Professional Documents
Culture Documents
App-A BLBK295-Teodorescu October 22, 2010 23:53 Printer Name: Yet to Come
Appendix A
Space Vector Transformations
of Three-Phase Systems
A.1 Introduction
A generic three-phase electrical system consists of a set of three voltages and three currents
interacting with each other to deliver electrical power. A practical three-phase system cannot
be considered as the simple addition of three independent single-phase subsystems. Actually,
particular relations exist between the phase variables of a three-phase system, such as those
resulting from the Kirchhoff laws or regarding phase sequences, which invite the application
of certain space vector transformations to obtain a more elegant and meaningful representation
of its variables. Generally, the control system of a power converter connected to a three-phase
system is based on these transformed variables. This appendix reviews the most commonly
used space vector transformations and highlights their applications in control grid-connected
power converters.
Grid Converters for Photovoltaic and Wind Power Systems Remus Teodorescu, Marco Liserre and Pedro Rodríguez
© 2011 John Wiley & Sons, Ltd. ISBN: 978-0-470-05751-3
P1: OTA/XYZ P2: ABC
App-A BLBK295-Teodorescu October 22, 2010 23:53 Printer Name: Yet to Come
150
va
vc
100
vb
50 Vc Va
vabc
-50
Vb
Va = 148.7∠3.6º
-100
Vb = 67.5∠ − 61.5º
-150 Vc = 112.8∠165.5º
0 10 20 30 40
t [ms]
(a) (b)
Figure A.1 Unbalanced three-phase system: (a) instantaneous voltage waveforms and (b) phase voltage
phasors
The steady-state voltage waveforms of a three-phase unbalanced system together with their
phasor representation on a Gauss plane are shown in Figure A.1.
Applying the symmetrical components method, these three unbalanced phasors representing
the three-phase voltages can be transformed into a new set of three phasors representing the se-
quence components of one of the phases of the three-phase system. For example, the positive-,
negative- and zero-sequence phasors of phase a (Va+ , Va− and Va0 ) can be calculated by the
following transformation matrix:
with
⎡ ⎤ ⎡ ⎤ ⎡ ⎤ ⎡ + +⎤
Va Va ∠θa Va+ Va ∠θa
⎢ ⎥ ⎢ ⎥ ⎢ V − ⎥ ⎢ V − ∠θ − ⎥
Vabc = ⎣ Vb ⎦ = ⎣ Vb ∠θb ⎦ , V+−0(a) =⎣ a ⎦=⎣ a a ⎦
Vc Vc ∠θc Va0 Va0 ∠θa0
⎡ ⎤
1 α α2
1 ⎢1 α2 α⎥
[T+−0 ] = 3 ⎣ ⎦ (A.2)
1 1 1
where α = e j2π/3 = 1∠120◦ is known as the Fortescue operator. The phasors representing the
sequence components for phases b and c are given by
The inverse transformation to pass from the phasors representing symmetrical components of
phase a to the phasors representing the unbalanced phase voltages is given by
with
⎡ ⎤
1 1 1
[T+−0 ]−1 = ⎣ α2 α 1⎦ (A.5)
α α2 1
As an example, the phasors representing the sequence components of the unbalanced voltages
of Figure A.1, together with their corresponding instantaneous waveforms, are shown in
Figure A.2.
vc
⎡ ⎤ ⎡ ⎤ ⎡ ⎤
cos(ωt) cos(ωt) cos(ωt)
⎢ 2π ⎥ ⎢ 2π ⎥ ⎢ ⎥
= V + ⎣ cos(ωt − 3 ) ⎦ + V − ⎣ cos(ωt + 3 ) ⎦ + V 0 ⎣ cos(ωt) ⎦ (A.6)
cos(ωt + 2π3
) cos(ωt − 2π3
) cos(ωt)
It is worth mentioning that the Lyon transformation is usually defined by the following
normalized matrix:
⎡ ⎤
√ 1 α α2
1 ⎣
T+−0 = 3 [T+−0 ] = √ 1 α2 α⎦ (A.9)
3 1 1 1
−1 T
where T+−0 = T+−0 .
P1: OTA/XYZ P2: ABC
App-A BLBK295-Teodorescu October 22, 2010 23:53 Printer Name: Yet to Come
150
0
v
-50
Va+ = 100∠30º
-100
Vb+
Vb+ = 100∠ − 90º
-150
0 10 20 30 40
Vc+ = 100∠ − 210º
t [ms]
(a)
150
100
Vb−
− − −
v
a v
c v b
50
abc
0
Vc− Va−
v
-50
Va− = 50∠ − 40º
-100 Vb− = 50∠80º
Vc− = 50∠ − 160º
-150
0 10 20 30 40
t [ms]
(b)
150
100
0
v
-150
0 10 20 30 40
t [ms]
(c)
Figure A.2 Sequence components of the unbalanced three-phase system of Figure A.1: (a) positive-
sequence phasors, (b) negative-sequence phasors and (c) zero-sequence phasors
P1: OTA/XYZ P2: ABC
App-A BLBK295-Teodorescu October 22, 2010 23:53 Printer Name: Yet to Come
1
2
ωin2
vin α vin LPF ( s) =
( s + ωin )
2
3
LPF
From (A.8) it can concluded that, independently of the scale factor used in the Lyon
transformation, the resulting vector consists of two complex elements, v+ and v− , plus a
real element v0 . The complex elements v+ and v− can be represented by instantaneous space
vectors, having the same amplitude and rotating in opposite directions. Therefore, v+ and
v− should not be mistaken for the positive- and negative-sequence voltage vectors v + abc and
v−abc . The real element v0
is directly related to the zero-sequence component of the original
three-phase voltage vector.
To calculate the positive- and negative-sequence voltage vectors, v + −
abc and v abc , from the
unbalanced input vector vabc , it is necessary to translate the Fortescue operator, α, from
the frequency domain to the time domain. This translation can be performed by using a
simple time-shifting operator, provided the frequency of the sinusoidal input is a well-known
magnitude. In such a case, a 2/3 T time-shifted sinusoidal signal, with T the signal period, can
be understood as a 120◦ leaded version of the original sinusoidal
√signal.
This operator in the
time domain is named a in this appendix. Since α = −1 2 + j 3 2, the a operator can be
implemented by using a proper filter to generate the 90◦ phase-shifting associated to the j
operator [3]. As an example, Figure A.3 shows a simple implementation of the a operator
based on a second-order low-pass filter (LPF) tuned at the input frequency with a damping
factor ξ = 1. The a2 operator can be implemented by multiplying the output signal of the LPF
by −1.
Therefore, the following expressions can be used to calculate the instantaneous positive-
and negative-sequence components of v abc :
⎡ ⎤ ⎡ ⎤⎡ ⎤
va+ 1 a a2 va
⎢ +⎥ 1⎢ 2
a ⎦ ⎣ vb ⎥
⎥ ⎢
v+
abc = [T+ ] v abc ; ⎣ vb ⎦ = ⎣a 1 ⎦ (A.10)
3
vc+ a a2 1 vc
⎡ −⎤ ⎡ ⎤⎡ ⎤
va 1 a2 a va
⎢ −⎥ 1⎢
a2 ⎥ ⎢v ⎥
v−
abc = [T− ] v abc ; ⎣ vb ⎦ = ⎣ a 1 ⎦⎣ b ⎦ (A.11)
3
vc− a2 a 1 vc
from (A.8) as v+ , v+ , v 0 , although other combinations are also possible. At this
point, the following real transformation matrix can be written:
⎡ ⎤ ⎡ ⎤⎡ ⎤
v+)
( 1 (α) (α 2 ) va
⎢ (
v + ⎥ 1⎢
(α 2 ) ⎥ ⎢ ⎥
⎣ ) ⎦ = ⎣ 0 (α) ⎦ ⎣ vb ⎦ (A.12)
3
v 0
1 1 1 vc
A similar reasoning caused Clarke to reformulate the Lyon transformation and to propose the
following transformation matrix [4]:
v αβ0 = Tαβ0 v abc (A.13)
⎡ 1 1 ⎤
⎡ ⎤ 1 − −
⎢ ⎥⎡ ⎤
vα ⎢ √2 √2 ⎥ va
⎢v ⎥ 2⎢⎢ 3 3⎥
⎥⎢ ⎥
⎣ β⎦= 0 − ⎣ vb ⎦ (A.14)
3⎢⎢ 2 2 ⎥
⎥
v0 ⎣ 1 1 1 ⎦ vc
√ √ √
2 2 2
−1 T
where Tαβ0 = Tαβ0 .
It is worth remarking here that the input and output vectors have the same norm when the
normalized transformation of (A.14) is applied, i.e.
The αβ0 reference frame is graphically depicted in Figure A.4. In this figure, the αβ plane holds
all the symmetrical vectors, i.e. those vαβ vectors with no zero sequence (va + vb + vc = 0),
whereas the 0 axis is aligned with the space diagonal of the abc reference frame.
P1: OTA/XYZ P2: ABC
App-A BLBK295-Teodorescu October 22, 2010 23:53 Printer Name: Yet to Come
0
v0
v = vαβ 0 = v abc
b
a c
vβ β
vα
α vαβ
α − β plane
v dq0 = Tdq0 v αβ0 (A.18)
0
v0
v = v dq 0 = vαβ 0 = v abc
q
vq
vβ β
vα θ
α vαβ
vd
d
α − β plane ω
⎡ ⎤ ⎡ ⎤⎡ ⎤
vd cos(θ ) sin(θ ) 0 vα
⎣ vq ⎦ = ⎣ − sin(θ ) cos(θ ) 0 ⎦ ⎣ vβ ⎦ (A.19)
v0 0 0 1 v0
−1 T
where Tdq0 = Tdq0 . Therefore, the transformation matrix to translate a voltage vector
from the abc stationary reference frame to the dq0 synchronous reference frame is given by
vd2 + vq2 + v02 = vα2 + vβ2 + v02 = va2 + vb2 + vc2 (A.22)
Expressing voltage and currents using space vectors allows instantaneous phenomena in three-
phase systems to be studied using an efficient and elegant formulation. This formulation is
particularly useful to control active and reactive power components in three-phase systems.
References
[1] Fortescue, C. L. ‘Method of Symmetrical Coordinates Applied to the Solution of Polyphase Networks’. Transac-
tions of the AIEE, Part II, 37, 1918, 1027–1140.
[2] Lyon, W. V., Application of the Method of Symmetrical Components, New York: McGraw-Hill, 1937.
[3] Iravani, M. R. and Karimi-Ghartemani, M., ‘Online Estimation of Steady State and Instantaneous Symmetrical
Components’. Proceedings of the IEE on Generation, Transmission and Distribution, 150(5), September 2003,
616–622.
[4] Clarke, E., Circuit Analysis of AC Power Systems, Vol. 1, New York: John Wiley & Sons, Inc., 1950.
[5] Park, R. H., ‘Two Reaction Theory of Synchronous Machines. Generalized Method of Analysis – Part I’. In
Proceedings of the Winter Convention of the AIEE, 1929, pp. 716–730.