www.hilti.ca Profis Anchor 2.7.

1
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 09/07/2018
E-Mail:

Specifier's comments:

1 Input data
Anchor type and diameter: HIT-HY 200 + HIT-Z 1/2
Effective embedment depth: hef,opti = 70 mm (hef,limit = 93 mm)
Material: DIN EN ISO 4042
Evaluation Service Report: ESR-3187
Issued I Valid: -|-
Proof: Design method CSA A23.3-14 / Chem.
Stand-off installation: eb = 0 mm (no stand-off); t = 20 mm
Anchor plate: lx x ly x t = 508 mm x 458 mm x 20 mm; (Recommended plate thickness: not calculated
Profile: Square HSS (AISC); (L x W x T) = 305 mm x 305 mm x 6 mm
Base material: cracked concrete, fc' = 17.24 N/mm2; h = 150 mm, Temp. short/long: 20/20 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < 15M bar

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ca Profis Anchor 2.7.1
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 09/07/2018
E-Mail:

2 Load case/Resulting anchor forces y


Load case: Design loads
1 2
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y Tension
1 0.999 1.675 0.167 -1.667
2 0.405 1.675 0.167 -1.667 3 x 4
3 0.653 1.675 0.167 -1.667
4 0.059 1.675 0.167 -1.667
5 0.306 1.675 0.167 -1.667
6 0.000 1.675 0.167 -1.667 5 6
max. concrete compressive strain: 0.03 [‰]
max. concrete compressive stress: Compression
0.86 [N/mm2]
resulting tension force in (x/y)=(-131/68): 2.423 [kN]
resulting compression force in (x/y)=(160/-172): 12.423 [kN]

3 Tension load
Load Nf [kN] Capacity Nr [kN] Utilization bN = Nf/Nr Status
Steel Strength* 0.999 35.405 3 OK
Pullout Strength* 0.999 31.620 4 OK
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 2.423 18.200 14 OK
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


Ns,uta = Ase futa = ESR value refer to ICC-ES ESR-3187
Nsar = Ase f s futa R CSA A23.3-14 Eq. D.2
Nsar ≥ Nfa CSA A23.3-14 Table D.1

Variables
n Ase,N [mm2] futa [N/mm2]
1 92 649.48
Calculations
Ns,uta [kN]
59.504
Results
Ns,uta [kN] fs R Nsar [kN] Nfa [kN]
59.504 0.850 0.700 35.405 0.999

3.2 Pullout Strength


Ncpr,A = ESR value refer to ICC-ES ESR-3187
Ncpr = y c,p Ncpr,A f c l a R CSA A23.3-14 Eq. D.15
Ncpr ≥ Nfa CSA A23.3-14 Table D.1

Variables
y c,p la Ncpr,A [kN]
1.000 1.000 48.646
Calculations
-
-
Results
y c,p l a Ncpr,A [kN] fc R Ncpr [kN] Nfa [kN]
48.646 0.650 1.000 31.620 0.999

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ca Profis Anchor 2.7.1
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 09/07/2018
E-Mail:

3.3 Concrete Breakout Strength

Ncbgr = (AA ) y
Nc
Nc0
ec,N y ed,N y c,N y cp,N Nbr CSA A23.3-14 Eq. D.4
Ncbgr ≥ Nfa,g CSA A23.3-14 Table D.1
ANc see CSA A23.3-14, Part D.6.2.1, Fig. D.7
ANc0 = 9 h2ef CSA A23.3-14 Eq. D.5

( )
1
y ec,N = 2 e'N ≤ 1.0 CSA A23.3-14 Eq. D.8
1+
3 hef
y ed,N = 0.7 + 0.3 ( ca,min
1.5hef )
≤ 1.0 CSA A23.3-14 Eq. D.11

y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 CSA A23.3-14 Eq. D.13
1.5
Nbr = kc f c l a √fc hef R
'
CSA A23.3-14 Eq. D.6

Variables
hef [mm] e'1,N [mm] e'2,N [mm] ca,min [mm] y c,N
70 88 38 ∞ 1.000

cac [mm] kc la f'c [N/mm2]


133 7.0 1.000 17.24

Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N
182120 43911 0.542 0.734 1.000 1.000
Results
fc R Nbr [kN] Ncbgr [kN] Nfa,g [kN]
0.650 1.000 11.028 18.200 2.423

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ca Profis Anchor 2.7.1
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 09/07/2018
E-Mail:

4 Shear load
Load Vf [kN] Capacity Vr [kN] Utilization bV = Vf/Vr Status
Steel Strength* 1.675 14.466 12 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Concrete Breakout 10.050 107.263 10 OK
Strength controls)**
Concrete edge failure in direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength


Vs,uta = ESR value refer to ICC-ES ESR-3187
Vsar = 0.6 Ase,V f s futa R CSA A23.3-14 Eq. D.31
Vsar ≥ Vfa CSA A233-14 Table D.1

Variables
n Ase,V [mm2] futa [N/mm2]
1 92 649.48
Calculations
Vs,uta [kN]
26.182
Results
Vs,uta [kN] fs R Vsar [kN] Vfa [kN]
26.182 0.850 0.650 14.466 1.675

4.2 Pryout Strength (Concrete Breakout Strength controls)

Vcpgr = kcp [(AA ) y


Nc
Nc0
ec,N ]
y ed,N y c,N y cp,N Nbr R CSA A23.3-14 Eq. D.45
Vcpgr ≥ Vfa,g CSA A23.3-14 Table D.1
ANc see CSA A23.3-14, Part D.6.2.1, Fig. D.7
ANc0 = 9 h2ef CSA A23.3-14 Eq. D.5

( )
1
y ec,N = 2 e'N ≤ 1.0 CSA A23.3-14 Eq. D.8
1+
3 hef
y ed,N = 0.7 + 0.3 ( ca,min
1.5hef )
≤ 1.0 CSA A23.3-14 Eq. D.11

y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 CSA A23.3-14 Eq. D.13
1.5
Nbr = kc f c l a √fc hef R
'
CSA A23.3-14 Eq. D.6

Variables
kcp hef [mm] e'1,N [mm] e'2,N [mm] ca,min [mm]
2 70 0 0 ∞

y c,N cac [mm] kc la f'c [N/mm2]


1.000 133 7.0 1.000 17.24

Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N
213552 43911 1.000 1.000 1.000 1.000
Results
fc Nbr [kN] Vcpg [kN] R Vcpgr [kN] Vfa,g [kN]
0.650 11.028 107.263 1.000 107.263 10.050

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ca Profis Anchor 2.7.1
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 09/07/2018
E-Mail:

5 Combined tension and shear loads


bN = Nf/Nr bV = Vf/Vr Utilization bN,V [%] Status
0.133 0.116 21 OK
bNV = (bN + bV) / 1.2 <= 1

6 Warnings
• Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!

Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Condition A applies when supplementary reinforcement is used. The R factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
• Checking the transfer of loads into the base material is required in accordance with CSA A23.3!
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. CSA A23.3-14 Annex
D, Clause D.10.1

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ca Profis Anchor 2.7.1
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 09/07/2018
E-Mail:

7 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-HY 200 + HIT-Z 1/2
Profile: Square HSS (AISC); 305 x 305 x 6 mm Installation torque: 0.040 kNm
Hole diameter in the fixture: df = 14 mm Hole diameter in the base material: 14 mm
Plate thickness (input): 20 mm Hole depth in the base material: 95 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 127 mm
Drilling method: Hammer drilled
Cleaning: No cleaning of the drilled hole is required

7.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • No accessory required • Dispenser including cassette and mixer
• Properly sized drill bit • Hilti seismic filling set
• Torque wrench
y

254 254

79
1 2

229
150

3 4 x
150

229

5 6
79

42 425 42

Coordinates Anchor mm
Anchor x y c-x c+x c-y c+y Anchor x y c-x c+x c-y c+y
1 -213 150 - - - - 4 213 0 - - - -
2 213 150 - - - - 5 -213 -150 - - - -
3 -213 0 - - - - 6 213 -150 - - - -
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ca Profis Anchor 2.7.1
Company: Page: 7
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 09/07/2018
E-Mail:

8 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan