :
a) All switch gear/panels shall be suitable for 25 KA rating.
b) All outgoing will have 96 sq. mm size ammeter and CT.
c) All starter units for pumps to be provided with 3 level liquid level
contractor.
d) All outgoing starter units to have "ON" red lamps.
e) All pumps to be provided with duty selector switch.
f) All pumps to be provided with sequence timer 220/440 V AC/DC and
alternate working of pumps between 6 to 8 hours or alternate use of
pumps after one service in sequence.
g) All pumps to be provided with over load relay.
h) Necessary cable alleys for space switches, level controller internal
wiring and copper earthing of all equipment shall also be included. All
switch gears/control gears shall be motor duty rating. Set

12.5.2 Providing, laying, jointing, testing, & commissioning the PVC insulated
& sheathed FRLS Armoured cables of 1.1 K.V. Aluminium Conductor
including supplying and making and termination with brass
compression glands:

a) 3 Core x 2.5 sq.mm Metre


b) 3 Core x 10 sq.mm Metre

12.6 Providing, fixing, testing and commissioning electrical back of 30 kW in


each hot water vessel (to be operated manually) complete with
electrical control panel for electrical backup Nos

TOTAL OF HOT WATER HEAT PUMP SYSTEM CARRIED OVER TO


SUMMARY