Professional Documents
Culture Documents
SEMESTER 3
1.MEASUREMENT OF SINGLE PHASE POWER AND POWER FACTOR
USING THREE AMMETERS.
AIM
To measure the power and power factor of the given R-L circuit using three Ammeters.
(Without using Wattmeter)
APPARATUS REQUIRED:Sl No
Apparatus
1
2
3
4
5
Ammeter
Voltmeter
Rheostat
Autotransformer
Transformer
Specification
Quantity
THEORY
Power factor is the cosine of the angle between phase voltage and current. The maximum
value of power factor is unity, i.e. for pure resistive load and minimum value is zero.ie for pure
inductive load (lagging) or pure capacitive load (leading).
For an R-L circuit, the current lags voltage by certain angle, which is called the power
factor angle .
The vector diagram is shown in figure. Voltage V is taken as the reference, I2is in phase
with V (since current through pure resistance- in phase with V,), I3 lags behind V by angle ,
(since R-L circuit), I1 is the vector sum of I2 and I3.
1 2 = (2 + 3 )2 + ( 3 )2
= 2 2 + 3 2 2 + 22 3 + 3 2 2
= 2 2 + 3 2 + 22 3
= ( 1 2 2 2 3 2 )/22 3
= 2
, = 3
= 2 3 ( 1 2 2 2 3 2 )/22 3
=
( 1 2 2 2 3 2 )
2
PROCEDURE:
1. Connect the circuit as in the connection diagram.
2. Check the connections and correct the mistake if any.
3. Switch on the supply
4. First note the reading in the Voltmeter, then gradually increase the input voltage and take
the corresponding readings in all the three meters. Tabulate.
5. Calculate the results accordingly.
RESULT
Power =
Power factor =
OBSERVATION
Sl No
V/m
I1
I3
Power=
I2
ReadingR/2(I12-I22-I32)
Amps Amps Amps
Volts
CIRCUIT DIAGRAM
PF=
(I12-I22-I32)/2 I2I3
Apparatus
1
2
3
4
5
Ammeter
Voltmeter
Rheostat
Autotransformer
Transformer
Specification
Quantity
THEORY
Power factor is the cosine of the angle between phase voltage and current. The maximum value
of power factor is unity, i.e. for pure resistive load and minimum value is zero.ie for pure
inductive load (lagging) or pure capacitive load (leading).
For an R-L circuit, the current lags voltage by certain angle, which is called the power factor
angle .
The vector diagram is shown in figure. Voltage V is taken as the reference, I2is in phase with V (
since current through pure resistance- in phase with V,), I3 lags behind V by angle , (since R-L
circuit), I1 is the vector sum of I2 and I3.
V12= (V2+V3Cos)2+ ( V3Sin)2
= V22+V32Cos2+2V2V3Cos+V32Sin2
= V22+V32+2 V2V3 Cos
... PF=( V12-V22-V32)/2 V2V3
We have V2= IR
So, Power Consumed by the load= V3ICos
= ( V12-V22-V32)/2 R
Power =( V12-V22-V32)/2 R
PROCEDURE:
1. Connect the circuit as in the connection diagram.
2. Check the connections and correct the mistake if any.
3. Switch on the supply
4. Adjust the autotransformer and take all meter readings.
5. Calculate the results accordingly.
RESULT
Power =
Power factor =
OBSERVATION
Sl No
V/m
V1
V3
Power=
V2
Reading(V12-V22-V32)/2R
Amps
Amps
Amps
Volts
CIRCUIT DIAGRAM
PF=
(V12-V22V32)/2V2V3
Apparatus
1
2
3
4
5
Autotransformer
Voltmeter
Ammeter
Wattmeter
Lamp load
Specification
Quantity
THEORY
Electric power is the rate at which electric energy is transferred by an electric circuit.
The SI unit of power is the watt. there are three types of ac power
Apparent power
It is the product of RMS value of applied voltage and current. S = VI KVA
Active power
It the power actually consumed in a ac circuit. P = V Icos KW
Reactive power
This power is due to the reactance of the circuit. Q = VIsin KVAR
By wattmeter method the active power of the circuit is measured.
PROCEDURE
1. Connect the circuit as in the connection diagram.
2. Check the connections and correct the mistake if any.
( / / /)
.
RESULT
Power=
Power factor=
OBSERVATION
Sl.
No
CIRCUIT DIAGRAM
= (/)
AIM
To measure the input power and determine power factor of a balanced three phase load using two
W/ms.
APPARATUS REQUIRED:Sl No
Apparatus
1
2
3
4
5
Specification
Quantity
THEORY:
.
. .
. / .
. / .
= = =
3 .
+ = ( ) + ( + )
= [ ( ) + ( + )]
= .
= . /.
= . = .
= ( ) ( + )
= [ ( ) ( + )]
= . .
= . /. .
= .
= [ (
.
3
+
1
3
tan
)]
PROCEDURE
1. Connections are made as shown in the circuit diagram
2. Keep the autotransformer at minimum position
3. Adjust the autotransformer till the voltmeter reads 400v
4. Take the corresponding v/m, a/m and w/m readings.
5. Tabulate the readings and calculate the power and power factor
RESULT:
Power=
Power factor=
OBSERVATION
Sl no
CIRCUIT DIAGRAM
W1
W2
W1+W2 W2-W1
5. VERIFICATION OF KCL&KVL
AIM
To verify KCL&KVL in dc circuits
APPARATUS REQUIRED
Sl No
Apparatus
1
2
3
4
Autotransformer
Voltmeter
Ammeter
Rheostat
Specification
Quantity
THEORY
()
.
=
()
,
, + =
PROCEDURE
1. Connect the circuit as in the connection diagram.
2. Check the connections and correct the mistake if any.
3. Switch on the supply
4. Vary the autotransformer
5. Take all meter readings& tabulate
6. Verify kcl & kvl
RESULT
Verified Kirchhoffs current law &voltage law
OBSERVATION
Sl no
V1
V2
CIRCUIT DIAGRAM
V3
V2+V3
I1
I2
I3
I2+I3
Apparatus
1
2
3
4
Voltmeter
Ammeter
Wattmeter
Lamp load
Specification
Quantity
THEORY
Calibration of wattmeter means standardizing of meter and finding out the error. A
wattmeter is a device that is constructed out of pressure coil and current coil. The pressure coil is
connected in parallel with the circuit, and current coil in series with the circuit. The current coil
has low resistance connected in series with the ammeter.
There are Induction type (used in AC measurements only) and Dynamometer type
wattmeter (used in both AC & DC measurements).
= .
/
=
.
= / /
,
, .
% =
100
PROCEDURE
1. Connect the circuit as shown in figure
2. Checked the connections and given the supply.
OBSERVATION
Sl
No
CIRCUIT DIAGRAM
/ / .
Sl No
Apparatus
1
2
3
4
5
Voltmeter
Ammeter
Wattmeter
Transformer
autotransformer
Specification
Quantity
THEORY
= / .
= / = /
= . . . . , = . . . , = /
= . . . / . . . = /
, / = /
, = , = / , = ( / )
=
PROCEDURE
1) Polarity test.
1. Connections are made as shown in figure (1)
2. Checked the connections and given a specified voltage to primary.
3. Noted the volt meter reading and verified the polarity of the transformer.ie If the
voltmeter reading in the inter connected voltmeter is greater than the input voltage, and
then the polarity is additive, So Opposite polarity on the other adjacent terminal on
secondary.
Transformation ratio=
OBSERVATION
Sl No
Prim. V/m
reading E1
CIRCUIT DIAGRAM
Sec. V/m
reading E2
Watt meter
reading W0
A/m
reading I0
Turns ratio
Transf.
ratio =K
Apparatus
1
2
3
4
5
Voltmeter
Ammeter
Wattmeter
Lamp load
Energy meter
Specification
Quantity
THEORY
The process of comparing of an instrument with standard or absolute instrument is called
calibration. The energy meter records the energy consumed in KWH. Let be the number
of revolutions of the disc. Is the revolution per KWH (meter constant).
Recorded energy=
The true energy=/
%error= ( )/ 100
PROCEDURE
1.
2.
3.
4.
Calibrated the given single phase energy meter by direct loading at UPF and plotted the error
curve
OBSERVATION
Sl no
CIRCUIT DIAGRAM
Actual
energy
%error
APPARATUS REQUIRED:Sl No
Apparatus
1
2
3
4
Voltmeter
Ammeter
Wattmeter
Lamp load
Specification
Quantity
THEORY
When current rating of the meter under test is high, a test with actual loading
arrangements involves considerable waste of power. Phantom loading consists of supplying
the pressure circuit with required normal voltage and the current circuit from a low voltage
supply. the total power required for testing the meter with phantom loading is comparatively
very small.
PROCEDURE
At UPF
1.
2.
3.
4.
5.
6.
At 0.5pf lag
1. Connect the pressure coil across N&Y and CC in R phase
OBSERVATION
PF
UPF
0.5
LAG
v/m
A/m
KWH
Actual
power
cos
/1000
Error
%error=
Apparatus
1
2
3
4
Voltmeter
Ammeter
Wattmeter
Inductive coil
Specification
Quantity
THEORY
Inductance is the property of a circuit or a component to oppose the change in current
through it. An induction coil has a small resistance and an inductive reactance.
XL =
But XL=2fL
I.e., L=
RESULT
Inductance=
Power factor=
OBSERVATION
Sl no
V/m
A/m
W/m
Z=V/I
R= 2
XL
L=
2
2
= XL 2
Pf=