You are on page 1of 1

Air System Sizing Summary for CORRIDOR 3

Project Name: 21014 BARKA MALL R4 08/01/2017


Prepared by: Amjaad 07:55AM

Air System Information


Air System Name .................................... CORRIDOR 3 Number of zones ............................................................. 1
Equipment Class ......................................... SPLT AHU Floor Area ................................................................. 260.0 m
Air System Type ................................................ SZCAV Location .................................................... Masqat, Oman

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s .......................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space L/s ...................... Individual peak space loads Sizing Data ...................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load .......................................................... 43.2 kW Load occurs at ................................................... Jun 1700
Sensible coil load ................................................... 34.1 kW OA DB / WB ...................................................... 44.6 / 29.8 C
Coil L/s at Jun 1700 .............................................. 2288 L/s Entering DB / WB ............................................. 25.5 / 18.2 C
Max block L/s ........................................................ 2288 L/s Leaving DB / WB .............................................. 13.1 / 12.5 C
Sum of peak zone L/s ........................................... 2288 L/s Coil ADP ..................................................................... 11.7 C
Sensible heat ratio ............................................... 0.790 Bypass Factor .......................................................... 0.100
m/kW ....................................................................... 6.0 Resulting RH ................................................................. 63 %
W/m ..................................................................... 166.3 Design supply temp. ................................................... 12.5 C
Water flow @ 5.6 K rise ......................................... N/A Zone T-stat Check .................................................... 1 of 1 OK
Max zone temperature deviation .................................. 0.0 K

Supply Fan Sizing Data

Actual max L/s ....................................................... 2288 L/s Fan motor BHP ........................................................... 0.28 BHP
Standard L/s .......................................................... 2284 L/s Fan motor kW ............................................................. 0.21 kW
Actual max L/(s-m) ................................................ 8.80 L/(s-m) Fan static ....................................................................... 50 Pa

Outdoor Ventilation Air Data


Design airflow L/s ........................................................ 0 L/s L/s/person ................................................................... 0.00 L/s/person
L/(s-m) ................................................................... 0.00 L/(s-m)

Hourly Analysis Program v4.50 Page 1 of 1

You might also like