You are on page 1of 4

LOW IMPEDANCE RESTRICTED EARTH FAULT PROTECTION

P. Bertrand, B. Gotzig, C. Vollet

Schneider Electric, France

1NTRODU.CTION
The need for sensitivity is half the maximum earth-
In a nowadays competitive environment, investments fault current on delta side, but much more on star
must have a minimum global cost. For protection relays, side.
as for any other electrical device, users need standard,
packaged solutions, with a minimum engineering study. The need for sensitivity of an earth-fault protection
system is based on the maximum earth fault current,
Restricted earth fault (REF) protection, as other limited by the grounding impedance. This value may be
protections, is a good candidate because it needs' no time much lower than the rated current of the transformer.
grading study. Recent evolution in computer relaying
have made this protection available in a multi-functional When a phase-to-earth fault occurs in a star-connected
device for transformer application. In such an winding, at a distance of x% from the neutral point, the
implementation a low impedance principle in used. No value of the fault current is x% of the maximum earth-
extemal stabilising resistor nor class X CTs are needed, fault.
making the installation of the protection straightforward.
For protecting 90% of the ,transformer winding, the
It is thus possible to build a fully packaged cubicle for sensitivity of the earth-fault detection must be set to 10%
transformer protection, 'including CTs and multi- of the maximum earth-fault current, as limited by the
functional relay giving improved transformer protection neutral impedance.
thanks to a REF protection.
In general, the earth-fault detection .level of a
transformer differential protection is not sufficient.
WHY TRANSFORMER EARTH-FAULT
PROTECTION MUST BE IMPROVED A power transformer is very often protected by a
transformer differential protection (87T), which measures
The detection of transformer internal fault must be primary and secondary phase currents. Such a protection
fast in order to avoid tank explosion or fire. detects any fault occurring inside the transformer and is
particularly efficient for interkm fault detection
The tripping time of an earth-fault protection system (Bertrand et al., (1) & (2)).
using only residual over-current relays may be very long,
due to time-grading . In case of a phase-to-earth fault, it is important to know
more about its basics.

When comparing the primary and the secondary current,


it is first of all necessary to take into account the winding
connection and to carry out a compensation. Three
different methods may be used ; they are explained in
Table 1 in the case of a delta-star transformer. These
methods are also chosen in order to provide zero
sequence current compensation in case of an earth fault
occurring outside the protected zone.

After compensation, the relay computes the differential


current (Id) and the through current (It). The latter inay be
obtained in different ways ; we have considered here the
maximum value between primary and secondary currents.
Figure 1 : a typical definite time elf protection system for
an industrial network. Insulation faults in the transformer The differential protection trips when both of the
are cleared within 1.3s ! following conditions are satisfied :

Developments in Power System Protection, Conference Publication No.479 0 IEE 2001. 479
Id exceeds a threshold, usually set to about 30% of In a system where the neutral impedance has been
the transformer rated current designed so that the maximum earth-fault current is
IdIt exceeds a threshold, (the slope of the sufficiently high (more than 50% of the transformer rated
characteristic)here set at 30% current), the REF protection will then ensure effective
protection of the transformer.
Table 1 shows that the earth-fault current must exceed 0.3
to 0.74 times the transformer rated current to be detected. Due to its unit protection characteristic, the REF relay
In many cases, this is not satisfactory. trips instantaneously. A tripping time of 40 ms is a
common value for digital relays

REF PRINCIPLE
BACK TO THE PAST :DESIGNING A HIGH
IMPEDANCE PROTECTION
The REF typically protects the star winding of
transformer where the neutral point is earthed. It
measures the four cyrrents flowing to the star point - one The basic principle is bright and simple ...
neutral and three phase currents.
The stabilising resistor forces the false differential current
When an earth fault occurs inside the protected zone, the to flow outside the differential circuit.
differential current - sum of these four currents - appears.
...but the design of the protection needs engineering
Due to its unit protection characteristic, the REF forces ...
protection does not need any time grading, hence it is fast
and, furthermore,.sensitive. In order to find the rate of the stabilising resistor, the
value of the wiring impedance must be estimated. The
sizing of the CT depends on the value of the resistor. This
means that the complete engineering study of the
protection must be achieved before ordering the
switchgear panel.

... and the protection brings high voltage and heat


dissipation in the cubicle.

data :
transformer : 20 MVA
1 1 kV
Rct CT: 1250/5
Rct = 2 . 4 0
RW wiring: R w = 0 . 7 ~
resistor : Rs = 2200

short-circuit current :
3-phase : 8.7 kA
ph/earth : 3 kA
Figure 2 : The REF protection is sensitive to the phase-to-
protection :
earth faults inside the protected transformer winding setting: 10%

HOW REF IMPROVES TRANSFORMER


PROTECTION

A REF protection may be as sensitive as 5% of the CT Moreover, high impedance protection needs a
rated current. comfortably sized CT winding for its own.
This limit is due to CT accuracy. For usual protective When an internal fault occurs, CTs are forced into
current transformers class 5P,the maximum error at rated saturation, which could lead other protections sharing the
current is +/- 1% (IEC, (3)) ; hence, under normal same CT core to an unwanted behaviour.
balanced load conditions, a false differential current may
appear, which must not exceed the threshold of the relay.

480
DESCRIPTION OF THE SCHNEIDER'S LOW
IMPEDANCE SOLUTION When a three-phase fault occurs outside the protected
zone, the phase CTs may saturate ; as seen in the previous
With its digital, multi-functional Sepam relay range, case, Ir = Id and the stability of the protection is ensured.
Schneider Electric has developped a low impedance REF
protection. In case of a phase-to-earth fault with a long DC time
constant (inductive earthing system), leading the phase
The basic principle is to compare the residual current CT into saturation, the problem is more difficult : Id
to the differential current. increases, Ir decreases and the operating point may reach
the tripping zone.
The differential current is given by : Id = Ia+Ib+Ic-In
(phase currents are considered positive when flowing to The stability is achieved by increasing the stabilising
the transformer, neutral current is considered positive current as soon as an external fault is detected
when flowing to the earth). When a fault occurs inside the
protected zone, the differential current is equal to the An external fault is detected as soon as the following
current flowing to the earth. When the fault is located conditions become valid :
outside the protected zone, the differential current is zero, the residual current.exceeds the seking (Ir > Ido)
as long as the CT errors remains low. and remains lower than the.differentia1 current (Ir < Id)

In order to compensate the CT errors and to ensure the From that moment, the restraint current of the protection
stability of the protection in case of an external fault, a is increased in order to guarantee the stability of the
restraint quantity is chosen equal to the residual current : protection : Ir (external fault) = Ia+Ib+Ic+In/3
Ir = Ia+Ib+Ic
Thanks to the stabilising element, the relay does not
The Sepam REF protection is a percentage differential need specific CTs to work properly.
protection ; it trips when both of the following conditions
are satisfied : The general CT sizing rule is 5P20, according to IEC (3).
Id exceeds the Ido threshold, adjustable between 5
and 50% of the transformer rated current With the additional external fault detection system
IdIt exceeds 1.05 (a fixed threshold ) described above, the sizing of the CTs must ensure
correct measurement during the first cycle of the fault.

t Id = la+Ib+lc+In
/ In case of an external phase-to-earth fault, this constraint
can be expressed in terms of CT saturation current (Isat)
with the following rules, where Ief is the maximum value
of the current flowing through the earthing impedance of
the transformer :
REF located on the primary (source side) : Isat > 0.8 Ief
REF located on the secondary (load side) : Isat > 2.4 Ief
Ir = la+Ib+Ic The two requirements differ because on the source side,
only one third of the neutral point current flows into the
Figure 4 : Sepam REF tripping characteristic phase CTs.

This principle ensures good stability in case of CT It can be seen that, with 5P20 CTs, the rules are always
saturation on the source side. valid, except when the REF is located on the secondary
winding and the limited earth-fault current exceeds 8x the
If we consider a REF protection located on the primary phase CT rated current. This case is usually encountered
side of the transformer, one of the requirement is to on LV networks only.
ensure stability during transformer energisation.
Because of the DC component of the inrush current, the In the case of an external two-phase-to-earth fault, the
phase CT saturate, causing a false differential current. fault current is limited by the short-circuit impedance of
As no current flows through the neutral point, Ir = Id and the transformer. Many simulations and tests with 5P20
the Sepam REF protection remains stable (no trip). CTs have shown the protection's stability.

On the load side, an extra restraint element is needed. A limit appears when the maximum 3-phase short-circuit
current at the secondary side of the transformer exceeds
We now consider a REF protection located on the 13x the phase CT rated current. This means that the short
secondary winding of the transformer.

481
circuit voltage of the transformer, USC,is below 8%. In compensated by the current flowing to the earthing coil,
that case, the CT sizing rule becomes : so that the earth-fault current can have very low values.
Isat > 22x transformer rated current.
And this additional rule has been tested with transformer Using such an earthing system, a REF protection may not
USC values as low as 4%. be sensitive enough to detect the fault. Furthermore the
REF protection principle described above is not adapted :
in case of an intemal fault, Ir, the total network capacitive
ADVANTAGES O F THE SEPAM REF current, will exceed Id, the earth fault, and the protection
PROTECTION AND LIMIT OF ITS USE will not trip.

But it must be kept in mind that the low impedance


The low impedance principle described above has two REF overcomes the main disadvantages of the
limitations. traditional high impedance solution.
The first limitation is that it cannot be used on a three-CT And, when this solution is included into a Sepam multi-
arrangement :' In case of an internal fault, as the neutral functional relay, it improves the protection scheme for
point is not connected to earth, the differential current is little cost and effort !
equal to the residual current and the protection does not
detect the fault. BIBLIOGRAPHY
This arrangement appears on the primary side of a power
1. Bertrand P, Martin E, Guillot M, 1997, "Neural
transformer, when the neutral point may or may not be networks, a mature technique for protection relays",
grounded, depending on the exploitation constraints.
CIRED 97
2. Bertrand P, Devalland A, Bastard P, 1993, "A
In-that case, an additional elf protection must enabled simulation model for transformer,intemal faults, base for
when the neutral switch is opened. As a second harmonic the study of protection and monitoring systems", CIRED
restraint is available for this elf protection, stability 93
during transformer energisation is ensured. -
3. Schiel L, "Stromdifferentialschutzanordnungf i r einen
Transformator", Europaische Patentschrift EP 0758497B1
The second limitation concerns its use with compensated 4. 1996, IEC 60044-1 Instrument transformers - Part 1 :
earthing systems. In such systems, the residual capacitive Current transformers
current appearing when an earth-fault occurs is
star-delta zero-sequence neutral-point current
compensation elimination elimination. Scheil(3)
1a'-Ib'
Ja'= -
Ja' = Ia'
J5
Ib'-Ia'
Jb'= Ib' Jb'= -
9 Jc' = IC'
Js
IC'-Ia'
Jet= -
J5
Ia - Ic
M
Jb Jc Ja = -
If Ja
Ia + Ib+ Ic
compensation
Js Ja = Ia -
3
In
Ja = Ia--
3
Ib-Ia
a=- Ia + Ib + Ic In
0 IIa Ib IC J5 Jb=Ib-
3
Jb=b--
3
IC-%
0 JC= - Ia + Ib+ Ic In
Js JC= IC-
3
JC=IC--
3
Value of the differential and through Id =
:urrents (Id & It)
y6 Id=%lf Id = If
It = II+ %If
[f : fault current
[l : load current
It = II+ y& It = Il+%lf
note : the source i!
connected to the delta side
Fault current detected - at no load 0.52 0.45 0.30
- at rated load 0.74 0.64 0.38
note : settings as indicated in the text of the document
.tive enough for earth ault detection. A F E
protection must be added.

482

You might also like