You are on page 1of 2

Smart Site Management Unit

SCC800

Introduction
Smart site management unit SCC800 is field supervision unit for site
and power. It applies advanced ICT technology to realize site
digitization, meticulous management, and build one operational,
maintenance and high reliability telecom energy network.
SCC800 is modular design. It is composed of the main control
module, the sensor access module, the intelligent device access
module, network interface module and D.G. access module and so
on. It can finish data acquisition, analysis processing, intelligent
dispatch and so on for intelligent equipment, no-intelligent
equipment and environment.
Features
Features
Modular design, supports hot plug and independent replacement, easy for maintenance and smooth expansion.
Multiple physical interfaces easily access different network element such as AI, DI, DO, RS232/RS484, CAN, FE and
so on.
Supports APP to debug and test site for efficient site deployment and maintenance.
Supports the local LCD display and maintenance
HTTPS encryption for network security prevents hacker attacks.
Records important log and makes sure important issues are traceable. Supports data storage and data retransfer to
keep data integrity.

Networking
Supervision Center SC GPRS/3G/4G/IP
RS485/232/CAN
Work AI/DI/DO
Mobile APP Station

SCC800

Smart site management

Grid D.G. Fuel Door


Battery A/C Environ. Video
Power Power Tank Access
Specifications

SCC800
1 FE
1 RS485 / 232 (For northbound management)
Site Monitoring Unit Communication Port
1 RS485 / CAN (For southbound equipment)
2 USB

1 ambient T/H sensor (TEM-HUM)


1 water sensor (WATER)
2 temperature sensor (TMP1, TMP2)
Sensor Port
1 door status sensor (GATE)
1 smoke sensor (SMOKE)
1 battery temperature sensor (BTEMP)

Dry Contact Input Port 6 DI (DIN1~DIN6)


User Interface Module
Dry Contact Output Port 4 DO (ALM1, ALM2, ALM3, ALM8)

2 Battery middle voltage monitoring


Battery Monitoring
2 Battery total voltage monitoring

Communication Port 2 RS485 (COM: 4 line RS485; ALM7: 2 line RS485)

Power Port 1 -48Vdc input

Communication Port 4 FE (FE1~FE4)

Network Interface Module Signal Input 4 AI/DI (4-20mA, 0-10V, CH14), 2 AI (4-20mA , CH56)

Power Port 2 12 Vdc output (0.3A max)

DG Control Port DG on/off control (DG1_CTL, DG2_CTL.)

DG Reset Port The DG is reset after the port is closed (RST1, RST2)
Generator Interface Module
Fuel Level Detection Port Fuel level detection (AI1, AI2)

Communication Port 1 RS485 , 1 CAN

Communication Interface Module Communication Port 4 RS485 , 1 CAN

Networking GPRS, 3G, 4G, IP

Intelligent Equipment Accessing Supports multiple mode accessing: RS485, RS232, CAN, IP

Network security Network data encryption, safety certification, network port protection

Dimension (W D H) 482.6 mm 330 mm 43.6 mm

Weight 4kg
Mechanical Parameters
Input Voltage -36~-60 Vdc

Power Consumption 10 W

Note: Whether all the functions of controller can be used depends on the power system structure and configuration.
Copyright Huawei Technologies Co., Ltd. 2016. All rights reserved. Huawei Industrial Base
No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of
Bantian Longgang
Huawei Technologies Co., Ltd.
Shenzhen 518129, P.R. China
General Disclaimer Tel: +86-755-28780808
The information in this document may contain predictive statements including, without limitation, statements regarding the future www.huawei.com
financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual
results and developments to differ materially from those expressed or implied in the predictive statements. Therefore, such information
is provided for reference purpose only and constitutes neither an offer nor an acceptance. Huawei may change the information at
any time without notice. HUAWEI TECHNOLOGIES CO., LTD.

You might also like