OPE - DRE - 001 - TPC - MYP Daily Report
OPE - DRE - 001 - TPC - MYP Daily Report
MIYAPUR PSS
Prepared by TPC:
Date: 24/07/2016
Power
Block
No.
Power
Block
No.
Part-A No.
Part-B No.
Part-B No.
Remarks
Company
PIC
Scheduled
Closure
Actual
Closure
Reason
(if any)
NIL
Part-A No.
Remarks
NIL
NIL
Location:
Description:
NIL
Root cause:
NIL
Resolution:
NIL
Miyapur Depot
Approved
Load
Maximum
Demand
Apparent
Power
Reactive
Power
Real Power
Power
Factor
2000 KVA
1168.7 KVA
16200 KVAH
(0) KVARH
16200 KWH
0.99
33kV Incomer-1
N/A
N/A
61393 KVAH
(0) KVARH
11160 KWH
0.182
33kV Incomer-2
N/A
N/A
12101 KVAH
(0) KVARH
4159 KWH
0.344
25kV Incomer-1
N/A
N/A
4510 KVAH
2370 KVARH
2899 KWH
0.643
25kV Incomer-2
N/A
N/A
0 KVARH
0 KWH
N/A
325170652
KVAH
4. Miscellaneous Remarks :
1. Since 11/04/2015 SS-125 is not operating through SCADA (AMS No: 16-41223)
2. Since 15/06/2015 SS-124 Isolator is showing unknown status in SCADA workstation (AMS No: 16-41224)
3. Since 15/06/2015 BS101 Interrupter when given close command goes to unknown state sometimes (AMS
No: 16-41225)
4. Since 7/10/2015 SS-121 Isolator is showing OPEN status in SCADA workstation even though CLOSED
in field (AMS No: 16-41227)
5. Since 30/11/2015 Minor oil Leakage from Traction Transformer -2 at secondary bushings inspection
chamber. (AMS No: 16-41228)
6. Since 16/2/2016 Battery charger displaying false alarm every time when any of the 25KV GIS breakers are
operated. (AMS No: 16-41230)
7. HVAC Unit-1 is not working at MYP-RSS Building (AMS No.16-41231)
8. SCADA communication is intermittently failing in RSS & TSS RTU (AMS 16-31777)
9. 33KV I/C-1 & I/C-2 Circuit Breaker Face plate showing Ready to close indication in SCADA workstation
even though closed in field (AMS 16-32145)
10. MYP-Depot ASS,HT Board-2 Trafo WTI fault operated showing TRUE status in SCADA workstation (AMS
16-32149)
11. MYP-Depot ASS, HT Board-1 Bus Voltage showing ZERO (0) in PINK colour value even though BUS
charged in SCADA workstation (AMS 16-32150)
12. MYP-Depot ASS Breakers (52-13,52-15,52-16) Face plate showing TRUE Status for both Service & Test
position at the same time in SCADA workstation (AMS 16-32151)
13. In detail view of 33KV RSS C.B (M B 52 010) is not showing MWH & MVAH readings in SCADA
workstation (AMS 16-32152)
14. Since 26/04/2016 SS-113 is not operating through SCADA but when operated locally feedback is true
(AMS 16-32156)
15. Since 01/05/2016 Isolators SS-111, SS-114 & SS-115 are showing Unknown status in SCADA workstation
(AMS 16-32551).
16. MYP-TT2 abnormal sound observed at LT side (AMS 16-72566).
17. KPHB Circuit Breaker (52-33) not operating thru SCADA (AMS 16- 81626).
18. SR NAGAR Circuit Breaker (52-79) Showing Local Mode in SCADA, even it is in remote mode @ field
(AMS 16-81635)
19. BS-103 is showing unknown status in SCADA workstation when given OPEN/CLOSE command through
SCADA (AMS No. 16-82215)
20. TSTRANSCO M.D Reset was done @ 11:00 Hrs on 21/07/2016 & New MD recorded as 1168.7 KVA @ 12:30
hrs. On 22/07/2016.
325170652