Control Logic

1) CHW Pump
Discharger header pressure (Existing Pr. Transmitter)

2) PHE Chiller
AFT
Water outlet TT
Flow switch

3) Condenser
Discharge Header Pressure (PT)
No use of fan VFD. SS only to be provided as per tender.

4) Ice Silo
Existing logic

5) Ammonia Pump
PDC
Discharge header PT
Low level Float

6) LP Receiver
Liquid SOV Cutoff - Operating level float
Compressor Trip - High level float (New & Old LP receiver -5/-2)
Need to be confirmed.

7) Compressor
Compressor Trip - High level float (New & Old LP receiver -5/-2)
Compressor Trip High level float in Economizer No Need.
Liquid SOV of Economizer - Operating level float.
SOV of Economizer port - Compressor Loading percentage.