Basi Calculation For Pump Tank Selection
Basi Calculation For Pump Tank Selection
9000
gpm
34065
34
litres
m3
45000
gpm
170325
litres
m3
3) SPRINKLER SYSETM
Sprinkler spacing will be 3.6 meters
design density will be 0.15gpm/ft2(Ordinary Hazard)
area will be 1500 ft2 to be assumed as fire zone
1500 x 0.15 = 225 gpm
Total capacity will be 225gpm...
Sprinkler Water Storage Capacity (for Ordinary Hazard Area)
= 225 gpm * 1 No * 90 Mins
1 galloons = 3.785 litres
20250
1 OF 28
gallons
Total storage volume required = 20250 gallons * 3.785
76646
77
litres
m3
4) WET RISER
Wet Riser(Landing Valve) Flow rate = 250 gpm
Max No of WR in operation at any time = 1 No
Duration of operation = 90 mins Ordinary hazard II (e.g Public)
Fire hydrant TANK STORAGE CAPACITY (for Ordinary Hazard Area)
= 250 gpm * 1 No * 90 Mins
22500
gpm
85163
85
litres
m3
and in-racks
2) If rack sprinklers are provided, then the flow rate and number of sprinklers
will vary
TANK CAPACITY
PUMP CAPACITY
FHR
FH
SPRINKLER
SAFETY FACTOR
11 m3
28 m3
34 m3
7 m3
TOTAL
80 m3
FHR
FH
SPRINKLER
HOSE STREAM
SAFETY FACTOR
TOTAL
2 OF 28
100 GPM
250 GPM
300 GPM
50 GPM
50 GPM
750 GPM
1
1.1
a)
b)
3 OF 28
c)
SPRINKLER SYSETM
Accordance with NFPA 13. Maximum hazard 1500sq.feet will be occur in Ordinary
hazard
Sprinkler spacing will be 3.6 meters
design density will be 0.15gpm/ft2
1500 x 0.15 = 225 gpm
Total capacity will be 225gpm...
Residual Pressure required at Sprinkler
= 3.5 Bar
Pressure loss in pipe/fittings etc = 0.5 bar
Safety
= 0.5 bar
Total head pressure required
= 4.5bar Minimum.
NOTE:-
WET RISER
Accordance with NFPA 13.
Wet Riser(Landing Valve) Flow rate = 250 gpm
Max No of WR in operation at any time = 1 No
Pump flow rate required
= 1 x 250 gpm = 250 gpm
Fire hose reel pump Head calculation
Residual Pressure required at WR
= 4.5 Bar
Pressure loss in pipe/fittings etc = 1.5 bar (assumed, larger length of pipe needs
more pressure)
Safety
= 0.5 bar
Total head pressure required
4 OF 28
e)
Table
ITEM
FHR
FH
SPRINKLER
LANDING VALVE
HOSE STREAM( 5%)
SAFETY FACTOR(5%)
TOTAL
100 GPM
500 GPM
225 GPM
250 GPM
54 GPM
56 GPM
1185 GPM
1.2
a)
9000
= 9000 gallons (Minimum)
5 OF 28
gpm
b)
45000
gpm
22500
gpm
SPRINKLER SYSETM
Sprinkler spacing will be 3.6 meters
design density will be 0.15gpm/ft2(Ordinary Hazard)
area will be 1500 ft2 to be assumed as fire zone
1500 x 0.15 = 225 gpm
Total capacity will be 225gpm...
Sprinkler Water Storage Capacity (for Ordinary Hazard Area)
= 225 gpm * 1 No * 90 Mins
1 galloons = 3.785 litres
Total storage volume required = 20250 gallons * 3.785
TOTAL STORAGE TANK VOLUME
d)
WET RISER
Wet Riser(Landing Valve) Flow rate = 250 gpm
Max No of WR in operation at any time = 1 No
Duration of operation = 90 mins Ordinary hazard II (e.g Public)
Fire hydrant TANK STORAGE CAPACITY (for Ordinary Hazard Area)
= 250 gpm * 1 No * 90 Mins
Total storage volume required = 22500 gallons (Minimum)
1 galloons = 3.785 litres
Total storage volume required = 22500 gallons * 3.785
TOTAL STORAGE TANK VOLUME
6 OF 28
e)
e)
Table
ITEM
FHR
FH
SPRINKLER
LANDING VALVE
WATER MIST SYSTEM
TOTAL
CAPACITY (M3)
34 M3
170 M3
77 M3
85 M3
28 M3
394 M3
7 OF 28
SIMON ENGG. PARTNERS
8 OF 28
rs for overhead and in-racks
9 OF 28
34065
34
litres
m3
10 OF 28
170325
170
litres
m3
20250
gallons
76646
litres
77
85163
85
m3
litres
m3
11 OF 28
28000
28
litres
m3
12 OF 28
PROJECT NO: 1091
PROJECT NAME:
PUMP POWER
BHP
SAMPLE CALCULATION
750 GPM * 93 * 1
3960 * 0.7
69750
2772
25.16
18872
19
1 hp = 750 Watts
1)
140800
2772
50.79
1 hp = 750 Watts
38095
=
2)
38
UTILITY PUMP FOR PASFR ADMIN BUILDING
For total loading unit of 8 corresponding design flow rate is =
6 Litre / Sec
360
95.11
95 GPM * 192 * 1
3960 * 0.7
18240
2772
3)
6.58
4935
SUMP PUMP
15 GPM * 200 * 1
3960 * 0.7
=
3000
2772
1.08
812
0.812
D (Feet) * SP GRAVITY
P EFFICIENCY
SP GRAVITY
hp
Watts
kW
110
352
meter
feet
hp
Watts
kW
6 l/s
Litre / Mins
gallons / min
60
192
meter
feet
200
hp
Watts
kW
feet
PECIFIC GRAVITY OF LIQUID
ORMAL WATER = 1
Each pump can discharge 120 lpm @ 120 bar pressure
Hence no. of pump required = 316.8/120 = 2.6 ~ 3 nos.
Each Motor Drive 1 pump, hence we choose main 3x120 L/min + stand by 1x120 L/min.
Total
pump capacity on duty of 360 lpm @ 120 bar + 120 lpm @ 120 bar stand by, utilizing
4 nos. Of
30 kW electric driven motor.
Water Tank for 360 lpm with 30 minutes operation = 360 x 30 minute = 10800 litre
effective
water capacity, therefore water tank capacity with 20% allowance which is of 12960
litre shall
be the minimum water capacity.
ng 4 nos. Of
WET RISER
Wet Riser(Landing Valve) Flow rate = 250 gpm
Max No of WR in operation at any time = 1 No
Duration of operation = 90 mins Ordinary hazard II (e.g Public)
Fire hydrant TANK STORAGE CAPACITY (for Ordinary Hazard Area)
= 250 gpm * 1 No * 90 Mins
22500
gpm
45000
PUMP POWER
BHP
SAMPLE CALCULATION
750 GPM * 93 * 1
3960 * 0.7
69750
gpm
2772
=
25.16
hp
18872
19
Watts
kW
1 hp = 750 Watts
67500
85163
85
170325
litres
m3
litres
170
m3
255
m3
BASIC CALCULATION FOR PUMP & TANK SELECTION
The following are the design considered based on NFPA 13 / 14 & 24
1) FIRE HOSE REEL SYSETM
FHR Flow rate = 50 gpm
Max No of FHR in operation at any time = 2 Nos
Duration of operation = 90 mins Ordinary Hazard- II (e.g Public )
Fire hose reel TANK STORAGE CAPACITY (for Ordinary Hazard Area)
= 50 gpm * 2 No * 90 Mins
Total storage volume required
1 galloons = 3.785 litres
9000
gpm
34065
34
litres
m3
45000
gpm
170325
170
Pump flow rate required
= 2 x 250 gpm = 500 gpm
Fire hose reel pump Head calculation
Residual Pressure required at FHR
= 4.5 Bar
Pressure loss in pipe/fittings etc = 1.5 bar (assumed, larger length of pipe needs
more pressure)
Safety
= 0.5 bar
Total head pressure required
4) WET RISER
Wet Riser(Landing Valve) Flow rate = 250 gpm
Max No of WR in operation at any time = 1 No
Duration of operation = 90 mins Ordinary hazard II (e.g Public)
Fire hydrant TANK STORAGE CAPACITY (for Ordinary Hazard Area)
= 250 gpm * 1 No * 90 Mins
22500
25 OF 28
gpm
litres
m3
1 galloons = 3.785 litres
Total storage volume required = 22500 gallons * 3.785
85163
85
litres
m3
and in-racks
2) If rack sprinklers are provided, then the flow rate and number of sprinklers
will vary
TANK CAPACITY
PUMP CAPACITY
FHR
FH
SAFETY FACTOR
11 m3
28 m3
7 m3
TOTAL
80 m3
FHR
FH
HOSE STREAM
SAFETY FACTOR
TOTAL
100 GPM
250 GPM
50 GPM
50 GPM
750 GPM
1
1.1
a)
b)
e)
Table
ITEM
FHR
FH
HOSE STREAM( 5%)
SAFETY FACTOR(5%)
TOTAL
ore pressure)
SAMPLE CAL
750 GPM * 93 * 1
3960 * 0.7
60450
2772
25.16
hp
18872
19
Watts
kW
1 hp = 750 Watts