Transformer Voltage Regulation (1)
Ideal: VP
n
VS
NP
n
NS
Non-ideal:
UCF
Transformer Voltage Regulation (2)
Full load : VP
VSfl ( Reqs jX eqs )I S
n
VSnl VSfl VP / n VSfl
Voltage regulation: VR 100% 100%
VSfl VSfl
UCF
Transformer Voltage Regulation (3)
VP
VSfl ReqsI S jX eqsI S
n
VP / n VSfl
Discussions: VR 100%
VSfl
(1) Load is lagging (inductive)
I 0
s
VP / n VSfl VR 0
UCF
Transformer Voltage Regulation (4)
VP
VSfl ReqsI S jX eqsI S
n
(2) Load is resistive (unit power factor)
VP / n VSfl VR 0
(3) Load is leading (capacitive)
I 0
s
VP / n may be VSfl VR may be <0
UCF
Discussions on Phasor Diagram
lagging load VP
VS ReqsIS jXeqsIS
n
I 0
s
leading load
I 0
s
Assume the angle of VS is 0.
VP
Real part: cos VS Reqs I S cos I s X eqs I S sin I s
n
VS ( Reqs cos X eqs sin ) I S
VP
Imaginary part: sin Reqs I S sin I s X eqs I S cos I s
n
( Reqs sin X eqs cos ) I S
Transformer VR Calculation Case I
UCF
VP / n VS
VR 100%
VS
VP
VS ( Reqs jX eqs ) I S
n
Transformer VR Calculation Case II (1)
UCF
VP / n VS
VR 100%
VS
VP
VS ( Reqs jX eqs ) I S
n
Given: (1) VP (fixed)
(2) IS of the load
(3) power factor (pf) of the load
Find: VS
IS : cos1 ( pf ) + lagging, - leading
jIS
set V 0
S
I V
S S
IS IS e
UCF
Transformer VR Calculation Case II (2)
lagging load VP
VS (Reqs jXeqs )IS
n
I 0
s VS ZeqsIS
VP
Imaginary part: sin ( Reqs sin X eqs cos ) I S = Im( Z eqs I S )
n
sin 1 ( Reqs sin X eqs cos ) I S / (VP / n) = sin 1 Im( Z eqs I S ) / (VP / n)
VP / n VS
VR 100%
VS
VP
VS (Reqs jXeqs )IS
n
Given: (1) VP (fixed) VS ZeqsIS
(2) ZL
Find: VS
VP VP j 0
Assume the angle of VP is 0. e
n n
VP / n
IS
Zeqs ZL
ZL VP
VS ZLIS
Zeqs ZL n
UCF
Example 3
For a 15 kVA, 2300/230 V, 60 Hz transformer, the equivalent circuit
parameters are:
Req 5, X eq 6, RC 100 k, X M 10 k
Find voltage regulation:
(1) The secondary voltage 230 V (fixed), full load at (a) 0.8 pf lagging;
(b)1.0 pf; (c) 0.8 pf leading;
(2) The primary voltage 2300 V (fixed), load current 65 A at
(a) 0.8 pf lagging; (b)1.0 pf; (c) 0.8 pf leading;
(3) The load resistance Z L 3+j2 .
trans3.m.
Per Unit System
UCF Per Unit System (1)
Actual quantity
Quantity in per unit
Base value of quantity
UCF Per Unit System (2)
Analysis Procedure:
(1) select VA base and voltage base
VA base
(2) current base
voltage base
voltage base
(3) resistance base
current base
(4) normalize all the quantities (or : get quantities per unit)
(5) perform a standard circuit analysis with all quantities
in per unit
(6) actual values of results
base value solved quantity in per unit
UCF Example 4 (1)
UCF Example 4 (2)
Process is in trans4.m.
UCF
Non-ideal Transformer in Per Unit System
Or
UCF
Voltage Regulation in Per Unit System
Req , pu I S , pu
VS , pu
Assume the angle of VS , pu is 0.