L&T CHIYODA LIMITED
CIVIL & STRUCTURAL DEPT
PROJECT
AEP
L&T Job No.
DL 4103
DOC. NO.:- L&T-DESIGN02754
REV. NO.
DESIGN OF FOUNDATION
( with RCC column
F2
)
1. GENERAL :
1.1 SPECIFICATION FOR DESIGN :
THE DESIGN IS IN ACCORDANCE WITH THE FOLLOWING :
SPECIFICATION USED :
DESIGN PHILOSOPHY FOR FOUNDATION FOR HORIZONTAL HEAT EXCHANGER C1R-00017-MSQ-CE-SP-0007
1.2 CODES USED :
IS:456-2000
SP: 16
1.3 MATERIAL USED :
CODE OF PRACTICE FOR PLAIN AND REINFORCED CONCRETE
DESIGN AIDS FOR REINFORCED CONCRETE TO IS:456
LEVELLING CONCRETE :
75
1:4:8
Thick
Nominal Mix
STRUCTURAL CONCRETE :
UNIT WEIGHT OF CONCRETE
gc
24
kN / m3
GRADE OF CONCRETE
fck
20
MPa
fy
415
MPa
UNIT WEIGHT
gs
18
NET SAFE BEARING CAPACITY (SHEAR CRITERION)
SBC
250.0
kN / m3
ALLOWABLE BEARING PRESSURE (SETTLEMENT CRITERION)
ABP
250.0
kN / m3
REINFORCING BAR :
STRENGTH
SOIL PARAMETERS :
kN / m
MISCELLANEOUS DATA :
COVER TO BE PROVIDED FOR MAIN BARS IN FOOTING
COV_F
50
mm
COVER TO BE PROVIDED FOR COLUMN
COV_P
40
mm
FRICTION COEFFICIENT (CONCRETE TO SOIL)
m1
: 0.414
DEPTH OF GROUND WATER TABLE (BELOW HPP)
Dw
: 0.00
L&T CHIYODA LIMITED
CIVIL & STRUCTURAL DEPT
PROJECT
AEP
DOC. NO.:- L&T-DESIGN02754
L&T Job No.
DL 4103
REV. NO.
2.1 GEOMETRY OF FOUNDATION
(UNIT : M)
Lf
3.00
H3
Bf
0.00
2.00
H6 = DF - H1
1.00
Lp
0.600
H2 = H3 + H6
1.00
Bp
0.230
DF
1.50
H1
0.50
HF = H1 + H2
1.50
230
Bp =
2000
B
Bf =
Z
Lecc. =
1200
Lp =
600
Lf =
3000
1200
X
0
PLAN
Y
HPP
H3 =
0
H2
H6
Hf
Df = D
1500
H1 =
500
ELEVATION
2.2 FOUNDATION WEIGHT
AREA OF FOOTING
Af = L f x Bf
SECTION MODULUS
Zx = (Bf x Lf ) / 6
SECTION MODULUS
Zz = (Lf x Bf ) / 6
WT. OF PEDESTAL
W p = Lp x Bp x H2 x
WT. OF FOOTING
W f = Af x H1 x
3.00
2.00
87.52
kN
) /6
( 3.00 x
2.00
) /6
gc
0.60
0.23 x
0.00 x
25.0
6.00 x
0.50
24.0
( 6.00 -
0.60
0.23 ) x
UPLIFT
Vf = Af x (Df - Dw) x 9.8
6.00 x
( 1.50 -
0.00
72.00 +
105.52 - 90.00
FOUNDATION WT.
3.00
W so = (Af - Lp x Bp) x H6 x gs
(Df < Dw)
( 2.00 x
WT. OF SOIL ON FTG.
(Df > Dw)
kN
gc
=
=
1.00
) x
10
m2
6.00
3.00
2.00
0.00
72.00
105.52
90.00
x 18.0 =
m3
m3
kN
kN
kN
= 0.00
W fd = W p + W f + W so - Vf
0.00 +
L&T CHIYODA LIMITED
CIVIL & STRUCTURAL DEPT
PROJECT
AEP
DOC. NO.:- L&T-DESIGN02754
L&T Job No.
DL 4103
REV. NO.
3.0 LOAD CASE AND LOADING CONDITION
X
Mx
Mz
Z
PLAN
Fy
G.L.
G.L.
Fz
Y
F
ELEVATION
3.1 UNFACTORED LOADS
LOAD
CASE
LC 100
LC 109
LC 110
LC 122
LC 109
(AT BOTTOM OF FOOTING)
LOADING
CONDITION
Fx
(kN)
Fy
(kN)
Fz
(kN)
Mx
(kN-m)
My
(kN-m)
Mz
(kN-m)
D+L
5.00
6.00
8.00
5.00
6.00
171.00
253.00
89.00
71.00
253.00
12.00
15.00
8.00
7.00
8.00
73.00
60.00
89.00
81.00
90.00
0.00
0.00
0.00
0.00
0.00
3.00
3.00
4.00
2.00
3.00
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX
WHERE :
Fx
Fy
Fz
Mx
=
=
=
=
UNFACTORED HORIZONTAL SHEAR ALONG X AXIS
UNFACTORED VERTICAL LOAD
UNFACTORED HORIZONTAL SHEAR ALONG Z AXIS
UNFACTORED MOMENT ABOUT X-AXIS
My
UNFACTORED MOMENT ABOUT Y-AXIS
Mz
UNFACTORED MOMENT ABOUT Z-AXIS
(AT TOP OF PEDESTAL)
(AT TOP OF PEDESTAL)
L&T CHIYODA LIMITED
CIVIL & STRUCTURAL DEPT
PROJECT
AEP
L&T Job No.
DL 4103
DOC. NO.:- L&T-DESIGN02754
REV. NO.
4.0 CHECK FOR STABILITY
4.1 CHECK FOR SLIDING
FACTOR OF SAFETY AGAINST SLIDING =
(Fy+Wfd)*m1
FE
WHERE :
Fy
W fd
FE
m1
= UNFACTORED VERTICAL LOAD AT TOP OF PEDESTAL
= FOUNDATION WEIGHT
= UNFACTORED HORIZ. SHEAR AT TOP OF PEDESTAL (RESULTANT) =
= FRICTION COEFFICIENT (CONCRETE TO SOIL)
LOAD
LOADING
CASE
CONDITION
Fx
Fy + Wfd
Fz
FE
(kN)
(kN)
(kN)
(kN)
m1
Fx2 + Fz2
Sliding
Resisting
Force
Force
Factor of Safety
against Sliding
Act.
LC 100
LC 109
LC 110
LC 122
LC 109
D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX
5.00
6.00
8.00
5.00
6.00
258.52
340.52
176.52
158.52
340.52
12.00
15.00
8.00
7.00
8.00
13.00
16.16
11.31
8.60
10.00
0.414
0.414
0.414
0.414
0.414
13.00
16.16
11.31
8.60
10.00
107.03
140.97
73.08
65.63
140.97
8.23
8.72
6.46
7.63
14.10
Perm
>
>
>
>
>
1.50
1.50
1.50
1.50
1.50
Judge
O.K
O.K
O.K
O.K
O.K
L&T CHIYODA LIMITED
CIVIL & STRUCTURAL DEPT
AEP
L&T Job No.
DL 4103
DOC. NO.:- L&T-DESIGN02754
REV. NO.
4.2 CHECK FOR OVERTURNING
3a
X
885
230
1200
600
2000
PROJECT
1200
3000
3a
PLAN
Fy
Mx
HP
Fz
1
500 1000
A
UPLIFT
4.2.1 Moment at A about X axis :
ELEVATION
Restoring Moment (Due to permanent loads including effect of Buoyancy)
Portion - 1
1.20
1.00
2.00
18.0
2.40
103.68
KN-m
Portion - 2
1.20
1.00
2.00
18.0
0.60
25.92
KN-m
Portion - 3
0.60
1.00
0.23
24.0
1.50
4.97
KN-m
Portion- 3a
0.60
1.00
x (2 x 0.89) x
18.0
1.50
28.67
KN-m
Portion - 4
3.00
0.50
2.00
24.0
1.50
108.00
KN-m
Force - 5
3.00
1.50
2.00
-10.0
1.50
-135.00
KN-m
TOTAL
LOAD
CASE
LOADING
CONDITION
Overturning Moment due to
Fz
LC 100
LC 109
LC 110
LC 122
LC 109
D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX
= 136.24 KN-m
0.00
0.00
0.00
0.00
0.00
Mx
73.00
60.00
89.00
81.00
90.00
Total
73.00
60.00
89.00
81.00
90.00
Restoring Moment due to
Fy
256.50
379.50
133.50
106.50
379.50
Permam
nent
Loads
136.24
136.24
136.24
136.24
136.24
Total
392.74
515.74
269.74
242.74
515.74
L&T CHIYODA LIMITED
CIVIL & STRUCTURAL DEPT
PROJECT
AEP
L&T Job No.
DL 4103
DOC. NO.:- L&T-DESIGN02754
REV. NO.
4.2.2 Moment at A about Z axis :
Restoring Moment (Due to permanent loads including effect of Buoyancy)
Portion - 1
1.20
1.00
2.00
18.0
1.00
43.20
KN-m
Portion - 2
1.20
1.00
2.00
18.0
1.00
43.20
KN-m
Portion - 3
0.60
1.00
0.23
24.0
1.00
3.31
KN-m
Portion - 3a
1.77
1.00
0.23
18.0
1.00
7.33
KN-m
Portion - 4
3.00
2.00
0.50
24.0
1.00
72.00
KN-m
Force - 5
3.00
1.50
2.00
-10.0
1.00
-90.00
KN-m
TOTAL
79.04 KN-m
LOAD
CASE
LOADING
CONDITION
Overturning Moment due to
Fx
LC 100
LC 109
LC 110
LC 122
LC 109
D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX
0.00
0.00
0.00
0.00
0.00
Mz
3.00
3.00
4.00
2.00
3.00
Total
3.00
3.00
4.00
2.00
3.00
Restoring Moment due to
Fy
171.00
253.00
89.00
71.00
253.00
Permamnent
Loads
79.04
79.04
79.04
79.04
79.04
Total
250.04
332.04
168.04
150.04
332.04
L&T CHIYODA LIMITED
CIVIL & STRUCTURAL DEPT
PROJECT
AEP
DOC. NO.:- L&T-DESIGN02754
L&T Job No.
DL 4103
REV. NO.
PLAN
Y
HP
Fy
Mx
Fz
ELEVATION
4.2.3 ECCENTRICITY OF LOADING IN Z DIRECTION ( Overturning about X axis)
LOAD
CASE
LOADING
CONDITION
Net Moment at A about X-Axis
(KN-m)
P=Fy+Wfd
(kN)
C.G. of
Loading
Eccen.
ez = C.G.Lf/2
(m)
(m)
Factor of Saftey Against Overturning FSx
Actual
Permi
Judge
=0.5/ (ez/Lf)
LC 100
LC 109
LC 110
LC 122
LC 109
D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX
392.74
515.74
269.74
242.74
515.74
73.00
60.00
89.00
81.00
90.00
=
=
=
=
=
319.74
455.74
180.74
161.74
425.74
258.52
340.52
176.52
158.52
340.52
1.237
1.338
1.024
1.020
1.250
0.263
0.162
0.476
0.480
0.250
5.703
9.259
3.151
3.127
6.007
>
>
>
>
>
1.5
1.5
1.5
1.5
1.5
O.K.
O.K.
O.K.
O.K.
O.K.
L&T CHIYODA LIMITED
CIVIL & STRUCTURAL DEPT
PROJECT
AEP
DOC. NO.:- L&T-DESIGN02754
L&T Job No.
DL 4103
REV. NO.
4.2.4 ECCENTRICITY OF LOADING IN X DIRECTION (Overturning about Z axis)
LOAD
CASE
LOADING
CONDITION
Net Moment at A about Z axis
(KN-m)
P=Fy+Wfd
(kN)
C.G. of
Loading
Eccen.
ex = C.G.Bf/2
(kN)
(m)
Factor of Saftey Against Overturning FSz
Actual
Permi
Judge
=0.5/ (ex/Bf)
LC 100
LC 109
LC 110
LC 122
LC 109
D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX
250.04
332.04
168.04
150.04
332.04
3.00
3.00
4.00
2.00
3.00
=
=
=
=
=
247.04
329.04
164.04
148.04
329.04
258.52
340.52
176.52
158.52
340.52
0.956
0.966
0.929
0.934
0.966
0.044
0.034
0.071
0.066
0.034
22.727
29.412
14.085
15.131
29.671
>
>
>
>
>
1.5
1.5
1.5
1.5
1.5
O.K.
O.K.
O.K.
O.K.
O.K.
L&T CHIYODA LIMITED
CIVIL & STRUCTURAL DEPT
PROJECT
AEP
DOC. NO.:- L&T-DESIGN02754
L&T Job No.
DL 4103
REV. NO.
4.2.5 CHECK FOR COMBINED ECCENTRICITY (Overturning about X and Z axis)
LOAD
FSx
LOADING
Fsz
Combined Check (**)
Judge
Min. of FSz required for Fx
For FSx< 2
LC 100
LC 109
LC 110
LC 122
LC 109
D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX
5.703
9.259
3.151
3.127
6.007
For FSx > 2
22.727
29.412
14.085
15.131
29.671
1.644
1.586
1.783
1.785
1.636
O.K.
O.K.
O.K.
O.K.
O.K.
(** Note )
For Combined Check
[Refer Annexure - I]
For FSx <=2
Minimum of FSz required =
0.5 x FSx / (FSx - 1.5)
For FSx > 2
Minimum of FSz required =
1.5 x FSx / (FSx - 0.5)
5. CHECK FOR BEARING CAPACITY AND LIFT-UP
5.1 UNFACTORED LOADS & ECCENTRICITY (AT FOUNDATION BASE LEVEL)
LOAD
CASE
LC 100
LC 109
LC 110
LC 122
LC 109
LOADING
D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX
CONDITION
P=Fy+Wfd
ez
ex
Mx
=P.ez
Mz
=P.ex
(kN)
(m)
(m)
(kN-m)
(kN-m)
258.52
340.52
176.52
158.52
340.52
0.263
0.162
0.476
0.480
0.250
0.044
0.034
0.071
0.066
0.034
67.99
55.16
84.02
76.03
85.03
11.37
11.58
12.53
10.48
11.48
L&T CHIYODA LIMITED
CIVIL & STRUCTURAL DEPT
PROJECT
AEP
L&T Job No.
DL 4103
DOC. NO.:- L&T-DESIGN02754
REV. NO.
5.2 INTENSITY OF SOIL BEARING PRESSURE
LOAD
LOADING
CONDITION
CASE
ez/Lf
ex/Bf
Af
CASE
(I or II)
x in Lf
(kN/m2)
LC 100
LC 109
LC 110
LC 122
LC 109
D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX
43.09
56.75
29.42
26.42
56.75
LIFTUP
(*Note)
y in Bf
For CASE II only
0.088
0.054
0.159
0.160
0.083
0.022
0.017
0.036
0.033
0.017
I
I
II
II
I
(* Note)
1.70
1.45
2.15
2.15
1.65
0.22
0.25
0.080
0.090
Lift up is less than25 %
pmax.= K
x (P/Af) Permissible
(kN/m2)
73.25
82.29
63.25
56.80
93.64
(kN/m2)
<
<
<
<
<
277
340
340
340
340
L&T CHIYODA LIMITED
CIVIL & STRUCTURAL DEPT
PROJECT
AEP
DOC. NO.:- L&T-DESIGN02754
L&T Job No.
DL 4103
REV. NO.
6.0 MEMBER DESIGN
6.1 SECTION FORCE PER UNIT WIDTH
(FOR FACTORED LOADS)
qs : UNIT WEIGHT OF FOOTING AND SOIL
= H1*gc+H6*gs-Vf/Af =
15.0 (kN/m2)
11
2
d
Z 1.5d
X
3
3
Z
SECTION 1-1
Critical Section for Flexure
d : Effective Depth of Footing
In Z direction =500 -50 -6 mm =
In X direction =500 -50 -12 - 5 mm =
MuLi = gf (pmax-qs) xA1^2/2
VuLi = gf ( pmax - qs) A2
MuLi' = gf (pmin-qs)*A1^2/2
WHERE
SECTION 2-2
Section for Shear at d
444 mm
433 mm
X
3
SECTION 3-3
Critical Section for Maximum Shear
SECTION 4-4
Section for Shear at 1.5d
MuBi = gf (pmax-qs) x B1^2/2
VuBi = gf ( p max - qs) B2
MuBi' = gf (pmin-qs)x B1^2/2
Mui : POSITIVE BENDING MOMENT UNDER THE GIVEN CONDITIONS ALONG L or B
(FOR BOTTOM REINFORCEMENT)
Vui : SHEAR FORCE UNDER THE GIVEN CONDITIONS
Mui' : NEGATIVE BENDING MOMENT UNDER THE GIVEN CONDITIONS ALONG L or B
(FOR TOP REINFORCEMENT)
A1,B1 : MAX. PROJECTION OF FOOTING IN Z DIRECTION/ X DIRECTION FROM
COLUMN FACE(VIZ. Sect. 1-1) = SPAN FOR FLEXURE DESIGN :
A1 =
1.200 m
B1 =
0.885 m
A2,B2 : MAX. PROJECTION OF FOOTING IN Z DIRECTION/ X DIRECTION FROM
SECTION CRITICAL FOR SHEAR AT d :
A2 = ( 1.2 -0.444 ) =
0.756 m
B2 = ( 0.885 -0.433 ) =
0.441 m
A3,B3 : MAX. PROJECTION OF FOOTING IN Z DIRECTION/ X DIRECTION FROM
SECTION CRITICAL FOR MAXIMUM SHEAR :
A3 =A1=
1.200 m
B3 = B1=
0.885 m
A4,B4 : MAX. PROJECTION OF FOOTING IN Z DIRECTION/ X DIRECTION FROM
SECTION CRITICAL FOR SHEAR AT 1.5d :
A4 = ( 1.2 -0.666 ) =
0.534 m
B4 = ( 0.885 -0.6495 ) = 0.236 m
gf
: REFER NEXT PAGE
L&T CHIYODA LIMITED
CIVIL & STRUCTURAL DEPT
PROJECT
AEP
DOC. NO.:- L&T-DESIGN02754
L&T Job No. DL 4103
For Case I
p min = 2 x (P/Af) - p max
For Case II
p min = 2 x (P/Af)
0 - p max
REV. NO. 0
Pmax = P/Af + M/Z + M/Z
Pmin = P/Af - M/Z - M/Z
= 2 x (P/Af') - Pmax
LOAD
CASE
LOADING
CONDITION
pmax.
gf
pmin.
2
73.25
82.29
63.25
56.80
93.64
12.93
31.21
0.00
0.00
19.86
1.5
1.5
1.5
1.5
1.5
pmax.
pmin.
gf
(kN/m ) (kN/m )
LC 100
LC 109
LC 110
LC 122
LC 109
LOAD
CASE
D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX
LOADING
CONDITION
73.25
82.29
63.25
56.80
93.64
12.93
31.21
0.00
0.00
19.86
(kN/m ) (kN/m )
LC 100
LC 109
LC 110
LC 122
LC 109
D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX
1.5
1.5
1.5
1.5
1.5
MuLi
(1-1)
VuLi
(2-2)
MuLi'
(1-1)
MuBi
(1-1)
VuBi
(2-2)
MuBi'
(1-1)
62.91
72.67
52.11
45.15
84.93
66.05
76.31
54.72
47.40
89.18
-2.24
17.51
-16.20
-16.20
5.25
34.21
39.53
28.34
24.56
46.20
38.53
44.51
31.92
27.65
52.02
-1.22
9.52
-8.81
-8.81
2.86
VuLi
(3-3)
VuBi
(3-3)
VuLi
(4-4)
VuBi
(4-4)
104.84
121.12
86.85
75.24
141.56
77.32
89.33
64.05
55.49
104.40
46.66
53.90
38.65
33.48
62.99
20.58
23.77
17.04
14.77
27.78
L&T CHIYODA LIMITED
CIVIL & STRUCTURAL DEPT
PROJECT
AEP
L&T Job No.
DL 4103
DOC. NO.:- L&T-DESIGN02754
REV. NO.
6.2 GOVERNING CONDTITION
MuL =
MuB =
MuL' =
MuB' =
VuL =
VuB =
VuL =
VuB =
VuL =
VuB =
84.93
46.20
-16.20
-8.81
89.18
52.02
141.56
104.40
62.99
27.78
(kNm)
(kNm)
(kNm)
(kNm)
(kN)
(kN)
(kN)
(kN)
(kN)
(kN)
(At section2-2)
(At section2-2)
(At section3-3)
(At section3-3)
(At section4-4)
(At section4-4)
6.3 PROVISION OF REINFORCEMENT FOR FLEXURE
(PER 1.0 M WIDTH )
FY =
415
(N / mm2)
Fck =
20
(N / mm2)
(As per Clause 34.2.3.2 a) of IS:456-2000)
REQUIRED RE-BAR FOR TENSILE SIDE
pt required =
50 x
1-
1.
4.6 Mu
fck bd2
Fy / fck
ptmin =
0.06 %
Astreq = MAX(pt*d*1.0,ptmin*H1*1.0)
MAXIMUM ALLOWABLE SPACING FOR REINFORCEMENT IN FOOTING
Mu
(kN-m)
d
(mm)
Mu/bd^2
N/mm2
pt
%
300 mm
ptmin
%
Astreq
(mm2)
Astprov
(mm2)
DIA (*)
Spacing
(mm) Reqd / (Prov)
(mm)
BOTTOM IN Z DIRECTION
84.93
444
0.43
0.12
0.06
546
754
12
BOTTOM IN X DIRECTION
46.20
433
0.25
0.07
0.06
299
524
10
TOP IN Z DIRECTION
16.20
444
0.08
0.02
0.06
266
524
10
TOP IN X DIRECTION
8.81
433
0.05
0.01
0.06
260
524
10
200
150
250
150
275
150
300
150
(*) Minimum bar diameter shall be T-10
L&T CHIYODA LIMITED
CIVIL & STRUCTURAL DEPT
PROJECT
AEP
L&T Job No.
DL 4103
6.4 SHEAR CHECK
DOC. NO.:- L&T-DESIGN02754
REV. NO.
(As per Clause 34.2.4.1 a) and Clause 40.5 of IS:456-2000)
For Section 2-2
Vu
(kN)
Astprov
pt
av
Vc = (1.5d/av) x tc x b x d
(mm)
(mm2)
(mm)
(kN)
(*)
Judge
IN Z DIRECTION
89.18
444
754
0.17
444
202.27
O.K.
IN X DIRECTION
52.02
433
524
0.12
433
186.74
O.K.
* (tc As per Table 19 of IS:456-2000)
For Sectioin 3-3
Vu
(kN)
d
(mm)
Vcmax = tc max x b x d
(kN)
Judge
IN Z DIRECTION
141.56
444
622
O.K.
IN X DIRECTION
104.40
433
606
O.K.
tc max =
1.40
N/mm2
For Section 4-4
Vu
(kN)
Astprov
pt
av
Vc = (1.5d/av) x tc x b x d
(mm)
(mm2)
(mm)
(kN)
(*)
Judge
IN Z DIRECTION
62.99
444.00
754
0.17
666
134.85
O.K.
IN X DIRECTION
27.78
433.00
524
0.12
649.5
124.49
O.K.
* (tc As per Table 19 of IS:456-2000)
CRITICAL SUPPORT REACTION FROM STAAD OUT PUT FOR RECT. COLUMNS (F2)
(At the base of footing)
LOAD COMBINATION LOAD
(**)
D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX
Fx
Fy
Fz
Mx
My
Mz
FS
FS
CASE (kN) (kN) (kN) (kN-m)(kN-m) (kN-m) Sliding Overturning Load Factor
100
5 171
12
73
0
3
1.5
1.5
1.5
109
6 253
15
60
0
3
1.5
1.5
1.5
110
8
89
8
89
0
4
1.5
1.5
1.5
122
5
71
7
81
0
2
1.5
1.5
1.5
109
6 253
8
90
0
3
1.5
1.5
1.5
Long Term(L)/
Short Term (S)
Node
No.
L
S
S
S
S
3
3
3
3
4
Table for max. permissible Shear Stress in Concrete
15
2.5
20
2.8
25
3.1
30
3.5
35
3.7
40
4.0
1 STEEL COLUMN
2 RC COLUMN
2 RC COLUMN