0% found this document useful (0 votes)
460 views18 pages

Foundation Design for Heat Exchanger

This document provides the design of a foundation with an RCC column (F2) for a project (AEP). It includes specifications, codes, materials, geometry, loads, and stability checks. The foundation geometry includes dimensions for the footing and pedestal. Loads considered include dead loads, live loads, vertical and horizontal forces. Checks performed include sliding resistance, overturning about the X and Z axes. Factors of safety against sliding and overturning are calculated for different load cases and found to be greater than the minimum required of 1.5.

Uploaded by

hemantkle2u
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
460 views18 pages

Foundation Design for Heat Exchanger

This document provides the design of a foundation with an RCC column (F2) for a project (AEP). It includes specifications, codes, materials, geometry, loads, and stability checks. The foundation geometry includes dimensions for the footing and pedestal. Loads considered include dead loads, live loads, vertical and horizontal forces. Checks performed include sliding resistance, overturning about the X and Z axes. Factors of safety against sliding and overturning are calculated for different load cases and found to be greater than the minimum required of 1.5.

Uploaded by

hemantkle2u
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
  • Introduction and Overview: Displays initial diagrams related to engineering values, setting the context for foundation design.
  • Foundation Design: Lists general specifications, concrete requirements, and guidelines for designing foundations.
  • Stability and Safety Checks: Explains methods to evaluate stability, safety against sliding, and overturning conditions.
  • Eccentricity and Bearing Pressure: Discusses calculations for bearing pressure and checking eccentricity in multiple directions.
  • Reinforcement and Structural Integrity: Focuses on reinforcement design, structural integrity, and moment design considerations for foundations.
  • Support Reaction and Stress Guidelines: Outlines critical support reactions from engineering outputs and permissible shear stress in materials.

L&T CHIYODA LIMITED

CIVIL & STRUCTURAL DEPT


PROJECT

AEP

L&T Job No.

DL 4103

DOC. NO.:- L&T-DESIGN02754


REV. NO.

DESIGN OF FOUNDATION

( with RCC column

F2
)

1. GENERAL :
1.1 SPECIFICATION FOR DESIGN :
THE DESIGN IS IN ACCORDANCE WITH THE FOLLOWING :
SPECIFICATION USED :
DESIGN PHILOSOPHY FOR FOUNDATION FOR HORIZONTAL HEAT EXCHANGER C1R-00017-MSQ-CE-SP-0007
1.2 CODES USED :
IS:456-2000
SP: 16
1.3 MATERIAL USED :

CODE OF PRACTICE FOR PLAIN AND REINFORCED CONCRETE


DESIGN AIDS FOR REINFORCED CONCRETE TO IS:456

LEVELLING CONCRETE :

75
1:4:8

Thick
Nominal Mix

STRUCTURAL CONCRETE :
UNIT WEIGHT OF CONCRETE

gc

24

kN / m3

GRADE OF CONCRETE

fck

20

MPa

fy

415

MPa

UNIT WEIGHT

gs

18

NET SAFE BEARING CAPACITY (SHEAR CRITERION)

SBC

250.0

kN / m3

ALLOWABLE BEARING PRESSURE (SETTLEMENT CRITERION)

ABP

250.0

kN / m3

REINFORCING BAR :
STRENGTH
SOIL PARAMETERS :
kN / m

MISCELLANEOUS DATA :
COVER TO BE PROVIDED FOR MAIN BARS IN FOOTING

COV_F

50

mm

COVER TO BE PROVIDED FOR COLUMN

COV_P

40

mm

FRICTION COEFFICIENT (CONCRETE TO SOIL)

m1

: 0.414

DEPTH OF GROUND WATER TABLE (BELOW HPP)

Dw

: 0.00

L&T CHIYODA LIMITED


CIVIL & STRUCTURAL DEPT
PROJECT

AEP

DOC. NO.:- L&T-DESIGN02754

L&T Job No.

DL 4103

REV. NO.

2.1 GEOMETRY OF FOUNDATION


(UNIT : M)
Lf

3.00

H3

Bf

0.00

2.00

H6 = DF - H1

1.00

Lp

0.600

H2 = H3 + H6

1.00

Bp

0.230

DF

1.50

H1

0.50

HF = H1 + H2

1.50

230

Bp =

2000
B

Bf =

Z
Lecc. =

1200

Lp =

600

Lf =

3000

1200

X
0

PLAN
Y
HPP

H3 =

0
H2

H6

Hf
Df = D
1500

H1 =

500

ELEVATION
2.2 FOUNDATION WEIGHT
AREA OF FOOTING

Af = L f x Bf

SECTION MODULUS

Zx = (Bf x Lf ) / 6

SECTION MODULUS

Zz = (Lf x Bf ) / 6

WT. OF PEDESTAL

W p = Lp x Bp x H2 x

WT. OF FOOTING

W f = Af x H1 x

3.00

2.00

87.52

kN

) /6

( 3.00 x

2.00

) /6

gc

0.60

0.23 x

0.00 x

25.0

6.00 x

0.50

24.0

( 6.00 -

0.60

0.23 ) x

UPLIFT

Vf = Af x (Df - Dw) x 9.8

6.00 x

( 1.50 -

0.00

72.00 +

105.52 - 90.00

FOUNDATION WT.

3.00

W so = (Af - Lp x Bp) x H6 x gs

(Df < Dw)

( 2.00 x

WT. OF SOIL ON FTG.


(Df > Dw)

kN

gc

=
=

1.00

) x

10

m2

6.00
3.00
2.00
0.00
72.00
105.52
90.00

x 18.0 =

m3
m3
kN
kN
kN

= 0.00
W fd = W p + W f + W so - Vf

0.00 +

L&T CHIYODA LIMITED


CIVIL & STRUCTURAL DEPT
PROJECT

AEP

DOC. NO.:- L&T-DESIGN02754

L&T Job No.

DL 4103

REV. NO.

3.0 LOAD CASE AND LOADING CONDITION


X
Mx
Mz
Z

PLAN
Fy

G.L.

G.L.

Fz

Y
F

ELEVATION
3.1 UNFACTORED LOADS
LOAD
CASE
LC 100
LC 109
LC 110
LC 122
LC 109

(AT BOTTOM OF FOOTING)

LOADING
CONDITION

Fx
(kN)

Fy
(kN)

Fz
(kN)

Mx
(kN-m)

My
(kN-m)

Mz
(kN-m)

D+L

5.00
6.00
8.00
5.00
6.00

171.00
253.00
89.00
71.00
253.00

12.00
15.00
8.00
7.00
8.00

73.00
60.00
89.00
81.00
90.00

0.00
0.00
0.00
0.00
0.00

3.00
3.00
4.00
2.00
3.00

D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX

WHERE :
Fx
Fy
Fz
Mx

=
=
=
=

UNFACTORED HORIZONTAL SHEAR ALONG X AXIS


UNFACTORED VERTICAL LOAD
UNFACTORED HORIZONTAL SHEAR ALONG Z AXIS
UNFACTORED MOMENT ABOUT X-AXIS

My

UNFACTORED MOMENT ABOUT Y-AXIS

Mz

UNFACTORED MOMENT ABOUT Z-AXIS

(AT TOP OF PEDESTAL)


(AT TOP OF PEDESTAL)

L&T CHIYODA LIMITED


CIVIL & STRUCTURAL DEPT
PROJECT

AEP

L&T Job No.

DL 4103

DOC. NO.:- L&T-DESIGN02754


REV. NO.

4.0 CHECK FOR STABILITY


4.1 CHECK FOR SLIDING
FACTOR OF SAFETY AGAINST SLIDING =

(Fy+Wfd)*m1
FE

WHERE :

Fy
W fd
FE
m1

= UNFACTORED VERTICAL LOAD AT TOP OF PEDESTAL


= FOUNDATION WEIGHT
= UNFACTORED HORIZ. SHEAR AT TOP OF PEDESTAL (RESULTANT) =
= FRICTION COEFFICIENT (CONCRETE TO SOIL)

LOAD

LOADING

CASE

CONDITION

Fx

Fy + Wfd

Fz

FE

(kN)

(kN)

(kN)

(kN)

m1

Fx2 + Fz2

Sliding

Resisting

Force

Force

Factor of Safety
against Sliding
Act.

LC 100
LC 109
LC 110
LC 122
LC 109

D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX

5.00
6.00
8.00
5.00
6.00

258.52
340.52
176.52
158.52
340.52

12.00
15.00
8.00
7.00
8.00

13.00
16.16
11.31
8.60
10.00

0.414
0.414
0.414
0.414
0.414

13.00
16.16
11.31
8.60
10.00

107.03
140.97
73.08
65.63
140.97

8.23
8.72
6.46
7.63
14.10

Perm

>
>
>
>
>

1.50
1.50
1.50
1.50
1.50

Judge

O.K
O.K
O.K
O.K
O.K

L&T CHIYODA LIMITED


CIVIL & STRUCTURAL DEPT
AEP

L&T Job No.

DL 4103

DOC. NO.:- L&T-DESIGN02754


REV. NO.

4.2 CHECK FOR OVERTURNING

3a
X

885

230

1200

600

2000

PROJECT

1200

3000

3a

PLAN
Fy
Mx

HP

Fz

1
500 1000

A
UPLIFT

4.2.1 Moment at A about X axis :

ELEVATION

Restoring Moment (Due to permanent loads including effect of Buoyancy)


Portion - 1

1.20

1.00

2.00

18.0

2.40

103.68

KN-m

Portion - 2

1.20

1.00

2.00

18.0

0.60

25.92

KN-m

Portion - 3

0.60

1.00

0.23

24.0

1.50

4.97

KN-m

Portion- 3a

0.60

1.00

x (2 x 0.89) x

18.0

1.50

28.67

KN-m

Portion - 4

3.00

0.50

2.00

24.0

1.50

108.00

KN-m

Force - 5

3.00

1.50

2.00

-10.0

1.50

-135.00

KN-m

TOTAL
LOAD
CASE

LOADING
CONDITION

Overturning Moment due to

Fz
LC 100
LC 109
LC 110
LC 122
LC 109

D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX

= 136.24 KN-m

0.00
0.00
0.00
0.00
0.00

Mx
73.00
60.00
89.00
81.00
90.00

Total
73.00
60.00
89.00
81.00
90.00

Restoring Moment due to

Fy
256.50
379.50
133.50
106.50
379.50

Permam
nent
Loads
136.24
136.24
136.24
136.24
136.24

Total
392.74
515.74
269.74
242.74
515.74

L&T CHIYODA LIMITED


CIVIL & STRUCTURAL DEPT
PROJECT

AEP

L&T Job No.

DL 4103

DOC. NO.:- L&T-DESIGN02754


REV. NO.

4.2.2 Moment at A about Z axis :


Restoring Moment (Due to permanent loads including effect of Buoyancy)
Portion - 1

1.20

1.00

2.00

18.0

1.00

43.20

KN-m

Portion - 2

1.20

1.00

2.00

18.0

1.00

43.20

KN-m

Portion - 3

0.60

1.00

0.23

24.0

1.00

3.31

KN-m

Portion - 3a

1.77

1.00

0.23

18.0

1.00

7.33

KN-m

Portion - 4

3.00

2.00

0.50

24.0

1.00

72.00

KN-m

Force - 5

3.00

1.50

2.00

-10.0

1.00

-90.00

KN-m

TOTAL

79.04 KN-m

LOAD
CASE

LOADING
CONDITION

Overturning Moment due to

Fx
LC 100
LC 109
LC 110
LC 122
LC 109

D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX

0.00
0.00
0.00
0.00
0.00

Mz
3.00
3.00
4.00
2.00
3.00

Total
3.00
3.00
4.00
2.00
3.00

Restoring Moment due to

Fy
171.00
253.00
89.00
71.00
253.00

Permamnent
Loads
79.04
79.04
79.04
79.04
79.04

Total
250.04
332.04
168.04
150.04
332.04

L&T CHIYODA LIMITED


CIVIL & STRUCTURAL DEPT
PROJECT

AEP

DOC. NO.:- L&T-DESIGN02754

L&T Job No.

DL 4103

REV. NO.

PLAN
Y
HP

Fy
Mx

Fz

ELEVATION
4.2.3 ECCENTRICITY OF LOADING IN Z DIRECTION ( Overturning about X axis)
LOAD
CASE

LOADING

CONDITION

Net Moment at A about X-Axis

(KN-m)

P=Fy+Wfd

(kN)

C.G. of
Loading

Eccen.
ez = C.G.Lf/2

(m)

(m)

Factor of Saftey Against Overturning FSx

Actual

Permi

Judge

=0.5/ (ez/Lf)
LC 100
LC 109
LC 110
LC 122
LC 109

D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX

392.74
515.74
269.74
242.74
515.74

73.00
60.00
89.00
81.00
90.00

=
=
=
=
=

319.74
455.74
180.74
161.74
425.74

258.52
340.52
176.52
158.52
340.52

1.237
1.338
1.024
1.020
1.250

0.263
0.162
0.476
0.480
0.250

5.703
9.259
3.151
3.127
6.007

>
>
>
>
>

1.5
1.5
1.5
1.5
1.5

O.K.
O.K.
O.K.
O.K.
O.K.

L&T CHIYODA LIMITED


CIVIL & STRUCTURAL DEPT
PROJECT

AEP

DOC. NO.:- L&T-DESIGN02754

L&T Job No.

DL 4103

REV. NO.

4.2.4 ECCENTRICITY OF LOADING IN X DIRECTION (Overturning about Z axis)


LOAD
CASE

LOADING

CONDITION

Net Moment at A about Z axis

(KN-m)

P=Fy+Wfd

(kN)

C.G. of
Loading

Eccen.
ex = C.G.Bf/2

(kN)

(m)

Factor of Saftey Against Overturning FSz

Actual

Permi

Judge

=0.5/ (ex/Bf)
LC 100
LC 109
LC 110
LC 122
LC 109

D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX

250.04
332.04
168.04
150.04
332.04

3.00
3.00
4.00
2.00
3.00

=
=
=
=
=

247.04
329.04
164.04
148.04
329.04

258.52
340.52
176.52
158.52
340.52

0.956
0.966
0.929
0.934
0.966

0.044
0.034
0.071
0.066
0.034

22.727
29.412
14.085
15.131
29.671

>
>
>
>
>

1.5
1.5
1.5
1.5
1.5

O.K.
O.K.
O.K.
O.K.
O.K.

L&T CHIYODA LIMITED


CIVIL & STRUCTURAL DEPT
PROJECT

AEP

DOC. NO.:- L&T-DESIGN02754

L&T Job No.

DL 4103

REV. NO.

4.2.5 CHECK FOR COMBINED ECCENTRICITY (Overturning about X and Z axis)


LOAD

FSx

LOADING

Fsz

Combined Check (**)

Judge

Min. of FSz required for Fx


For FSx< 2

LC 100
LC 109
LC 110
LC 122
LC 109

D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX

5.703
9.259
3.151
3.127
6.007

For FSx > 2

22.727
29.412
14.085
15.131
29.671

1.644
1.586
1.783
1.785
1.636

O.K.
O.K.
O.K.
O.K.
O.K.

(** Note )
For Combined Check

[Refer Annexure - I]

For FSx <=2


Minimum of FSz required =

0.5 x FSx / (FSx - 1.5)

For FSx > 2


Minimum of FSz required =

1.5 x FSx / (FSx - 0.5)

5. CHECK FOR BEARING CAPACITY AND LIFT-UP


5.1 UNFACTORED LOADS & ECCENTRICITY (AT FOUNDATION BASE LEVEL)
LOAD
CASE

LC 100
LC 109
LC 110
LC 122
LC 109

LOADING

D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX

CONDITION

P=Fy+Wfd

ez

ex

Mx
=P.ez

Mz

=P.ex

(kN)

(m)

(m)

(kN-m)

(kN-m)

258.52
340.52
176.52
158.52
340.52

0.263
0.162
0.476
0.480
0.250

0.044
0.034
0.071
0.066
0.034

67.99
55.16
84.02
76.03
85.03

11.37
11.58
12.53
10.48
11.48

L&T CHIYODA LIMITED


CIVIL & STRUCTURAL DEPT
PROJECT

AEP

L&T Job No.

DL 4103

DOC. NO.:- L&T-DESIGN02754


REV. NO.

5.2 INTENSITY OF SOIL BEARING PRESSURE

LOAD

LOADING
CONDITION

CASE

ez/Lf

ex/Bf

Af

CASE

(I or II)

x in Lf

(kN/m2)
LC 100
LC 109
LC 110
LC 122
LC 109

D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX

43.09
56.75
29.42
26.42
56.75

LIFTUP

(*Note)

y in Bf

For CASE II only


0.088
0.054
0.159
0.160
0.083

0.022
0.017
0.036
0.033
0.017

I
I
II
II
I

(* Note)

1.70
1.45
2.15
2.15
1.65

0.22
0.25

0.080
0.090

Lift up is less than25 %

pmax.= K
x (P/Af) Permissible
(kN/m2)
73.25
82.29
63.25
56.80
93.64

(kN/m2)
<
<
<
<
<

277
340
340
340
340

L&T CHIYODA LIMITED


CIVIL & STRUCTURAL DEPT
PROJECT

AEP

DOC. NO.:- L&T-DESIGN02754

L&T Job No.

DL 4103

REV. NO.

6.0 MEMBER DESIGN


6.1 SECTION FORCE PER UNIT WIDTH
(FOR FACTORED LOADS)
qs : UNIT WEIGHT OF FOOTING AND SOIL
= H1*gc+H6*gs-Vf/Af =
15.0 (kN/m2)

11

2
d

Z 1.5d

X
3

3
Z

SECTION 1-1
Critical Section for Flexure

d : Effective Depth of Footing


In Z direction =500 -50 -6 mm =
In X direction =500 -50 -12 - 5 mm =
MuLi = gf (pmax-qs) xA1^2/2
VuLi = gf ( pmax - qs) A2
MuLi' = gf (pmin-qs)*A1^2/2
WHERE

SECTION 2-2
Section for Shear at d

444 mm
433 mm

X
3

SECTION 3-3
Critical Section for Maximum Shear

SECTION 4-4
Section for Shear at 1.5d

MuBi = gf (pmax-qs) x B1^2/2


VuBi = gf ( p max - qs) B2
MuBi' = gf (pmin-qs)x B1^2/2

Mui : POSITIVE BENDING MOMENT UNDER THE GIVEN CONDITIONS ALONG L or B


(FOR BOTTOM REINFORCEMENT)
Vui : SHEAR FORCE UNDER THE GIVEN CONDITIONS
Mui' : NEGATIVE BENDING MOMENT UNDER THE GIVEN CONDITIONS ALONG L or B
(FOR TOP REINFORCEMENT)
A1,B1 : MAX. PROJECTION OF FOOTING IN Z DIRECTION/ X DIRECTION FROM
COLUMN FACE(VIZ. Sect. 1-1) = SPAN FOR FLEXURE DESIGN :
A1 =
1.200 m
B1 =
0.885 m
A2,B2 : MAX. PROJECTION OF FOOTING IN Z DIRECTION/ X DIRECTION FROM
SECTION CRITICAL FOR SHEAR AT d :
A2 = ( 1.2 -0.444 ) =
0.756 m
B2 = ( 0.885 -0.433 ) =
0.441 m
A3,B3 : MAX. PROJECTION OF FOOTING IN Z DIRECTION/ X DIRECTION FROM
SECTION CRITICAL FOR MAXIMUM SHEAR :
A3 =A1=
1.200 m
B3 = B1=
0.885 m
A4,B4 : MAX. PROJECTION OF FOOTING IN Z DIRECTION/ X DIRECTION FROM
SECTION CRITICAL FOR SHEAR AT 1.5d :
A4 = ( 1.2 -0.666 ) =
0.534 m
B4 = ( 0.885 -0.6495 ) = 0.236 m
gf
: REFER NEXT PAGE

L&T CHIYODA LIMITED


CIVIL & STRUCTURAL DEPT
PROJECT

AEP

DOC. NO.:- L&T-DESIGN02754

L&T Job No. DL 4103


For Case I
p min = 2 x (P/Af) - p max
For Case II
p min = 2 x (P/Af)
0 - p max

REV. NO. 0
Pmax = P/Af + M/Z + M/Z
Pmin = P/Af - M/Z - M/Z

= 2 x (P/Af') - Pmax

LOAD
CASE

LOADING
CONDITION

pmax.

gf

pmin.
2

73.25
82.29
63.25
56.80
93.64

12.93
31.21
0.00
0.00
19.86

1.5
1.5
1.5
1.5
1.5

pmax.

pmin.

gf

(kN/m ) (kN/m )
LC 100
LC 109
LC 110
LC 122
LC 109

LOAD
CASE

D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX

LOADING
CONDITION

73.25
82.29
63.25
56.80
93.64

12.93
31.21
0.00
0.00
19.86

(kN/m ) (kN/m )
LC 100
LC 109
LC 110
LC 122
LC 109

D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX

1.5
1.5
1.5
1.5
1.5

MuLi
(1-1)

VuLi
(2-2)

MuLi'
(1-1)

MuBi
(1-1)

VuBi
(2-2)

MuBi'
(1-1)

62.91
72.67
52.11
45.15
84.93

66.05
76.31
54.72
47.40
89.18

-2.24
17.51
-16.20
-16.20
5.25

34.21
39.53
28.34
24.56
46.20

38.53
44.51
31.92
27.65
52.02

-1.22
9.52
-8.81
-8.81
2.86

VuLi
(3-3)

VuBi
(3-3)

VuLi
(4-4)

VuBi
(4-4)

104.84
121.12
86.85
75.24
141.56

77.32
89.33
64.05
55.49
104.40

46.66
53.90
38.65
33.48
62.99

20.58
23.77
17.04
14.77
27.78

L&T CHIYODA LIMITED


CIVIL & STRUCTURAL DEPT
PROJECT

AEP

L&T Job No.

DL 4103

DOC. NO.:- L&T-DESIGN02754


REV. NO.

6.2 GOVERNING CONDTITION


MuL =
MuB =
MuL' =
MuB' =
VuL =
VuB =
VuL =
VuB =
VuL =
VuB =

84.93
46.20
-16.20
-8.81
89.18
52.02
141.56
104.40
62.99
27.78

(kNm)
(kNm)
(kNm)
(kNm)
(kN)
(kN)
(kN)
(kN)
(kN)
(kN)

(At section2-2)
(At section2-2)
(At section3-3)
(At section3-3)
(At section4-4)
(At section4-4)

6.3 PROVISION OF REINFORCEMENT FOR FLEXURE


(PER 1.0 M WIDTH )
FY =
415
(N / mm2)
Fck =
20
(N / mm2)

(As per Clause 34.2.3.2 a) of IS:456-2000)

REQUIRED RE-BAR FOR TENSILE SIDE

pt required =

50 x

1-

1.

4.6 Mu

fck bd2
Fy / fck

ptmin =
0.06 %
Astreq = MAX(pt*d*1.0,ptmin*H1*1.0)
MAXIMUM ALLOWABLE SPACING FOR REINFORCEMENT IN FOOTING
Mu
(kN-m)

d
(mm)

Mu/bd^2
N/mm2

pt
%

300 mm
ptmin
%

Astreq
(mm2)

Astprov
(mm2)

DIA (*)
Spacing
(mm) Reqd / (Prov)
(mm)

BOTTOM IN Z DIRECTION

84.93

444

0.43

0.12

0.06

546

754

12

BOTTOM IN X DIRECTION

46.20

433

0.25

0.07

0.06

299

524

10

TOP IN Z DIRECTION

16.20

444

0.08

0.02

0.06

266

524

10

TOP IN X DIRECTION

8.81

433

0.05

0.01

0.06

260

524

10

200
150
250
150
275
150
300
150

(*) Minimum bar diameter shall be T-10

L&T CHIYODA LIMITED


CIVIL & STRUCTURAL DEPT
PROJECT

AEP

L&T Job No.

DL 4103

6.4 SHEAR CHECK

DOC. NO.:- L&T-DESIGN02754


REV. NO.

(As per Clause 34.2.4.1 a) and Clause 40.5 of IS:456-2000)

For Section 2-2


Vu
(kN)

Astprov

pt

av

Vc = (1.5d/av) x tc x b x d

(mm)

(mm2)

(mm)

(kN)
(*)

Judge

IN Z DIRECTION

89.18

444

754

0.17

444

202.27

O.K.

IN X DIRECTION

52.02

433

524

0.12

433

186.74

O.K.

* (tc As per Table 19 of IS:456-2000)


For Sectioin 3-3
Vu
(kN)

d
(mm)

Vcmax = tc max x b x d
(kN)

Judge

IN Z DIRECTION

141.56

444

622

O.K.

IN X DIRECTION

104.40

433

606

O.K.

tc max =

1.40

N/mm2

For Section 4-4


Vu
(kN)

Astprov

pt

av

Vc = (1.5d/av) x tc x b x d

(mm)

(mm2)

(mm)

(kN)
(*)

Judge

IN Z DIRECTION

62.99

444.00

754

0.17

666

134.85

O.K.

IN X DIRECTION

27.78

433.00

524

0.12

649.5

124.49

O.K.

* (tc As per Table 19 of IS:456-2000)

CRITICAL SUPPORT REACTION FROM STAAD OUT PUT FOR RECT. COLUMNS (F2)
(At the base of footing)

LOAD COMBINATION LOAD


(**)
D+L
D+L+VX
D+L-VX
0.9(D+L)-VX
D+L-VX

Fx

Fy

Fz

Mx

My

Mz

FS

FS

CASE (kN) (kN) (kN) (kN-m)(kN-m) (kN-m) Sliding Overturning Load Factor
100
5 171
12
73
0
3
1.5
1.5
1.5
109
6 253
15
60
0
3
1.5
1.5
1.5
110
8
89
8
89
0
4
1.5
1.5
1.5
122
5
71
7
81
0
2
1.5
1.5
1.5
109
6 253
8
90
0
3
1.5
1.5
1.5

Long Term(L)/
Short Term (S)

Node
No.

L
S
S
S
S

3
3
3
3
4

Table for max. permissible Shear Stress in Concrete


15
2.5
20
2.8
25
3.1
30
3.5
35
3.7
40
4.0

1 STEEL COLUMN
2 RC COLUMN
2 RC COLUMN