Professional Documents
Culture Documents
2
Transient Analysis
of Three-Phase Power Systems
Figure 2.1 A set of three unbalanced voltage phasors resolved in three sets of symmetrical
components
SEQUENCE COMPONENTS FOR UNBALANCED NETWORK IMPEDANCES 17
The relation between the set of phasors (Va , Vb , Vc ) and the positive
phasors, negative phasors, and zero phasors is
V 1 1 1 Va0
a
Vb = 1 a2 a Va1 (2.2)
Vc 1 a a2 Va2
or
Vabc = AV 012 (2.3)
The a-operator rotates any phasor quantity by 120° and the inverse
relation of Equation (2.2) can be written as
V 1 1 1 Va
a0
1
Va1 = 1 a a2 Vb (2.4)
3
Va2 1 a2 a Vc
or
V012 = A−1 Vabc (2.5)
Ia Zaa
Zab
Ib Zbb
Zca
Zbc
Ic Zcc
m + − n
Vmn
V Z Zab Zac Ia
mn−a aa
Vmn = Vmn−b = Zba Zbb Zbc Ib (2.7)
Vmn−c Zca Zcb Zcc Ic
with
Zs0 = 13 (Zaa + Zbb + Zcc )
Zs1 = 13 (Zaa + aZbb + a2 Zcc ) (2.11)
Zs2 = 13 (Zaa + a2 Zbb + aZcc )
and
Zm0 = 13 (Zbc + Zca + Zab )
Zm1 = 13 (Zbc + aZca + a2 Zab ) (2.12)
Zm2 = 13 (Zbc + a2 Zca + aZab )
Vmn−1 = (Zs1 − Zm1 )Ia0 + (Zs0 − Zm0 )Ia1 + (Zs2 + 2Zm2 )Ia2 (2.13)
The positive-sequence voltage drop depends not only on Ia1 but also on
Ia2 , and this means that there is a mutual coupling between the sequences.
Further, we can conclude that Zmn−012 is not symmetric; therefore, the
mutual effects are not reciprocal and this is a rather disturbing result.
This is the reason that we prefer to work with the special cases of both
self-impedances and mutual impedances in which the matrix Zmn−012 is
simplified. In many practical cases, the mutual impedances can be neglected
because they are small compared with the self-impedances. The matrix
Zmn−012 , however, is nonsymmetric with respect to Zs and Zm terms
and is therefore not made symmetric by eliminating either the self-terms
or the mutual terms, and because elimination of self-impedance terms
cannot be applied (because of the inherent nature of the power system),
a simplification must be sought in the special case of equal impedance
and symmetric impedance. In many practical power system problems, the
self-impedances or mutual impedances are equal in all the three phases. In
such cases, Equation (2.11) and Equation (2.12) become
and
Zm0 = Zbc , Zm1 = Zm2 = 0 (2.15)
20 TRANSIENT ANALYSIS OF THREE-PHASE POWER SYSTEMS
Ia 0 F0 Ia1 F1 Ia 2 F2
+ + +
Z0 + Z1 Z2
Va 0 Vf Va1 Va 2
−
− − −
N0 N1 N2
Figure 2.3 Sequence networks for the zero, positive, and negative sequences
22 TRANSIENT ANALYSIS OF THREE-PHASE POWER SYSTEMS
a F
+
b
+
c
+
Zf
Va Vb Vc Ia Ib = 0 Ic = 0
− − −
Figure 2.4 Three-phase circuit diagram of an SLG fault at fault point F of the power
system
Ib = Ic = 0 (2.20)
Va = Zf Ia (2.21)
These boundary equations are transformed from the a-b-c system to the
0-1-2 coordinate system:
This implies that all the sequence currents are equal, and when the
boundary equations for the voltage relations of Equation (2.21) are trans-
formed, we find the relation
The fact that the sequence currents are equal implies that the sequence
networks must be connected in series. From Equation (2.24), we note
that the sequence voltages add to 3Zf Ia1 – this requires the addition of
24 TRANSIENT ANALYSIS OF THREE-PHASE POWER SYSTEMS
F1 Ia1
+
+ Z1
Vf Va1
−
−
N1
F2
Z2 +
Va 2 3 Zf
−
N2
F0
Z0 +
Va 0
−
N0
and now that the sequence current relations are known, we can determine
the sequence voltage relations from Equation (2.24).
a F
+
b
+
c
+
Zf Zf Zf
Va Vb Vc Ia Ib Ic
Zg
Ia + Ib + Ic
− − −
Figure 2.6 Three-phase circuit diagram of a TPG fault at fault point F of the power
system
Va = Zf Ia + Zg (Ia + Ib + Ic ) (2.26)
Vb = Zf Ib + Zg (Ia + Ib + Ic ) (2.27)
Vc = Zf Ic + Zg (Ia + Ib + Ic ) (2.28)
The boundary conditions are again transformed from the a-b-c system
to the 0-1-2 coordinate system, and when we write in terms of the
symmetrical components of phase a, we get
F1 Ia1 F2 Ia 2 F0 Ia 0
+ Z1 + Z2 + Z0 +
Vf Va1 Zf Va 2 Zf Va 0 Z f + 3Z g
− − − −
N1 N2 N0
This leads to Ia1 = Ia , Ia0 = Ia2 = 0. The sequence networks are therefore
connected as shown in Figure 2.7. When the fault impedance Zf is small,
or even zero, the TPG fault is in fact a short circuit.
After clearing a three-phase fault, the power system changes from the
steady-state situation, in which the three-phase short-circuit current is
flowing, to the state in which only the power frequency–recovery voltage
is present across the contacts of the circuit breaker. In an inductive circuit,
the change from one steady state to another is always accompanied by a
transient – the transient recovery voltage or TRV. At current zero, the arc
voltage and the arc current extinguish and the TRV oscillates from zero
to the crest of the AC power frequency–recovery voltage (See Chapter 4,
Circuit Breakers). One of the breaker poles clears first and the two last
clearing poles interrupt 90° later – they, in fact, form a single-phase circuit.
Of interest is the value of the AC power frequency–recovery voltage of
the first clearing phase because the TRV oscillates to this value. Let us
consider the situation depicted in Figure 2.8.
The system is grounded by means of a neutral impedance at the star
point of the three-phase delta/wye transformer. When the first pole of the
circuit breaker interrupts the short-circuit current, let us assume that this
is phase a, the other two poles are still arcing and therefore in a conducting
state. In fact, these two last clearing poles interrupt a double line-to-ground
Power
Generator transformer
Transmission line Circuit breaker
Zn TPG
(DLG) fault. The boundary conditions for this DLG fault are
Ia = 0
Vb = (Zf + Zg )Ib + Zg Ic (2.33)
Vc = (Zf + Zg )Ic + Zg Ib
These boundary conditions are transformed from the a-b-c system to the
0-1-2 coordinate system and this results in
Vb − Vc = Zf (Ib − Ic ) (2.38)
or
Va1 − Zf Ia1 = Va2 − Zf Ia2 (2.41)
Because Equation (2.42) and Equation (2.46) are equal, we can collect
terms and write
2Va0 − 2Zf Ia0 − 4Zg Ia0 = Va1 + Va2 − Zf (Ia1 + Ia2 ) − 2Zg (Ia1 + Ia2 )
(2.47)
By using Equation (2.41) and the property that Ia1 + Ia2 = −Ia0 , we find,
after rearranging, that
Vf
Ia1 = (2.49)
(Z2 + Zf ) Z0 + Zf + 3Zg
Z1 + Zf +
Z0 + Z2 + 2Zf + 3Zg
F1 Ia1 F2 Ia 2 F0 Ia 0
+ + + +
Z1 Zf Z2 Zf Z0 Z f + 3Z g
Vf Va1 Va 2 Va 0
− − − −
N1 N2 N0
and
Va1 = Vf − Z1 Ia1 (2.50)
Z2 Z0 /(Z2 + Z0 )
Va = 3Va1 = 3Vf (2.51)
Z2 Z0
Z1 +
(Z2 + Z0 )
The ratio between the voltage across the first clearing pole and the phase
voltage of the undistorted power system is called the first-pole-to-clear
(FPTC) factor
Va Z2 Z0
FPTC = =3 (2.52)
Vf Z1 (Z2 + Z0 ) + Z2 Z0
with an isolated neutral, this is two times the FPTC factor, which is three
times the phase voltage.
For solidly grounded systems, Zn = 0, and the expression for the FPTC
factor becomes
3X0
FPTC = (2.54)
X + 2X0
When X has a larger value then X0 , the FPTC factor is smaller than one.
For cases in which X = X0 , the FPTC factor for solidly grounded systems
is one, and in an undamped situation, the peak of the TRV for the first
clearing pole is twice the crest value of the system phase voltage.