Section 17

COMMUNICATION
AND SIGNAL
SYSTEMS
This section includes manhour time frames for the installation of wire, cable, and various communication and signaling devices.
The manhours listed are for labor only. No consideration
has been given to the value of materials.
Labor for checking out of project storage, handling, job
hauling, and installing have been given consideration in the
manhour tables for the operations as listed in accordance
with the notes appearing with the tables.
These manhour units are average of many projects and
should be evaluated and adjusted by the estimater for use
on an individual project as outlined in the Introduction of
this manual.

LOW VOLTAGE WIRE AND CABLE FOR


CONTROL CIRCUITS AND COMMUNICATION AND
ANNUNICIATOR SYSTEMS
MANHOURS PER LINEAR FOOT
,
o.
Size
and
,_
.
_ 5^6
Conductor

~
, A
Conductor
Description
_

Plastic Insulated
Twisted Copper
Conductor

KT u
Manhours Required for
Number
-77-.5
1
Underfloor
,
Ducts
and
Heights
to
n
4
Conductors C o n d u i t s - 1 Q , , 1 ^ , ^ ,

#22
Solid

2
3

0.009
0.015

0.010 0.011 0.011


0.016 0.017 0.017

#19
Solid

2
3
j

0.013
0.019

0.014 0.015 0.015


0.021 0.021 0.022

# l g

0 0 0 7

o o o g

QQQ8

QQ08

Solid

2
3

0.014
0.021

0.015
0.023

Plastic Insulated Telephone


Copper Weld Conductor

#19
Solid

2
3

0.012
0.017

0.013 0.013 0.014


0.018 . 0.019 0.020

,.
.
,
, ^ 1 ,
n
Rubber Insulated Telephone
Copper Weld Conductor

#19 Solid

i_t-

J -r 1

J W paif
or p

i_

0 Q 1 3

Q 0 1 4

Q 0 1 5

Q 0 1 5

# 1 7 Solid

Rubber Insulated Telephone

Bronze Conductor

0.016 0.016
0.024 0.024

T W pair

o r Parallel

0 Q 1 7

a 0 1 g

a Q l p

Qmo

Manhours include checking out of job storage, handling, job hauling, placing wire coils or spools on
reel stands or racks, attaching to fish tape or other pull-in means, pulling wire into conduit type
raceway, ducts and underfloor ducts or pull-out and laying into wireways or channels or pulling over
suspended ceilings or through bar joist or trusses, identifying or "polling out" the circuit conductors,
and splicing or tagging for connection to terminal blocks or equipment.
Manhours exclude extensive identification, "ringing out", connecting to terminal blocks or equipment,
and scaffolding. See respective tables for these time frames.

LOW VOLTAGE WIRE AND CABLE FOR CONTROL


CIRCUITS AND COMMUNICATION AND
ANNUNICIATOR SYSTEMS
Plastic Insulated, Jacket Copper Conductors
MANHOURS PER LINEAR FOOT
.
,
Size and
Type of
Conductor

..
.
Number
of
Conductors

Manhours Required for


1
~
Ducts and
Heights to
\
,
Conduits
1Q,

Under fl O or

25

2
3
4

0.011
0.013
0.014

0.012
0 014
0.015

0.012
0.015
0.016

0.013
0.015
0.016

2
3
4

0.012
0.013
0.014

0.013
0.014
0.015

0.013
0.015
0.016

0.014
0.015
0.016

#22
Stranded

2
3
4
5
10
12
15
25

0.013
0.013
0.015
0.016
0.022
0.023
0.027
0.031

0.014
0.014
0.016
0.017
0.024
0.025
0.029
0.033

0.015
0.015
0.017
0.018
0.025
0.026
0.030
0.035

0.015
0.015
0.017
0.019
0.026
0.027
0.031
0.036

2
3
4

0.014
0.015
0.018

0.015
0.016
I 0.019

0.016
0.017
I 0.020

0.016
0.017
| 0.021

*,
bolld

^J
0

:=>tranae(1

Manhours include checking out of job storage, handling, job hauling, placing wire coils or spools on
reel stands or racks, attaching to fish tape or other pull-in means, pulling wire into conduit type
raceway, ducts and underfloor ducts or pull-out and laying into wireways or channels or pulling over
suspended ceilings or through bar joist or trusses, identifying or "polling out" the circuit conductors,
and splicing or tagging for connection to terminal blocks or equipment.
Manhours exclude extensive identification, "ringing out", connecting to terminal blocks or equipment,
and scaffolding. See respective tables for these time frames.

LOW VOLTAGE WIRE AND CABLE FOR CONTROL


CIRCUITS AND COMMUNICATIONS AND
ANNUNICIATOR SYSTEMS
Plastic Insulated Jacket Copper Conductors
MANHOURS P E R LINEAR F O O T
Size and
Yf
^ j 4
Conductor

#18
Stranded

btranded

. .
btranded

Number
f
r- J *
Conductors

, ^
Manhours Required for
undernoor
Ducts and
Heights to
, .4
77:7 1 7^7 1
o
Conduits
10
15

TT

TT=-,
25

2
3
4
5
7
9
12
15

0.016
0.018
0.020
0.023
0.027
0.030
0.035
0.050

0.017
0.019
0.022
0.025
0.029
0.032
0.038
0.054

0.018
0.020
0.022
0.026
0.030
0.034
0.039
0.056

0.019
0.021
0.023
0.027
0.031
0.035
0.040
0.058

2
3
4
5
7
9
12
15
19

0.019
0.021
0.024
0.030
0.043
0.049
0.056
0.059
0.062

0.021
0.023
0.026
0.032
0.046
0.053
0.060
0.064
0.067

0.021
0.024
0.027
0.034
0.048
0.055
0.063
0.066
0.070

0.022
0.024
0.028
0.035
0.050
0.057
0.065
0.068
0.072

2
3
4

0.027
0.033
0.051

0.029
0.036
0.055

0.030
0.037
0.057

12

Q0 5 g

0.070

0 063

0.076

QQ 6 5

0.079

0.031
0.038
0.059
QQ 6 7

0.081

Manhours include checking out of job storage, handling, job hauling, placing wire coils or spools on
reel stands or racks, attaching to fish tape or other pull-in means, pulling wire into conduit type
raceway, ducts and underfloor ducts or pull-out and laying into wireways or channels or pulling over
suspended ceilings or through bar joist or trusses, identifying or "polling out" the circuit conductors,
and splicing or tagging for connection to terminal blocks or equipment.
Manhours exclude extensive identification, "ringing out", connecting to terminal blocks or equipment,
and scaffolding. See respective tables for these time frames.

LOW VOLTAGE WIRE AND CABLE FOR


SOUND AND SHIELDED INSTRUMENTATION
CIRCUITS
MANHOURS PER LINEAR FOOT
o.

Conductor
Description
[
. , . . ..
Plastic Insulated with
OL U M P
^S? 1 "
Shield-No Ground Wire
Ol

,
Size and
~>
~
y e
P
n
Conductor
#22 Solid
#20 Stranded
#18 Stranded
#16 Stranded

#22 Solid
~
A A
Stranded

Plastic Insulated and


Jacket-Braided Copper
Shield-No Ground Wire

c, HH
stranded

#18 Solid

Mu
Manhours 12i21
Required for
Number
i
T1 , ~
,
Underfloor
.
Ducts and
Heights to
n
Conductors ^ ^
- 1Q, , ^
I g , 2
2
2
2
2

0.011
0.014
0.01619
0.012

0.012
0.015
0.017
0.021
0.013

2
3

0.013
0.015

0.014 0.014 0.015


0.016 0.017 0.017

Q017

aQlg

2
3
4

0.022
0.023
0.025

0027

0029

0030

Q 02Q

Q Q31

Q033

7
8

0.031
0.033

0.033
0.036

0.035
0.037

0.036
0.038

0.025

0.027

0.028

0.029

0.024
0.025
0.027

0.012
0.016
0.018
0.021
0.013

Qmg

0.025
0.026
0.028

0.013
0.016
0.019
0.022
0.014

QQ2Q

0.026
0.027
0.029
'031
Q Q34

#18 Stranded
2
0.026
0.028 0.029 0.030
#16
2
0.035
0.038 0.039 0.040
I Stranded |
4
| 0.039 | 0.042 | 0.043 | 0.045
Manhours include checking out of job storage, handling, job hauling, placing wire coils or spools on
reel stands or racks, attaching to fish tape or other pull-in means, pulling wire into conduit type
raceway, ducts and underfloor ducts or pull-out and laying into wireways or channels or pulling over
suspended ceilings or through bar joist or trusses, identifying or "polling out" the circuit conductors,
and splicing or tagging for connection to terminal blocks or equipment.
Manhours exclude extensive identification, "ringing out", connecting to terminal blocks or equipment,
and scaffolding. See respective tables for these time frames.

LOW VOLTAGE WIRE AND CABLE FOR


SOUND AND SHIELDED INSTRUMENTATION
CIRCUITS
MANHOURS PER LINEAR FOOT
,
o.
Size and
_
.
~ ?
Conductor

.
Number
^ J
Conductors

#22 Solid
#22 Stranded

2
2

0.016
0.017

0.017 0.018 0.019


0.018 0.019 0.020

0.010

0.011 0.011 0.012

Conductor
Description
PIastic Insulation and
9
t*Twaur
FZShield-With Ground Wire
Rubber Insulated Rubber
Jacket-Braided Copper
Shield-No Ground Wire
Plastic Insulated-Plastic
Jacket-Braided Copper
Shield-No Ground Wire

Manhours Required
for
.5 1
^1-1-3
Underfloor
Ducts and
Heights to
p ^ Conduhs
1Q , , ^

KT

TT

-[ ^tranded
^9|

btranded

1
|

0.010
|

0.011 0.011 0.012


[
|

Manhours include checking out of job storage, handling, job hauling, placing wire coils or spools on
reel stands or racks, attaching to fish tape or other pull-in means, pulling wire into conduit type
raceway, ducts and underfloor ducts or pull-out and laying into wireways or channels or pulling over
suspended ceilings or through bar joist or trusses, identifying or "polling out" the circuit conductors,
and splicing or tagging for connection to terminal blocks or equipment.
Manhours exclude extensive identification, "ringing out", connecting to terminal blocks or equipment,
and scaffolding. See respective tables for these time frames.

LOW VOLTAGE WIRE AND CABLE FOR


SOUND AND SHIELDED INSTRUMENTATION
CIRCUITS
Plastic Insulated and JacketSpiral Wrap Shield
No Ground WireCopper Conductor
MANHOURS PER LINEAR FOOT
_.
,
Size and
Type of
Conductor

Kt i_
Number
of
Conductors

Underfloor
Ducts and
Conduits

#22
Solid

2
3

0.015
0.017

0.016
0.018

0.017
0.019

0.017
0.020

#22
Stranded

2
3
4
6

0.017
0.018
0.020
0.024

0.018
0.019
0.022
0.026

0.019
0.020
0.022
0.027

0.020
0.021
0.023
0.028

#20
Solid

2
3

0.017
0.018

0.018
0.019

0.019
0.020

0.020
0.021

#20
Stranded

2
3
4
6

0.018
0.019
0.022
0.026

0.019
0.021
0.024
0.028

0.020
0.021
0.025
0.029

0.021
0.022
0.026
0.030

#18
Stranded

2
3

0.019
0.020

0.021
0.022

0.021
0.022

0.022
0.023

#16
Stranded

2
3
4
6

0.023
0.024
0.027
0.028

0.025
0.026
0.029
0.030

0.026
0.027
0.030
I 0.031

0.027
0.028
0.031
0.032

Manhours Required for


I
Heights to
IQI Ty
1

25'

'

Manhours include checking out of job storage, handling, job hauling, placing wire coils or spools on
reel stands or racks, attaching to fish tape or other pull-in means, pulling wire into conduit type
raceway, ducts and underfloor ducts or pull-out and laying into wireways or channels or pulling over
suspended ceilings or through bar joist or trusses, identifying or "polling out" the circuit conductors,
and splicing or tagging for connection to terminal blocks or equipment.
Manhours exclude extensive identification, "ringing out", connecting to terminal blocks or equipment,
and scaffolding. See respective tables for these time frames.

LOW VOLTAGE WIRE AND CABLE FOR


SOUND AND SHIELDED INSTRUMENTATION
CIRCUITS
Plastic Insulation and JacketAluminum Foil
Shieldwith Ground WireCopper Conductor
MANHOURS PER LINEAR FOOT
o.

Size and
^ ~ y*?6
Conductor

Kr u

Number
~ , A
Conductors

rr-j=
Underfloor
Ducts and
~ , .
Conduits

Manhours Required for


1

77^
10

Heights to
1 737 1
15'

^
25

#22
Solid

2
3

0.016
0.018

0.017
0.019

0.018
0.020

0.019
0.021

#22
Stranded

2
3
4
6

0.018
0.019
0.021
0.026

0.019
0.021
0.023
0.028

0.020
0.021
0.024
0.029

0.021
0.022
0.024
0.030

#20
Stranded

2
3
4
6

0.019
0.021
0.022
0.027

0.021
0.023
0.024
0.029

0.021
0.024
0.025
0.030

0.022
0.024
0.026
0.031

#18
Stranded

2
3

0.023
0.024

0.025
0.026

0.026
0.027

0.027
0.028

#16
Stranded

2
3
4
6

0.024
0.026
0.029
0.036

0.026
0.028
0.031
0.039

0.027
0.029
0.033
0.040

0.028
0.030
0.034
0.042

?14 . .
2
0.029
0.031
0.033
0.034
Stranded
|
|
|
|
Manhours include checking out of job storage, handling, job hauling, placing wire coils or spools on
reel stands or racks, attaching to fish tape or other pull-in means, pulling wire into conduit type
raceway, ducts and underfloor ducts or pull-out and laying into wireways or channels or pulling over
suspended ceilings or through bar joist or trusses, identifying or "polling out" the circuit conductors,
and splicing or tagging for connection to terminal blocks or equipment.
Manhours exclude extensive identification, "ringing out", connecting to terminal blocks or equipment,
and scaffolding. See respective tables for these time frames.

LOW VOLTAGE CABLE


SHIELDED PAIR CABLES FOR SOUND AND
INSTRUMENTATION
MANHOURS PER LINEAR FOOT
,
Conductor
Description
I

Plastic Insulation and


Jacket-Individual pair
Foil Shield and Ground Wire

,
.
Manhours Required
for
o.
Size
and
Pair
1
-1^
TT .-z
Tf
f
Underfloor
- y|?
^ ,
Ducts and
Heights to
Conductor Conductors C o n d u i t s
^
I
1Q,

\ .
stranded

U2U

stranded
Plastic Insulation and
Jacket-Aluminum Foil
Shield Over Cabled pairs
with Single Ground Wire

3
6
9
11

0.023
0.031
0.039
0.049

15

Q051

19
27
2
3

0.058
0.065
0.023
0.028

0 030

0.025
0.033
0.042
0.053
Q055

0.063
0.070
0.025
0.030
Q Q32

0.026
0.035
0.043
0.055
QMJ

0.065
0.073
0.026
0.031
Q Q34

^ 0.027
0.036
0.045
0.057

Q QS9

0.067
0.075
0.027
0.032
QMS

#22
Solid

Manhours include checking out of job storage, handling, job hauling, placing wire coils or spools on
reel stands or racks, attaching to fish tape or other pull-in means, pulling wire into conduit type
raceway, ducts and underfloor ducts or pull-out and laying into wireways or channels or pulling over
suspended ceilings or through bar joist or trusses, identifying or "polling out" the circuit conductors,
and splicing or tagging for connection to terminal blocks or equipment.
Manhours exclude extensive identification, "ringing out", connecting to terminal blocks or equipment,
and scaffolding. See respective tables for these time frames.

LOW VOLTAGE CABLE


UNSHIELDED PAIR CABLES FOR INTERCOM
AND SOUND
MANHOURS PER LINEAR FOOT
^

A
Conductor
Description
v

c.

bize and

T>

rair

Manhours Required
for
3

:-

_
Underfloor
^ y^e
~ ,
Ducts and
Heights to
Conductor Conductors ~ , .
T7-,
^7
;r Fr Conduits
10
15
25
1
2
3
4
5
6

0.007
0.012
0.016
0.019
0.021
0.023

#22
Solid
Plastic Insulation
and Jacket

#22
Stranded

,
c
Stranded

8
9
10
11
12
13
15
19
23
27
32
51
101
6
9
15
27
6
9

0.008 I 0.008 I 0.008


0.013 0.013 0.014
0.017 0.018 0.019
0.021 0.021 0.022
0.023 0.024 0.024
0.025 0.026 0.027

0.024

0.026

0.025
0.026
0.029
0.030
0.031
0.035
0.039
0.048
0.050
0.051
0.058
0.064
0.093
0.029
0.034
0.030
0.056
0.031
0.052
0.058

0.027
0.028
0.031
0.032
0.033
0.038
0.042
0.052
0.054
0.055
0.063
0.069
0.100
0.031
0.037
0.042
0.060
0.033
0.056
I 0.063 |

0.027

0.028

0.028 0.029
0.029 0.030
0.033 0.034
0.034 0.035
0.035 0.036
0.039 0.040
0.043 0.045
0.054 0.056
0.056 0.058
0.057 0.059
0.065 0.067
0.072 0.074
0.104 0.108
0.033 0.034
0.038 0.039
0.043 0.045
0.063 0.065
0.035 0.036
0.058 0.060
0.065 | 0.067

Manhours include checking out of job storage, handling, job hauling, placing wire coils or spools on
reel stands or racks, attaching to fish tape or other pull-in means, pulling wire into conduit type
raceway, ducts and underfloor ducts or pull-out and laying into wireways or channels or pulling over
suspended ceilings or through bar joist or trusses, identifying or "polling out" the circuit conductors,
and splicing or tagging for connection to terminal blocks or equipment.
Manhours exclude extensive identification, "ringing out", connecting to terminal blocks or equipment,
and scaffolding. See respective tables for these time frames.

MISCELLANEOUS AUDIO CABLES


COAXIAL, CLOSED CIRCUIT AND TV ANTENNA
MANHOURS PER LINEAR FOOT
Conductor
Description
_
Plastic Jacket
Copper Shielded
RG/U Coaxial Cable

_.
,
%Ze*R*
^ j .
Conductor
-

cgffiSd
Closed Circuit TV CableCommunity Antenna

/2OSoHd
Copper Weld
#14 Solid
uopper
#22 Jacketed
Stranded

M L

Manhours Required for


Underfloor I
r* A .
Ducts and
Heights to
Conductors C o n d u i t s - lQ, , " ^ ,
Num ber
f

0.035

0.038

028

003

#20 Parallel
Stranded
Copper

0.040

031 032

0030

0 ( m

0041

Q044

0Q46

0.017

0.018

0.019

0.020

0.023

0.024

0.024

Cop

TV Antenna Lead-in

0.039

QM2

0Q47

Per

0.021

Manhours include checking out of job storage, handling, job hauling, distributing, attaching to fish
tape or other pull-in means where required, installing and tagging for connection.
Manhours exclude connecting to outlets or equipment, and scaffolding. See respective tables for these
time frames.

WIRE AND CABLE TERMINAL CONNECTIONS


MANHOURS PER HUNDRED
Wire
Gauge

Manhours Required
1
2

Spade Tongue
Spade Tongue
Ring Tongue
Ring Tongue
Flag Type
Flag Type

22-18
16-14
22-18
16-14
22-18
16-14

15.0
19.5
17.5
22.0
17.5
22.0

Solder Connection
Solder Connection
Terminal Screw Connection
Terminal Screw Connection
"Punch-On" Insulation Piercing Conn.

22-18
16-14
22-18
16-14
22-18

20.0
24.5
12.5
18.0
10.0

Code:
1 -Pressure Terminal Connections to terminal Strips or Blocks.
2Direct Conductor Connections to Terminal Strips or Blocks.
Manhours include checking out of job storage, handling, job hauling, distributing, and installing of
connectors as outlined.
Manhours exclude installation of wire or cable, equipment and scaffolding. See respective tables for
these time frames.

TELEPHONE AND BURGLAR AND CENTRALIZED


RADIO SYSTEMS
MANHOURS EACH
Item Type and Description

Manhours

Vestibule Telephones
Cordless Loud Speaking Telephone
Cordless Loud Speaking Telephone with Mail Box
Cord and Receiver Type Telephone
Cord and Receiver Type Telephone with Mail Box

4.50
7.20
3.90
6.60

Suite Telephones
Loud Speaking Flush Mounted Type
Loud Speaking Surface Mounted Type
Cord and Receiver Flush Mounted Type
Cord and Receiver Surface Mounted Type

2.70
1.70
2.30
1.30

Burglar Alarm Systems


Open or Closed Circuit Springs
Contactors
Electric Matting
Constant Ringing Drop
Relays

0.60
1.20
1.30
2.20
2.30

Centralized Radio Systems


Master Receiver and Control
Turntable Record Player
Preamplifier

5.10
2.70
3.90

Manhours include checking out of job storage, handling, job hauling, distributing, and installating of
items as outlined.
Manhours exclude installation of circuit conductors, conductor connections and scaffolding. See
respective tables for these time frames.

CLOCK AND PROGRAM SYSTEMS


MANHOURS EACH
Item Type and Description
Minute Impulse Type
Master Controller-Flush Mounted
Master Controller-Surface Mounted
Signal Control Board-Flush Mounted-20-Signal
Signal Control Board-Flush Mounted-30-Signal
Signal Control Board-Flush Mounted-40-Signal
Signal Control Board-Surface Mounted-20-Signal
Signal Control Board-Surface Mounted-30-Signal
Signal Control Board-Surface Mounted-40-Signal
Secondary Clocks-Flush
Secondary C locksSurface
Secondary Clocks-Double Face
Bell or Buzzer Contained in Clock
Skeleton DialSet and connect Mechanism and hands
Skeleton DialMount ring Type Hour Markings
Skeleton DialMount Set of Individual Hour Markings

Manhours
11.70
9.90
15.60
20.40
20.00
13.80
18.00
21.60
1.90
1.10
1.30
0.40
1.40
1.30
2.30

Dual Motor Type


Switch Reset Control Unit
2.40
Automatic -Reset Control Unit-Flush Mounted
6.60
Automatic Reset Control Unit-Surface Mounted
5.70
Single Circuit Program ControllerFlush Mounted
6.30
Single Circuit Program Controller-Surface Mounted
5.10
Multiple Circuit Program Controller-Flush Mount-2-Circuit
9.00
Multiple Circuit Program Controller-Flush Mount-4-Circuit
10.50
Multiple Circuit Program Controller-Flush Mount-6-Circuit
11.40
Multiple Circuit Program Controller-Surface Mount-2-Circuit
7.80
Multiple Circuit Program Controller-Surface Mount-4-Circuit
9.10
Multiple Circuit Program Controller-Surface Mount-6-Circuit
10.80
Dual Motor Clocks-Flush
2.70
Dual Motor C locks-Surface
1.70
Dual Motor Clocks-Double Face
1-90
Bell or Buzzer Contained in Clock
0.40
SKeleton Dial-Set and Connect Mechanism and Hands
1 -50
Skeleton Dial-Mount Ring Type Hour Markings
1 -30
Skeleton Dial-Mount Set of Individual Hour Markings
2.30
Manhours include checking out of job storage, handling, job hauling, distributing, and installating of
items as outlined.
Manhours exclude installation of circuit conductors, conductor connections and scaffolding. See
respective tables for these time frames.

FIRE ALARM AND HOSPITAL SIGNALING


SYSTEMS
MANHOURS EACH
Item Type and Description
Fire Alarm Systems
Alarm Stations-Manual
Alarm Stations-Automatic Thermostat
Alarm Stations-Special Outlet Box
Alarm Stations-Bell
Alarm Stations-Flush Horn
Alarm Stations-Megaphone Horn
Alarm Stations-Grille Horn
Alarm Stations-Small Motor Driven Siren
Alarm Stations-Chimes
Alarm Stations-Annunicators-Mounting
Alarm Stations-Annunciators-Per Terminal
Alarm Stations-Special Rough-In Can
Control panel
C ity Auxiliary Station
Hospital Signaling Systems
Elapsed Time Indicator-Flush
Elapsed Time Indicator-Surface
Elapsed Time Indicator-Control Station
In-Out Master Register-20-Name
In-Out Master Register-40-Name
In-Out Master Register-60-Name
In-Out Master Register-80*Name
In-Out Master Register-100-Name
In-Out Register Subannunciator-20-Name
In-Out Register Subannunciator-40-Name
In-Out Register Subannunciator-60-Name
In-Out Register Subannunciator-80-Name
In-Out Register Subannunciator-100-Name
In-Out Register Subannunciator with Recall-20-Name
In-Out Register Subannunciator with Recall-40-Name
In-Out Register Subannunciator with Recall-60-Name
In-Out Register Subannunciator with Recall-80-Name
In-Out Register Subannunciator with Recall-100-Name

Manhours
0.60
1.10
1.00
0.85
110
1 -30
1 -80
1.30
0.70
1.50
0.30
1.10
4.80
2.40
2.20
1.10
1.10
8.40
15.60
24.00
31.20
38.40
7.80
14.40
20.40
27.60
34.80
10.50
19.20
28.80
38.40
48.00

Manhours include checking out of job storage, handling, job hauling, distributing, and installating of
items as outlined.
Manhours exclude installation of circuit conductors, conductor connections and scaffolding. See
respective tables for these time frames.

NURSES CALL AND PAGING SYSTEMS


MANHOURS EACH
Item Type and Description
Nurses Call Systems
Master Duty Station-12 Units
Master Duty Station-24 Units
Master Duty Station-36 Units
Master Duty Station-48 Units
Annunciators12 Units
Annunciators-24 Units
Annunciators36 Units
Annunciators-48 Units
Audible-Visible Call Bed Station
MicrophoneSpeaker Only
Audible-Visible Call with Microphone Speaker
Emergency Station
Explosion-Proof Station
Remote Duty Station hand Set
Pilot Lamps
Dome Lamps
Barriers
Buzzers
Bells
Night Lights
Radio Receptacle
Television Receptacle
Underpillow Speaker
Special Rough-In Can
Paging Systems
Visual Selector 3-Digit Keyboard
Visual Control Relay Panel
Visual Annunciators-Flush Mounted
Visual AnnunciatorsSurface Mounted
Voice Selector Keyboard
Voice Microphone
Voice Amplifier and Power Unit
Voice Terminal Connector Panel
Voice Loud SpeakersFlush Mounted
Voice Loud Speakers-Surface Mounted

Manhours
6.60
12.00
18.00
24.00
6.30
12.00
18.00
24.00
1.00
0.80
1.30
0.70
1.80
1.20
0.60
0.70
0.40
0.70
0.70
1.20
0.90
1 00
0.70
1 00

9.60
6.00
2.40
0.90
7.20
0.60
4.50
6.00
2.10
LlO

Manhours include checking out of job storage, handling, job hauling, distributing, and installating of
items as outlined.
Manhours exclude installation of circuit conductors, conductor connections and scaffolding. See
respective tables for these time frames.

INTER COMMUNICATION SYSTEMS


MANHOURS EACH
Item Type and Description

Manhours

Telephone Systems
Central Switchboard-Set and Mount in Place
Central Switchboard-Connections per Pair of Terminals
Local Stations-Flush Mounted Talk Back Speaker
Local Stations-Surface Mounted Talk Back Speaker
Local Stations-Suspended Wall Handset
Local Stations-Suspended Desk Handset
Local Stations-Cradle Desk Set

8.40
0.30
2.70
1.80
1.20
1 20
1.10

Desk Type Intercom Systems


Master Station-Per Terminal
Substations

0.60
1 30

Public Address Systems


AmplifiersMounting
5.10
Amplifiers-Connecting Per Terminal
0.30
Microphone-Outlet
0.80
Microphone-Mounting and Connecting
0.60
SpeakersFlush WallMounting and Connecting
1.80
Speakers-Flush Ceiling-Mounting and Connecting
2.30
Speakers-Surface Wall-Mounting and Connecting
1.00
Trumpet Speakers-Indoor Wall-Mounting and Connecting
2.40
Trumpet SpeakersOutdoor WallMounting and Connecting
3.60
Trumpet SpeakersOutdoor PoleMounting and Connecting
4.80
Manhours include checking out of job storage, handling, job hauling, distributing, and installing items
as outlined.
Manhours exclude installation of circuit conductors, conductor connection except where indicated,
and scaffolding. See respective tables for these time frames.

MISCELLANEOUS SIGNAL SYSTEM DEVICES


MANHOURS EACH
Item Type and Description

Manhours

Door Chimes
Mechanical
Suspended Tubes
Wall Mounted

1.30
1 40
0.70

Directory Boards
DirectoryMedium Size

0.70

Door Openers
Mortise Type
Rim Type

2.30
120

Push Buttons and Contacts


Single Push Button
0.40
Push Button Panels with 1 -5 Buttons
3.30
Pushbutton Panels with 6-10 Buttons
4.50
Pushbutton Panels with 11-15 Buttons
5.70
Large Panels-Mounting Only
2.30
Push Buttons on Large panels-Per Button
0.30
Desk Block-6 Button
0-50
Floor Tread
I
-60
Manhours include checking out of job storage, handling, job hauling, distributing, and installating of
items as outlined.
Manhours exclude installation of circuit conductors, conductor connections and scaffolding. See
respective tables for these time frames.

POWER SUPPLY ITEMS


MANHOURS EACH
Item Type and Description

Manhours

Transformers
Door Bell Type
Signaling Type-50 VA
Signaling Type-100 VA
Signaling Type-250 VA
Signaling Type-500 VA
Signaling Type-750 VA
Signaling Type-1000 VA

0.70
1.20
1.40
1.80
2.30
3.30
4.50

Batteries
Dry Type
Storage Type

0.40
0.80

Battery Charges
Copper Oxide Rectifier Automatic type-12-Cell
Copper Oxide Rectifier Automatic type-24-Cell
Copper Oxide Rectifier Automatic Type-60-Cell
Automatic Unit with Generator and Control panel-5 HP
Automatic Unit with Generator and Control panel-7.5 HP
Automatic Unit with Generator and Control panel15 HP
Rectifier
SoleniumTelephone Type
Solenium-Small Capacity Type
Solenium-Singie Voltage Type
Solenium-Dual Voltage Type

4.80
6.00
7.50
14.70
16.80
18.90
2.30
2.30
4.50
5.70

Manhours include checking out of job storage, handling, job hauling, distributing, and installating of
items as outlined.
Manhours exclude installation of circuit conductors, conductor connections and scaffolding. See
respective tables for these time frames.