You are on page 1of 1

general diagram

wiring diagrams for basic version


esquemas elctricos STR 08 to 58
E30721

CHSSIS AUXILIARIES CONTROL UNIT BREAKER AUXILIARIES


CN 1 - CN +
Fu (1)

AT ready
BPO to
closed

BPF
connected disconnected fault closed open springs
charged

314 312 324 322 334 332 344 342 352 354 362 364 372 374 82 84 212 222 234 244 12 14 22 24 32 34 42 44 D4 C12 C2 A4 252 254 262 B4

CE
ou
or

M
MN
or MX XF
MNR
MX
OF

F F O O

SDE CH

processing
unit PF

CD CT

311 321 331 341 351 361 371 81 211 221 231 241 11 21 31 41 D1 C11 C1 A1 251 B1

Fu (1)

CN2 - CN

Fu :
fuse O : 2 auxiliary NO contacts
E30718

(10A/240V AC) MNR wiring for instantaneous tripping


AT :
emergency off
BPO :
open pushbutton F : 2 auxiliary NC contacts
(10A/240V AC) D4 254 262
BPF :
close pushbutton
SDE : fault trip indication contact
CE :
"connected" position contact (10A/240V AC)(exept STR 08) MNR
(10A/240V AC)
CH : "spring charged" contact
M : spring charging motor (180VA) (10A/240V AC) D1
XF : closing release (20VA) PF : ready to close contact Use the terminal 262
MX : shunt release (20VA) (10A/240V AC) (closing possible if ("spring charged contact")
MN : undervoltage release (20VA) breaker is open, not locked and and 254 (normally open contact of the PF)
operating mechanism charged)
MNR : time delayed undervoltage release
(20VA) CD : "disconnected" position contact
(10A/240V AC)
OF : auxiliary changeover contacts
(10A/240V AC) CT : "test" position contact
(10A/240V AC)

(1) to determine according to the auxiliary


consumptions.
Accessories such as pushbuttons, lamps and fuses
are not supplied with the circuit breaker
Diagram shown with circuits de-energized, all
devices open and relays in normal position, MN or
MNR energized. source : 689 905

28 Merlin Gerin