Professional Documents
Culture Documents
J Kearney
Transformers
DT021/4 BEng.
Power System Analysis
TRANSFORMERS
TRANSFORMERS .............................................................................................................. 2
Transformers .................................................................................................................... 2
Impedance Transformation .......................................................................................... 3
Losses in the core. ........................................................................................................ 4
Single - Phase Autotransformers ..................................................................................... 6
Three-phase Transformers ............................................................................................. 10
Three Phase transformer connections ........................................................................ 13
Harmonics in Three-Phase Transformers .................................................................. 16
Star without neutral ................................................................................................... 20
Tertiary winding......................................................................................................... 23
REGULATION OF A TRANSFORMER ................................................................. 25
Parallel Operation of Transformers ............................................................................... 26
Parallel Operation Of Single-phase Transformers ..................................................... 27
Tertiary winding............................................................................................................. 30
Transformers - Recap
Single phase transformer.
m
l1
l2
i2
i1
V1
V2
Primary winding
N1 turns
Secondary winding
N2 turns
Fig. 1
The dot convention determines the polarity of the voltages and currents in the core
without having to examine the windings. The significance of the dots is that a current
flowing into the dotted end of a winding produces a positive magnetomotive force, F,
while a current flowing out will produce a negative magnetomotive force. If one current
flows into a dotted end of a winding and one flows out of a dotted end, then the
magnetomotive forces will subtract from each other.
From a modelling point of view, a physical power transformer is reasonably close to an
ideal transformer
V1
=
d1/dt
=
N1 d/dt
Since the same flux passes through the N2 turns of the secondary winding, the
secondary voltage is
V2
=
d2/dt
=
N2 d/dt
and the voltage ratio:
V2/V1 =
N2/N1
=
n
where n is the ratio of secondary turns to primary turns. Frequently, it is also convenient
to work with the reciprocal of n. This is called the transformation turns ratio:
a
N1/N2 =
1/n
Since the core is assumed to have infinite permeability, the reluctance is zero. i.e the net
mmf required to establish a flux in the ideal core is zero. Thus:
so
N1i1
i2/i1
=
=
N1i1 - N2i2
N2i2
N1/N2
1/n
Transformation relationship.
V1
V2
N1
N2
or power V1 i1
I2
I1
V2 i2
Impedance Transformation
V2
V1
Z2
V1
I1
or
N2
N1
I2Z2
N
Z2 1
N2
I1 Z2
N1
N2
a2 Z2
Z2`
Z2` is the impedance seen form the primary of the transformer and is equal to the
impedance of the secondary multiplied by the turns ration squared.
Assumptions required for an ideal Transformer.
The above assumptions are for an ideal transformer, and are not normal in a practical
transformer, however the Ideal Transformer is often used because of its simplicity.
i1
i2= a i1
V2 = V1/a
V1
(wb)
In discussions of an ideal transformer above, it was assumed that the permeability of the
core material was infinite and as a result zero current required to magnetise the core since
the reluctance was zero. The second assumption regarding the ideal transformer was that
there were no losses in the core. In practical transformers the above assumptions are not
valid
When a transformer is operating with an open circuit secondary, a small current with a
very low power factor will be measured at the primary, so some current is required to
magnetise the core. This comprises the current required to magnetise the core and the inphase component required to supply the power loss in the core. The power losses result
form eddy currents and hysteresis.
I
Fig.
Eddy current can be reduced by a considerable degree by constructing the core from thin
laminations. The laminations are insulated and the path for the eddy currents is thus
confined within each lamination. Figure .. above shows the effect of laminations on the
flow of eddy currents.
The eddy current and hysteresis losses may be modelled using resistances in parallel with
the magnetising inductance where Re is the eddy current loss and Rh is the hysteresis loss.
Both eddy current and hysteresis losses may be combined to give a core (iron) loss Rc.
io
Rc
Xm
V1
V2
Vin
Fig .
The magnetising inductance Xm, accounts for the fact that some current, Io is required to
energise the core. This current, Io lags the applied voltage by 90o and hence is in phase
with the core flux. The magnetising branch is in parallel with the core loss resistance, and
depends on the applied voltage.
Leakage reactance and winding resistances.
The power losses associated with the winding resistances, I12R1 for the primary and I22R2
for the secondary where R1 and R2 are the primary and secondary resistances respectively.
The total I2R loss, transformer copper loss is
Pcu
I12R1 + I22R2
jX1
R1
i`r
jX2`
R 2`
io
im
jXm
ic
Vin
Rc
Vout
I1
I2
+
+
Series Winding
N1=Ns
N1=Ns
I2
I1
+
Common
Winding
N2=Nc
V2
ZL
ZL
N2=Nc
V1
Step-Down autotransformer
Step-up autotransformer
Advantages:
o A tap between primary and secondary sides which may be adjustable to provide stepup/down capability
o Able to transfer larger S apparent power than the two winding transformer
o Smaller and lighter than an equivalent two-winding transformer
Disadvantage:
o Lacks electrical isolation
A Step Down Autotransformer:
V1/V2 =
And
= N2 / (N1+N2)
A Step Up Autotransformer:
V1/V2 =
N1/(N1+N2)
I1/I2
(N1+N2)/N2
N1=Ns
I1
V2
N2=Nc
V1
-
Step-up autotransformer
ZL
V1/V2 =
N1 /(N1+N2)
And
I1/I2
= (N1+N2) / N2
Example
An autotransformer with a 40% tap is supplied by a 400-V, 50-Hz source and is used for
step-down operation. A 5-kVA load operating at unity power factor is connected to the
secondary terminals. Find: (a) the secondary voltage, (b) the secondary current, (c) the
primary current.
(a)
V1/V2 =
(N1+N2) /N2 = 1/0.4
V2 = 0.4 V1 = 0.4 . 400 = 160V
(b)
(c)
A variac is an autotransformer with a variable tapping as shown in the figure. In this way
the secondary voltage can be varied. Variacs usually consist of a toroidal core and the
output is obtained from a sliding contact attached to a rotating shaft.
Large transformers are often equipped with a tapping in the low voltage winding to enable
the turns ratio to be changed. If the tap changer has switches capable of diverting the
current in the coils, the tap change operation can be carried out under load the On-Load
Tapchanger or OLTC.
7 + j70 ohms
220 kV
Infinite bus
T:1 0.9:1pu
1.4 Transformer Construction & Rating
Transformers are limited by
(a) core saturation,
(b) winding, insulation and oil temperature rise,
(c) vibration and noise.
If the applied voltage rises to high, the magnetising current will increase considerably
causing waveform problems. Loss of life of insulation is generally held to be dependant
on the integral of the hot spot temperature over life, i.e. there is a finite amount of life in
the tank and the hotter the transformer is run the quicker the tank is emptied (just like
fuel consumption in a car). In addition there are absolute values that must not be
exceeded.
Due to the large mass of a transformer, there is an appreciable time lag of hot spot
temperature on applied load so an overload of 20 ~ 30% for a few hours is normally OK
as long as the load then falls back below nominal 100% for a few hours. Transformers are
thus best sited out of the sun and in a place where a good air flow can be obtained.
The leakage reactance of a transformer is determined by the physical spacing of the
windings from each other and from the core. As voltage levels increase the need for
higher insulation levels and hence clearances also increase. Thus the higher the voltage
the higher the per unit impedance of the transformer. Note that in calculating per unit
impedances a Base MVA value has to be assigned. This will normally be the name plate
rating.
However this rating is set by the type of cooling system being used (oil natural
circulation, external radiators with fans to the extreme of force circulation, directed oil
flow with high efficiency fans cooled radiators). These systems are described by a number
of acronyms
ONAN = oil natural (circulation), air natural (circulation past a radiator fin)
OFDAF = oil forced directed (flow), air forced (ie fans on radiators).
There are also dry type and water cooled versions of the above. The greater the effort used
to cool the transformer the shorter its thermal time constant will be and hence the
OFDAF transformer will be less capable of accepting cyclic loads.
The core can be constructed
N
3-limb core Fig.
Y
B
10
Fig.
Y
Shell type
B
Fig. 5
N
Limb type
Transformer Construction
The dried and treated transformer is placed in a steel tank.
The tank is filled, under vacuum, with heated transformer oil.
The end of the windings are connected to bushings.
The oil is circulated by pumps and forced through the radiators.
Transformer Construction
The transformer is equipped with cooling radiators which are cooled by forced
ventilation.
Cooling fans are installed under the radiators.
Large bushings connect the windings to the electrical system.
The oil is circulated by pumps and forced through the radiators.
The oil temperature, pressure are monitored to predict transformer performance.
Dry type transformers are used at medium and low voltage.
The assembled transformer is moulded in epoxy resin which surrounds both the
windings and iron core.
The winding is vacuumed and dried before the moulding.
11
4,500V
(0.44+j1.34)
16,000V
V2
15,000kVA
Ifl = 93.75A
Imag =17.8A
Ip = 346.4A
Iron Loss =12kW
72 : 256 turns
Fig
The same general format for a transformer but wound for three phases connected as a starstar produces a comparable arrangement as shown in Fig..
The mag current and iron losses would not necessarily change in a proportion of 3 or 3,
since the iron configuration in unlikely to be exactly equivalent to three single-phase
transformers operating a star-star system. However, a per-phase value of Io of 17.8A and
a total iron loss of 3 . 12 kW = 36 kW would not be too far from actual values.
12
(0.03+j0.092)
/phase
(0.44+j1.34)
phase
Primary
Secondary
y
4,500kVA
Vph = 4,500V
VLL = 7,800V
Iph =346.48A
Ip = 346.4A on full
load
72 : 256
turns/phase
Vph = 16,000V
VLL = 27,700V
Ifl =93.75A
Fig
Changing the transformer connections to a different form, star-delta, such as in Fig
below..
(0.03+j0.092)
/phase
(0.44+j1.34)
phase
Primary
Secondary
y
4,500kVA
72 : 256
turns/phase
Fig.
Three single-phase transformers connected in four possible ways:
Connection
YY
Y
Primary
VL
Vph
7800 4500
7800 4500
4500 4500
4500 4500
IL
346
346
600
600
Iph
346
346
346
346
VL
27700
16000
16000
27000
Secondary
Vph
IL
16000
93.8
16000
162
16000
162
16000
93.8
Iph
93.8
93.8
93.8
93.8
kVA
4500
4500
4500
4500
Fig
Three Phase transformer connections
Most common is the delta-star connection. The star point is earthed and hence normally
appears in the secondary (lower voltage) circuit. At very high primary voltages it is
common to use a star connected winding with the insulation graded so that there is less
insulation (and hence cost) the closer to the earthed star you get. Star-star have tertiary
windings (normally a delta connection) whose purpose is to provide a closed path for 3rd
harmonic currents necessary to magnetise the core and maintain sinusoidal voltages.
13
If the transformer is energised from a stiff (strong, high fault level) busbar then the
magnetising current would like to be non-sinusoidal (peaky) but the unearthed star
winding does not permit third harmonic current to flow so the output voltage must be nonsinusoidal. If however a closed delta winding is connected on the same core, the 150Hz
current necessary to produce a sinusoidal output voltage can flow. Even when both the
star points are earthed a delta connected tertiary winding is normally present to both
provide a closed low impedance path for the 3rd harmonics and to allow some power to be
tapped off for substation control.
Where large power electronic converters have to be connected to a HV supply, the
associated transformer may be made as a pair of 3phase units with a phase displacement
of 30 degrees between the two sets of voltages to cancel the 5th & 7th harmonics (see later
notes).
( Symmonds).
14
A star-connected winding has a voltage across it of only of the line voltage. This enables
its insulation to be reduced to a minimum for a given supply voltage and make it the most
economic connection for a high-voltage winding. The star point is available if a neutral
point is required. In a 3-wire system, where the star point is not solidly earthed, the thirdharmonic e.m.f.s, will make the neutral unstable.
Delta Connection.
A delta system is a good short-distance distribution system. It is used for neighborhood
and small commercial loads close to the supplying substation. Only one voltage is vailable
between any two wires in a delta system. The delta system can be illustrated by a simple
triangle. A wire from each point of the triangle would represent a three-phase, three-wire
delta system. The voltage would be the same between any two wires.
The transformer must be insulated for the full line voltage, but will only carry
of the line current. Thus it is the most economical connection for a low-voltage winding.
The main drawback is that there is no neutral point and so it is unstable for general
4-wire supplies. The closed circuit formed by the delta connection produces a circulating
third-harmonic current. This eliminates the third-harmonic e.m.f.s from the external
circuit and also improves the magnetic flux wave in the core, so that third-harmonic
effects become negligible in the outer winding, which may be star connected. The delta
winding is more effective for unbalanced load conditions.
A number of the more common transformer connections are given below.
Star-Star.
Economical for H.V. transformers, but neutral unstable if not solidly earthed. Not
suitable for general supplies with unbalanced load. Generally used for small balanced
power loads.
Delta - Delta.
Economical for L.V. transformers. Third harmonics are damped out. Large
unbalanced loads can be supplied, but this connection is not often used as there is no
neutral point and a four-wire supply cannot be given.
Star - Delta.
Delta winding damps out the third harmonic e.m.f.s and stabilises the star point
of the primary. There is no secondary neutral and four-wire supplies cannot be given. The
main use is as a step down transformer to supply balanced three phase loads.
Delta - Star.
This is the most commonly used connection for general supplies, although as a
step-down transformer, the windings are not the most economical. The secondary star
point can be earthed and a four-wire supply given. Since there is a delta winding
(primary), the third-harmonic e.m.f. is damped and both balanced and unbalanced loads
can be supplied.
What is the meaning of DYN 11 on a transformer nameplate
Answer
15
16
H = NI
17
Before converter loads were widely used, one of the principal harmonic sources in the
power system was the excitation current of power transformers. Although modern
transformers do not generate significant harmonics under normal steady state operating
condition but can considerably increase their harmonic contribution under abnormal
conditions when their magnetic cores are saturated.
The proportion of harmonic current to fundamental is determined by the degree of
saturation at which the core is operated.
The non-sinusoidal magnetising current can be resolved into a fundamental and a series of
odd harmonics, of which the 3rd is the most important. The negative half-cycle is identical
with the positive half-cycle so no even harmonics appear.
Typical proportions of the harmonic current are:
Fundamental 100%, 3rd harmonic = 40%, 5th harmonic = 15%, 7th harmonic = 8%.
The current can be resolved using Fourier analysis into
i
=
i1 + i3 + ..
The current i1 is sinusoidal with a frequency equal to that of the source. The current
i3 is a third-harmonic current with a frequency that is three times the source frequency.
im(t) =
Harmonic Problems.
The number of non-linear loads which draw non-sinusoidal currents even if fed with
sinusoidal voltage - connected to the power supply system is large and is continuing to
grow rapidly. These currents can be defined in terms of a fundamental component and
harmonic components of higher order.
In power transformers the main consequence of harmonic currents is an increase in losses,
mainly in windings, because of the deformation of the leakage fields. Higher losses mean
that more heat is generated in the transformer so that the operating temperature increases,
leading to deterioration of the insulation and a potential reduction in lifetime.
As a result, it is necessary to reduce the maximum power load on the transformer, a
practice referred to as de-rating, or to take extra care in the design of the transformer to
18
reduce these losses. To estimate the de-rating of the transformer, the loads K-factor may
be used. This factor is calculated according to the harmonic spectrum of the load current
and is an indication of the additional eddy current
load losses. It reflects the excess losses experienced in a traditional wire wound
transformer.
</p><p>Modern transformers use alternative winding designs such as foil windings or
mixed wire/foil windings. For these transformers, the standardised K-factor derived for
the load current - does not reflect the additional load losses and the actual increase in
losses proves to be very dependent on the construction method. It is therefore necessary to
minimise the additional losses at the design stage of the transformer for the given load
data using field simulation methods or measuring techniques
3 Rating for Harmonic loads
Any transformer supplying a power electronic drive , UPS or such equipment will be
subjected to non-sinusoidal waveforms. This increases the temperature rise of both core
and windings necessitating a derating. The need for derating depends very much on the
underlying Standard to which the transformer is being manufactured.
Delta Connection.
If the transformer has a delta (primary or secondary) the phase voltages are
constrained to be a balanced fundamental set. Any third harmonic voltage would
appear as a result acting around the delta, which is therefore a short-circuit to the 3rd
harmonic and can circulate third harmonic magnetising current. The primary lines then
supply the fundamental magnetising current and the delta supplies the third harmonic. 3rd
harmonic currents do not appear in the lines.
Star connection
Star with neutral connection
Voltages are sinusoidal and third harmonic currents flow. Each line carries fundamental
and 3rd harmonic magnetising current. The fundamental neutral current is zero, but the
neutral will carry the 3rd harmonic currents from all three windings.
Transformer with star
19
I1+I3
3I3
I1+I3
I1+I3
3 V1 ph.
A voltmeter across a phase winding will measure the resultant phase voltages,
fundamental and plus 3rd harmonic.
Vph.rms =
(V12 + V32 )
230 V
=
(2502 - 2302 )
=
98 V
a voltmeter between the neutral and the star point, will read 98 V (at the third harmonic
frequency).
Star-star transformers are usually fitted with tertiary wind connected in closed delta. The
delta will carry the third harmonic magnetising current. If the star-star has no neutral the
delta will suppress the star point cycling. If there is a neutral, the delta will suppress the
third harmonic current which the neutrals would otherwise carry, since the delta path is
usually a lower impedance than the neutral path.
V3
20
Y-
. The secondary voltage is shifted 30 relative to the primary voltage.
Vca
Vbc
a HV
30
HV
Van LV
Vab
LV
Unbalanced Loading.
Unbalanced loading normally occurs when the secondary load is biased to one or two
phases. i.e. there is not equal distribution of the total transformer load one each phase, in
terms of voltage magnitude or phase angle, (120o apart in phase angle). Symmetrical
(sequence) components can be used to analyse this. Unbalanced conditions usually
happen when single phase loads are connected, (common in distribution systems). Any
unbalanced load can be represented (superposition), as a combination of balanced loads
and singlephase loads.
Winding configuration can pose problems. The star-star connection with no primary
neutral and with a load on one phase only can cause particular problems. Other
connections allow ampere-turn balance to be achieved.
I
I
I
I
I
I
I
I
21
(a)
Star-star with neutral connection, 1 load
(b)
Star-star without neutral connection, 1 load
2I/3
I/3
2I/3
I/3
I
I/3
(c)
Delta-delta connection, 1 load
I/3
(d)
Star-delta connection, 1 load
I
I
I
(e)
Delta-Star connection, 1 load
(f)
Star-zig-zag connection, 1 load
The problem with star-star and no primary neutral is that there is no way of achieving
m.m.f (ampere-turn) balance in the two unloaded phases.
I
I/2
I/2
Fig.
A load connected to the secondary of phase A draws heavy current, which induces a
corresponding current in the phase A primary. This current must flow through the B and
C primary winding: it has no other path. But there are no secondary B and C currents
(winding open circuited) so all these primary B and C currents act purely as magnetising
22
currents, and so cause a substantial change in the B and C primary voltages; i.e. a shift of
the star-point neutral (zero) potential. This shift will be in a direction which reduces the A
phase voltage and consequently the load current (and all currents) but will not be
directly in phase with VA.
Tertiary winding
The solution is to fit a tertiary winding connected in closed delta. This allows a current to
circulate in the delta and give balancing ampere-turns.
2I/3
I/3
I
I/3
I/3
I/3
I/3
Three winding transformer with single-phase load.
Fig.
Neglecting magnetising current and referring all currents to the primary, the behaviour for
each phase can be analysed (assuming that positive currents are considered as into the
star-point):
Phase
A
B
C
Primary
2/3 I
-1/3I
-1/3 I
Secondary
-I
0
0
Tertiary
1/3 I
1/3 I
1/3 I
Total
0
0
0
Griffiths.
The extra winding may be to provide an output at another voltage, or to provide a source
of VARs for power factor improvement or line voltage control. In some cases it might be
to suppress the triplen harmonics for three-wire circuits. The equivalent cct most
frequently used is shown in Fig where the quantities are referred to the primary side
and are per-phase.
R1
V1
Rc
I1 R2
jX2
IT RT
jXT
jX1
V2
jXm
VT
23
Fig
The magnetising branch is moved to the supply side for simplicity. Three short-cct tests
are required between the pairs of windings to establish the impedance values referred to
the primary side. Consider the previous transformer (Griffiths Parallel) with a tertiary
winding of 128 turns (giving an nominal phase voltage of 8kV). This extra three-phase
winding to be rated at 600kVA with an impedance of (0.2+j1.0) /phase. An overall
representation of the transformer will then be as in Fig. . where all windings are taken as
star connected.
VL=13.86kV
ZT= (0.2+j1.0)
phase
Z1=(0.03+j0.092)
/phase
N
Z2 = (0.44+j1.34)
phase
VL=7.8kV
VL=27.7kV
Tertiary
N
4,500kVA
Primary
Secondary
y
Fig.
Do qs (Griffiths
VL
N
N
VL
Primary
Secondary
y
Vb
Vb
Va
Va
Vc
Vc
24
REGULATION OF A TRANSFORMER
Regulation is a subject that regularly occurs in power systems. Regulation is a measure of
the voltage drop in a device or circuit. It compares the volt-drop at full-load with the
terminal voltage at no-load, both of which can be obtained for a transformer from simple
factory tests.
The voltage regulation of a transformer is the change in the terminal voltage Vs between
no-load and full-load at a given power factor. It is usually expressed as a percentage of the
rated voltage.
The voltage regulation can be described as the change in magnitude of the secondary
voltage as the load current changes from no-load to the loaded condition.
Voltage Regulation =
V2
NL
V2
V2
The voltages in eqn above can be calculated by using equivalent circuit parms referred to
the primary, or secondary. The phasor diagram for the single-phase transformer or one
phase of three-phase transformer is Figure . Consider the equivalent cct referred to the
primary
Voltage Regulation =
V2
NL
V2
V2
jXeq
I2/a = I2`
aV2=V2`
25
V1 V2
Voltage regulation (%) =
V2
.100%
The voltage regulation depends on the power factor of the load. This can be appreciated
from the phasor diagram of the voltages:
V1
I2`Zeq1
V2`
I2`Xeq1
2+
eq1
I2`Req1
I2`
Fig. 2
The locus of V1 will be maximum if the phasor I2`Zeq1 is in phase with V2`. That is,
2 + eq1 = 0
Where 2 is the angle of the load impedance
eq1 is the angle of the transformer equivalent impedance, Zeq1.
Therefore 2 = - eq1
Therefore the maximum voltage regulation occurs if the power factor angle of the load is
equal to the transformer equivalent impedance angle and the load power factor is lagging.
In most power transformers Req is much smaller than Xeq and so Req can be ignored in
regulation and fault level calculations.
V1
I2`Xeq1
90o-
2
V2`
2
I2`
26
I1 R1
1
E1
I2
E2
I1 = I
Z2
Z1 + Z 2
I2 = I
Z1
Z1 + Z 2
jX1
Load
R2
jX2
I1 Z 2
=
I 2 Z1
VA1 = VI1
VI1 = VI
Z2
Z1 + Z 2
= total load VA
Also
Z2
Z1 + Z 2
Z1
Z1 + Z 2
27
Z1
I1
E1
Z2
I2
E2
Equivalent Circuit
The following conditions must exist for transformers to operate satisfactorily in parallel:
1. Connection diagrams must be identical. Paralleling transformers with different
connection diagrams is similar to short circuiting their secondary windings.
2. Voltage ratios must be the same. If voltage ratios are not the same, circulating
currents will flow in the secondaries with no or little load, and the division of load
will be improper.
3. Percent impedance, including primary and secondary leads to each transformer,
should be nearly equal. If the impedance's are equal and the turns ratios are
identical, the paralleled transformers will divide the load currents (properly) in
proportion to their kVA ratings. If the percent impedance's are different, the
transformer with the lower percent impedance will take more than its proper share
of the load.
4. The ratio of R to X must be the same for both transformers.
5. For three-phase transformers the ephase sequence and phase shifts must be the
same.
The conditions are an ideal scenario and unlikely to be achieved in practice, so he
maximum total output is usually less than the sum of the individual outputs. Briefly,
condition (2) ensures that there are no circulating currents, condition (3) ensures that
equality of voltage is observed at all times, and condition (4) maintains the same
power factor for each transformer.
It is convenient to use an equivalent cct referred to the secondary side for calculations
on load division between transformers.
The mag. current is ignored without detriment since it only affects the primary and
will not result in any circulating currents.
I1 = (E1 -V)/Z1,
I2 = (E2 -V)/Z2,
I1 = I1 + I2
V/Z = (E1 -V)/Z1 + (E2 -V)/Z2
V{1/Z + 1/Z1 + 1/Z2] = E1/Z1 + E2/Z2
28
I2 = (E2 -V)/Z2,
I = I1 + I2
I1 = I - I2
I1 = V/Z - (E2 -V)/Z2
V = Z(V1 -V)/Z1
I1 =
V1Z 2 + (V1 V2 ) Z
Z1 Z 2 + Z ( Z1 + Z 2 )
I1 R1
1
E1
I2
E2
Load Z
jX2
R2
E1 = I1 Z1 + (I1 + I2)Z
E2 = I2 Z2 + (I1 + I2)Z
29
I1 =
E1 Z 2 + ( E1 E 2 ) Z
Z1 Z 2 + Z (Z1 + Z 2 )
I2 =
E 2 Z 1 + ( E 2 E1 ) Z
Z1 Z 2 + Z ( Z1 + Z 2 )
E1 E 2
Z1 + Z 2
and I1 = -I2
Here actual values of impedance must be used since ratios are not involved, unless all
quantities are reduced to a common base.
Tertiary winding
The solution is to fit a tertiary winding connected in closed delta. This allows a current to
circulate in the delta and give balancing ampere-turns.
2I/3
I/3
I
I/3
I/3
I/3
I/3
Three winding transformer with single-phase load.
Fig.
Neglecting magnetising current and referring all currents to the primary, the behaviour for
each phase can be analysed (assuming that positive currents are considered as into the
star-point):
Phase
A
B
C
Primary
2/3 I
-1/3I
-1/3 I
Secondary
-I
0
0
Tertiary
1/3 I
1/3 I
1/3 I
Total
0
0
0
Griffiths.
The extra winding may be to provide an output at another voltage, or to provide a source
of VARs for power factor improvement or line voltage control. In some cases it might be
to suppress the triplen harmonics for three-wire circuits. The equivalent cct most
30
frequently used is shown in Fig where the quantities are referred to the primary side
and are per-phase.
R1
V1
I1 R2
jX2
IT RT
jXT
jX1
V2
jXm
Rc
VT
Fig
The magnetising branch is moved to the supply side for simplicity. Three short-cct tests
are required between the pairs of windings to establish the impedance values referred to
the primary side.
There are two turns ratios V1:V2 and V1:V3. It is necessary to refer all impedances to
primary values, then the transformer can be represented by a simple circuit and all
required values found as with the simple 2-winding transformer. Note that with the 2winding transformer it is not possible to separate primary and secondary leakage
reactance and these are usually considered to be equal. However the primary, secondary
and tertiary equivalent impedances of a 2-winding transformer can be found from short
circuit tests.
Short Circuit Tests (neglecting resistances)
S
XPS
X2
X1
XST
ZS
X3
XPT
T
ZT
Three s/c tests have to performed in order to cal. The three unknowns, X1, X21 and X31
Supply
O/C
S/C
Result
Test 1
XPT = VP/IT
Test 2
XPS = VP/IS
Test 3
XST = VS/IT
31
j0.08
ZS
X31
j0.16
T
ZT
Ex.
Obtain the equivalent circuit in pu of a 3 ph., 3 winding transformer rated: 20MVA,
132kV/30MVA, 33kV/10MVA, 6.6kV.
Chose a 30MVA base
The following are the s/c test results:
(i)
HV to T rated current is 87.5A and requires 7.92kv (line) to inject.
(ii)
HV to LV rated current, 87.5A and requires 13.2 kV (line) to inject.
(iii) T to LV rated current, 525A requires 2.64 kV kV Line to inject.
Soln,
(i) XP + XT = 7.92kV/3/87.5 = 52.3
1.0 pu in
(ii)
XP + XS = 13.2kV/3/87.5 = 87.1
1.0 pu in
32
XP + XS = 87.1/581 = 0.15pu
(or XP + XS = 0.09 . 13.2kV/7.92kV = 0.15 pu )
(iii)
XT + XS = 2.64kV/3/525 = 2.9
1.0 pu in
XP
XT
XS
33